Page 37 of 40
3.0
APPENDIX 3
Programming Parameters for CUB5B counter/rate meter fitted to Breeze
machines
– Breeze Serial Numbers 0121 Onwards
The device must be wired and installed into the machine prior to
programming.
Breeze is fitted with C-M-DEV-CUB5B, backlight version
The DIP switch positions are as follows:
1
OFF
2
OFF
3
OFF
4
OFF
Please see the attached CUB5 Programming Overview attached to
this document.
Press and hold SEL for 2 seconds to enter programming mode
Enter the Pro-Code
– 111 by pressing RST to change
numbers and SEL to skip to the next number.
Once correct Press and Hold SEL for 2 seconds
Pro-no should now be flashing, press RST
Press RST to move through the various sections 1-input, 2-
rate 3-dsplay, sections 4 and 5 will be unavailable, see the
next page of instructions for the parameters required.
Press SEL to enter that section
To change the value of a parameter press RST
Press SEL to move to the next parameter (You will have to
hold for 2 seconds on certain parameters).
When all the parameters in the section have been scrolled
through you will return to the Pro-no display, press RST to
scroll to another section else press SEL to exit programming
mode.