VRC2100 Vending Reader
15
Installation Guide
The following settings will appear only if the
PROX Sent as
setting
is set to
ASC
(ASCII).
Note:
Contactless support on the VRC2100 was extended in version
1.04.05 to support 128-bit cards.
DCD Start Pos:
Set to match the number of leading parity bits and
“custom” bits, if any, transmitted by the cards being used with this
reader. This selects the number of bits (0 – 32) to eliminate to the left
of the card data. For example, 26-bit Wiegand cards would set this to
1 for one leading parity bit.
Acct # Bits:
Set to match the number of bits transmitted by the
contactless card as the ID field. This selects the number of bits
(0 – 64) after the parity bit(s) of the contactless card data to be used
as the ID portion.
FC # Bits Setting:
Set to match the number of bits transmitted by
the contactless card as the
Facility Code
field. This selects the
number of bits (0 – 32) to be used as the facility code.
Acct # Digits Setting:
Set to the number of characters to be sent to
the host as the account number portion of the contactless card. This
selects how many digits (0 – 20) will be sent to the host for the
account number. Leading zeros will be added if necessary.
FC # Digits Setting:
This setting indicates how many digits will be
sent to the host for the facility code (0 –10). Additional zeros will be
padded at the beginning, if necessary.
Free Vend:
When you arrive at this option, press
CHG
to send a
$10.00 credit to the VMC for the purpose of testing MDB
compatibility. Select an item to complete the test. After the item is
dispensed, or after a 60-second timeout, the VRC2100 will complete
the transaction and leave the Free Vend mode. No accounts are
involved and no card data is sent. This is strictly a local function for
testing compatibility with the MDB bus.
MDB BUS Address:
This option sets the Multi-drop Bus Address,
either 0x10 or 0x60.The default setting is
0x10
.