background image

COOLING OPERATION

This product utilizes a 2-stage cooling indoor thermostat. With a
call for first stage cooling (Yl), the outdoor fan and low capacity
compressor are energized. If low capacity cannot satisfy cooling
demand, high capacity is energized (Yl and Y2 or just Y2) by the
second stage of indoor thermostat. After second stage is satisfied,
the unit returns to low-capacity operation until first stage is
satisfied or until second stage is required again. When both first
stage and second stage cooling are satisfied, the compressor will
shut off.

NOTE:

If unit has not operated within the past 12 hr, or following

a unit power-up, upon the next thermostat high- or low-speed
demand, unit operates for a minimum of 5 minutes on high speed.

NOTE:

Outdoor fan motor will continue to operate for one

minute after compressor shuts off, when outdoor ambient is greater
than 100°F.

NOTE:

When two-speed unit is operating in low-capacity cool-

ing, system vapor (suction) pressure will be higher than a standard
single-speed system or high-speed operation. This normal opera-
tion is due to the reduced capacity operating with typically larger
indoor and outdoor coils.

HEATING OPERATION

This product utilizes a 3-stage heating indoor thermostat. With a
call for first stage heating (Y1), the outdoor fan and low capacity
compressor are energized. If low capacity cannot satisfy heating
demand, high capacity is energized (Y1 and Y2) by the second
stage of the indoor thermostat. Auxiliary or back up heat is
controlled by third stage (W1). After second stage of heat is
satisfied, the unit returns to low capacity operation until first stage
is satisfied or until second stage is required again. When both first
stage and second stage heating are satisfied, the compressor will
shut off.

NOTE:

If unit has not operated within the past 12 hr, or following

a unit power-up, upon the next thermostat high- or low-speed
demand, unit operates for a minimum of 5 minutes on high speed.

STATUS FUNCTION LIGHTS

A system control STATUS function light is located on the outdoor
unit control board. (See Fig. 14.) The STATUS light provides
indication signals for several system operations. See Table 4 for
codes and definitions. Table 4 also provides the order of signal
importance.

NOTE:

Only one code will be displayed on the outdoor unit

control board (the most recent, with the highest priority).

FACTORY DEFAULTS

Factory defaults have been provided in the event of failure of
outdoor air thermistor and/or outdoor coil thermistor. Refer to
Table 6 for default and function.

ONE MINUTE SPEED CHANGE TIME DELAY

When compressor changes speeds from high to low or low to high,
there is a 1-minute time delay before compressor restarts. The
outdoor fan motor remains running.

COMPRESSOR OPERATION

When the compressor operates in second stage operation, the
motor rotates clockwise. Both the lower and upper pistons are
eccentric with the rotating crankshaft, and both compress refrig-
erant. When the compressor operates in single stage operation the
motor reverses direction (rotates counter-clockwise). The lower
piston becomes idle and the upper piston compresses refrigerant.
During single capacity operation the “start” and “run” wind-
ings are reversed.

Table 3—Required Liquid-Line Temperature (°F)

LIQUID PRESSURE AT

SERVICE VALVE

(PSIG)

REQUIRED SUBCOOLING TEMPERATURE

(°F)

5

10

15

20

174

56

51

46

41

181

58

53

48

43

188

61

56

51

46

195

63

58

53

48

202

65

60

55

50

209

67

62

57

52

216

69

64

59

54

223

71

66

61

56

230

73

68

63

58

237

75

70

65

60

244

77

72

67

62

251

79

74

69

64

258

81

76

71

66

265

82

77

72

67

272

84

79

74

69

279

86

81

76

71

286

88

86

78

73

293

89

84

79

74

300

91

86

81

76

307

93

88

83

78

314

94

89

84

79

321

96

91

86

81

328

97

92

87

82

335

99

94

89

84

342

100

95

90

85

349

102

97

92

87

356

103

98

93

88

363

105

100

95

90

370

106

101

96

91

377

107

102

97

92

384

109

104

99

94

391

110

105

100

95

398

112

107

102

97

405

113

108

103

98

412

114

109

104

99

419

115

110

105

100

426

117

112

107

102

433

118

113

108

103

440

119

114

109

104

447

120

115

110

105

454

122

117

112

107

461

123

118

113

108

468

124

119

114

109

475

125

120

115

110

482

126

121

116

111

489

127

122

117

112

496

129

124

119

114

503

130

125

120

115

510

131

126

121

116

517

132

127

122

117

524

133

128

123

118

531

134

129

124

119

538

135

130

125

120

545

136

131

126

121

552

137

132

127

122

559

138

133

128

123

566

139

134

129

124

573

140

135

130

125

580

141

136

131

126

587

142

137

132

127

594

143

138

133

128

601

144

139

134

129

608

145

140

135

130

8

Содержание WeatherMaker 38YDB

Страница 1: ...ing label Electrical shock can cause personal injury or death Puron R 410A systems operate at higher pressures than standard R 22 systems Be certain that service equipment is rated for R 410A Some R 2...

Страница 2: ...e of unit and 12 in on all remaining sides must be maintained Maintain a distance of 24 in between units Position so water snow or ice from roof or eaves cannot fall directly on unit On rooftop applic...

Страница 3: ...lizer tube 9 Connect equalizer tube of TXV to 1 4 in equalizer fitting on vapor line adapter 10 Attach TXV bulb to horizontal section of suction line using bulb strap provided See Fig 6C Insulate bulb...

Страница 4: ...o indoor section using accessory tubing package or field supplied refrigerant grade tubing of correct size and condition Tubing diameters listed in Table 1 are adequate for equivalent lengths up to 50...

Страница 5: ...d tight Step 8 Make Electrical Connections To avoid personal injury or death do not supply power to unit with compressor terminal box cover removed Be sure field wiring complies with local and nationa...

Страница 6: ...HV 58UXV or 58MVP gas furnace no LCC is required The LCC for standard PSC blower products consists of a standard humidistat which opens contacts on humidity rise and a pilot duty relay with 24v coil N...

Страница 7: ...are not equipped with Schrader valves To prevent personal injury make sure gage manifold is connected to the valve gage ports before moving valves off fully back seated position Wear safety glasses an...

Страница 8: ...ions See Table 4 for codes and definitions Table 4 also provides the order of signal importance NOTE Only one code will be displayed on the outdoor unit control board the most recent with the highest...

Страница 9: ...TROL MODEL RH See notes 1 2 3 6 9 and 10 A01421 O W2 W W1 Y1 W2 G R THERMIDISTAT CONTROL MODEL RH SINGLE STAGE FURNACE TWO SPEED HEAT PUMP W G Y C Y2 W1 R Y1 O C DHUM HUM B S1 S2 R C HEAT STAGE 3 COOL...

Страница 10: ...B S1 S2 R W2 O Y1 R COM HUM PL9 10 DEHUM HEAT STAGE 3 FURNACE COOL HEAT STAGE 1 COMPRESSOR LO COOL HEAT STAGE 2 COMPRESSOR HI RVS COOLING FAN 24 VAC HOT 24 VAC COMM RVS SENSING N A OUTDOOR SENSOR CON...

Страница 11: ...and wiring information 4 Non Programmable Model 2S01 B when used in heat pump installations jumper R19 NOT cut uses O W2 to control reversing valve 5 Furnace must control its own second stage operatio...

Страница 12: ...oses anytime after the 15 minute delay then resume operation on call for Y1 and or Y2 HEATING VAPOR PRESSURE SWITCH PressureGuard This outdoor unit is equipped with a heating vapor pressure limiting d...

Страница 13: ...ve User s Manual with owner Explain system operation and periodic maintenance requirements outlined in manual 4 Fill out Dealer Installation Checklist and place in customer file CARE AND MAINTENANCE F...

Страница 14: ...PNK YEL PNK YEL PNK BRN BRN BLK BLK BLK ORN RVS ORN RED BLU CH 11 21 23 23 YEL BLK BLK BLK CL 11 21 H C START COMP RELAY BRN CAP L2 L1 EQUIPGND DUALCAPACITY A B C D BLU BRN BRN BLK YEL BRN VPS BLK C O...

Страница 15: ...RSUPPLY TIME MIN DEFROST VH L 2 ODF CCH VC RED YEL BLK BLU BRN PL5 PL4 PL3 YEL BLU BRN YEL OCT OAT LPS HPS Fig 19 Wiring Diagram 060 A01420 CONNECTION DIAGRAM OCT t LPS HPS OAT t LO HI TO INDOOR UNIT...

Страница 16: ...1 38ydb3si Manufacturer reserves the right to discontinue or change at any time specifications or designs without notice and without incurring obligations Book 1 4 Tab 5a 5a PC 101 Catalog No 533 8004...

Отзывы: