background image

11. Route equalizer tube through suction connection opening

(large hole) in fitting panel and install fitting panel in place.

12. Sweat inlet of TXV, marked “IN,” to liquid line. Avoid

excessive heat which could damage valve.

13. Install vapor elbow (See Fig. 6B) with equalizer adapter to

vapor line of line set and vapor connection to indoor coil.
Adapter has a 1/4-in. male flare connector for attaching
equalizer tube. (See Fig. 6B.)

14. Connect equalizer tube of TXV to 1/4-in. equalizer fitting on

vapor line adapter. Use backup wrench to prevent damage to
equalizer fitting.

15. Proceed with remainder of unit installation.

LONG-LINE APPLICATIONS, INSTALL LIQUID-LINE
SOLENOID VALVE (LSV)

For refrigerant piping arrangements with equivalent lengths
greater than 50 ft or when elevation difference between indoor
and/or outdoor unit is greater than ± 20 ft, follow all requirements
of the Long-Line Guideline section in the Application Guideline
and Service Manual—Air Conditioners and Heat Pumps Using
Puron® Refrigerant. If required by Long-Line Application Guide-
line, install LSV kit P/N KHALS0401LLS specifically designed
for Puron® Heat Pump. LSV should be installed between filter
drier and indoor coil as close as possible to outdoor unit (within 2
feet). (See Fig. 12 for wiring diagram.) Follow the Installation
Instructions included with accessory kit.

IMPORTANT:

Flow arrow must point toward outdoor unit.

Step 7—Make Piping Connections

Relieve pressure and recover all refrigerant before system
repair or final unit disposal to avoid personal injury or death.
Use all service ports and open all flow-control devices,
including solenoid valves.

Do not leave system open to atmosphere any longer than
minimum required for installation. POE oil in compressor is
extremely susceptible to moisture absorption. Always keep
ends of tubing sealed during installation.

If ANY refrigerant tubing is buried, provide a 6 in. vertical
rise at service valve. Refrigerant tubing lengths up to 36 in.
may be buried without further special consideration. Do not
bury lines for lengths over 36 in.

Outdoor units may be connected to indoor section using accessory
tubing package or field-supplied refrigerant grade tubing of correct

size and condition. Tubing diameters listed in Table 1 are adequate
for equivalent lengths up to 50 ft. For tubing requirements beyond
50 ft, substantial capacity and performance losses will occur.
Follow the recommendations in the Application Guideline and
Service Manual—Air Conditioners and Heat Pumps Using Pu-
ron® Refrigerant to minimize losses.
Refer to Table 1 for field tubing diameters. Refer to Table 2 for
accessory requirements.

If refrigerant tubes or indoor coil are exposed to atmosphere, they
must be evacuated to 500 microns to eliminate contamination and
moisture in the system.

OUTDOOR UNIT CONNECTED TO FACTORY-APPROVED
INDOOR UNIT

These outdoor units are carefully evaluated and listed with specific
indoor coils for proper system performance.

IMPORTANT:

Do not apply to indoor coils that are not factory

approved combinations.

INSTALL ADAPTER TUBE

1. Remove plastic retainer holding outdoor piston in liquid line

service valve.

2. Check to be sure outdoor piston is properly installed in liquid

line service valve.

3. Locate plastic bag taped to unit containing adapter tube.

4. Remove Teflon washer from bag and install on open end of

liquid service valve.

5. Remove adapter tube from bag and connect threaded nut to

liquid service valve. Tighten nut finger tight and then with
wrench an additional 1/2 turn (15 ft-lb). DO NOT OVER-
TIGHTEN!

REFRIGERANT TUBING AND FILTER DRIER

Installation of filter drier in liquid line is required.

Connect vapor tubing to fittings on outdoor unit vapor service
valve. Connect liquid tubing to filter drier. (See Table 1 and Fig.
9.) Connect other end of filter drier to adapter tube on liquid line
service valve.

Fig. 7—Positioning of Sensing Bulb

A00399

SENSING BULB

STRAP

8  O'CLOCK

4  O'CLOCK

Table 1—Refrigerant Connections and

Recommended Liquid and Vapor Tube

Diameters (In.)

UNIT

LIQUID

VAPOR

VAPOR (LONG-LINE)

SIZE

Connection

Diameter

Tube

Diameter

Connection

Diameter

Tube

Diameter

Connection

Diameter

Tube

Diameter

024

3/8

3/8

5/8

5/8

5/8

3/4

036

3/8

3/8

3/4

3/4

3/4

7/8

037,048

3/8

3/8

7/8

7/8

7/8

7/8

060

3/8

3/8

7/8

1-1/8

7/8

1-1/8

Notes:
1. Tube diameters are for lengths up to 50 equivalent ft
2. Do not increase or decrease tubing sizes.

4

Содержание WeatherMaker 38YDB

Страница 1: ...ing label Electrical shock can cause personal injury or death Puron R 410A systems operate at higher pressures than standard R 22 systems Be certain that service equipment is rated for R 410A Some R 2...

Страница 2: ...e of unit and 12 in on all remaining sides must be maintained Maintain a distance of 24 in between units Position so water snow or ice from roof or eaves cannot fall directly on unit On rooftop applic...

Страница 3: ...lizer tube 9 Connect equalizer tube of TXV to 1 4 in equalizer fitting on vapor line adapter 10 Attach TXV bulb to horizontal section of suction line using bulb strap provided See Fig 6C Insulate bulb...

Страница 4: ...o indoor section using accessory tubing package or field supplied refrigerant grade tubing of correct size and condition Tubing diameters listed in Table 1 are adequate for equivalent lengths up to 50...

Страница 5: ...d tight Step 8 Make Electrical Connections To avoid personal injury or death do not supply power to unit with compressor terminal box cover removed Be sure field wiring complies with local and nationa...

Страница 6: ...HV 58UXV or 58MVP gas furnace no LCC is required The LCC for standard PSC blower products consists of a standard humidistat which opens contacts on humidity rise and a pilot duty relay with 24v coil N...

Страница 7: ...are not equipped with Schrader valves To prevent personal injury make sure gage manifold is connected to the valve gage ports before moving valves off fully back seated position Wear safety glasses an...

Страница 8: ...ions See Table 4 for codes and definitions Table 4 also provides the order of signal importance NOTE Only one code will be displayed on the outdoor unit control board the most recent with the highest...

Страница 9: ...TROL MODEL RH See notes 1 2 3 6 9 and 10 A01421 O W2 W W1 Y1 W2 G R THERMIDISTAT CONTROL MODEL RH SINGLE STAGE FURNACE TWO SPEED HEAT PUMP W G Y C Y2 W1 R Y1 O C DHUM HUM B S1 S2 R C HEAT STAGE 3 COOL...

Страница 10: ...B S1 S2 R W2 O Y1 R COM HUM PL9 10 DEHUM HEAT STAGE 3 FURNACE COOL HEAT STAGE 1 COMPRESSOR LO COOL HEAT STAGE 2 COMPRESSOR HI RVS COOLING FAN 24 VAC HOT 24 VAC COMM RVS SENSING N A OUTDOOR SENSOR CON...

Страница 11: ...and wiring information 4 Non Programmable Model 2S01 B when used in heat pump installations jumper R19 NOT cut uses O W2 to control reversing valve 5 Furnace must control its own second stage operatio...

Страница 12: ...oses anytime after the 15 minute delay then resume operation on call for Y1 and or Y2 HEATING VAPOR PRESSURE SWITCH PressureGuard This outdoor unit is equipped with a heating vapor pressure limiting d...

Страница 13: ...ve User s Manual with owner Explain system operation and periodic maintenance requirements outlined in manual 4 Fill out Dealer Installation Checklist and place in customer file CARE AND MAINTENANCE F...

Страница 14: ...PNK YEL PNK YEL PNK BRN BRN BLK BLK BLK ORN RVS ORN RED BLU CH 11 21 23 23 YEL BLK BLK BLK CL 11 21 H C START COMP RELAY BRN CAP L2 L1 EQUIPGND DUALCAPACITY A B C D BLU BRN BRN BLK YEL BRN VPS BLK C O...

Страница 15: ...RSUPPLY TIME MIN DEFROST VH L 2 ODF CCH VC RED YEL BLK BLU BRN PL5 PL4 PL3 YEL BLU BRN YEL OCT OAT LPS HPS Fig 19 Wiring Diagram 060 A01420 CONNECTION DIAGRAM OCT t LPS HPS OAT t LO HI TO INDOOR UNIT...

Страница 16: ...1 38ydb3si Manufacturer reserves the right to discontinue or change at any time specifications or designs without notice and without incurring obligations Book 1 4 Tab 5a 5a PC 101 Catalog No 533 8004...

Отзывы: