48
Table 7 —
W7220 Menu Structure*
MENU
PARAMETER
PARAMETER
DEFAULT
VALUE
PARAMETER
RANGE AND
INCREMENT
†
EXPANDED PARAMETER NAME/NOTES
STATUS
ECON AVAIL
NO
YES/NO
ECONOMIZING AVAILABLE
YES = economizing available; the system can use outside air for free cool-
ing when required
ECONOMIZING
NO
YES/NO
ECONOMIZING ACTIVE
YES = outside air being used for 1 stage cooling
NO = economizing not active
OCCUPIED
NO
YES/NO
OCCUPIED
YES = OCC signal received from space thermostat or
unitary controller
YES = 24 Vac on terminal OCC
NO = 0 Vac on terminal OCC
HEAT PUMP
N/A**
COOL
HEAT
HEAT PUMP MODE
(Not available on 2-speed configuration)
COOL Y1—IN
OFF
ON/OFF
FIRST STAGE COOLING DEMAND (Y1-IN)
Y1–I signal from space thermostat or unitary controller for cooling stage 1.
ON = 24 Vac on terminal Y1–I
OFF = 0 Vac on terminal Y1–I
COOL Y1—OUT
OFF
ON/OFF
FIRST STAGE COOLING RELAY OUTPUT
ON = 24 Vac on terminal Y1-O; Stage 1 mechanical cooling called on
OFF = 0 Vac on terminal Y1-O; no mechanical cooling
COOL Y2—IN
OFF
ON/OFF
SECOND STAGE COOLING DEMAND (Y2–IN)
Y2–I signal from space thermostat or unitary controller for cooling stage 2.
ON = 24 Vac on terminal Y2–I
OFF = 0 Vac on terminal Y2–I
COOL Y2—OUT
OFF
ON/OFF
SECOND STAGE COOLING RELAY OUTPUT
ON = 24 Vac on terminal Y2-O; Stage 2 mechanical cooling called on
OFF = 0 Vac on terminal Y2-O; no Stage 2 mechanical cooling
MA TEMP
nn°F (or °C)
0 to 140°F
(-18 to 60°C)
SUPPLY AIR TEMPERATURE, Cooling Mode
Displays value of measured mixed air from SAT sensor in fan section.
Displays _ _ . _ if not connected, short or out-of-range. See Note 2.
DA TEMP
nn°F (or °C)
0 to 140°F
(-18 to 60°C)
DISCHARGE AIR TEMPERATURE, after Heating section
(Accessory sensor required)
Displays when Discharge Air sensor is connected and displays measured
discharge temperature.
Displays _ _ . _ if sensor sends invalid value, if not connected, short or
out-of-range.
OA TEMP
nn°F (or °C)
-40 to 140°F
(-40 to 60°C)
OUTSIDE AIR TEMP
Displays measured value of outdoor air temperature.
Displays _ _ . _ if sensor sends invalid value, short or out-of-range.
OA HUM
nn%
0 to 100%
OUTSIDE AIR RELATIVE HUMIDITY
Displays measured value of outdoor humidity from OA enthalpy sensor.
RA TEMP
nn°F (or °C)
0 to 140°F
(-18 to 60°C)
RETURN AIR TEMPERATURE
(Accessory sensor required)
Displays measured value of return air temperature from RAT sensor.
RA HUM
nn%
0 to 100%
RETURN AIR RELATIVE HUMIDITY
(Accessory enthalpy sensor required)
Displays measured value of return air humidity from RA sensor.
IN CO2
_ _ _ ppm
0 TO 2000 ppm
SPACE/RETURN AIR CO
2
(CO
2
sensor required, accessory or factory option)
Displays value of measured CO
2
from CO
2
sensor.
Invalid if not connected, short or out-of-range
DCV STATUS
N/A
ON/OFF
DEMAND CONTROLLED VENTILATION STATUS
(CO
2
sensor required, accessory or factory option)
Displays ON if IN CO
2
value above setpoint DCV SET and OFF if below
setpoint DCV SET.
DAMPER OUT
2.0V
2.0 TO 10.0v
Displays voltage output to the damper actuator.
2.0V = OSA damper fuily closed
10.0V = OSA damper fully open
ACT POS
nn%
0 to 100%
Displays actual position of outdoor air damper actuator
0% = OSA damper fuily closed
100% = OSA damper fully open
Содержание WeatherExpert 50LC14
Страница 4: ...4 Fig 2 50LC Vertical Airflow Size 14...
Страница 5: ...5 Fig 3 50LC Horizontal Airflow Size 14...
Страница 6: ...6 Fig 4 50LC Back View and Condensate Drain Location Size 14...
Страница 7: ...7 Fig 5 50LC Corner Weights and Clearances Size 14...
Страница 8: ...8 Fig 6 50LC Bottom View Size 14...
Страница 9: ...9 Fig 7 50LC Vertical Airflow Sizes 17 20...
Страница 10: ...10 Fig 8 50LC Horizontal Airflow Sizes 17 20...
Страница 11: ...11 Fig 9 50LC Back View and Condensate Drain Location Sizes 17 20...
Страница 12: ...12 Fig 10 50LC Corner Weights and Clearances Sizes 17 20...
Страница 13: ...13 Fig 11 50LC Bottom View Sizes 17 20...
Страница 14: ...14 Fig 12 50LC Vertical Airflow Sizes 24 26...
Страница 15: ...15 Fig 13 50LC Horizontal Airflow Sizes 24 26...
Страница 16: ...16 Fig 14 50LC Back View and Condensate Drain Location Sizes 24 26...
Страница 17: ...17 Fig 15 50LC Corner Weights and Clearances Sizes 24 26...
Страница 18: ...18 Fig 16 50LC Bottom View Sizes 24 26...
Страница 21: ...21 Fig 19 Roof Curb Details 14 Size Unit...
Страница 22: ...22 Fig 20 Roof Curb Details 17 and 20 Size Units...
Страница 23: ...23 Fig 21 Roof Curb Details 24 and 26 Size Units...
Страница 30: ...30 Fig 42 50LC 14 26 Electro Mechanical Control Wiring Diagram...
Страница 31: ...31 Fig 43 50LC 14 26 RTU Open Control Wiring Diagram...
Страница 32: ...32 Fig 44 50LC 14 26 SystemVu Control Wiring Diagram...
Страница 33: ...33 Fig 45 Typical Power Wiring Diagram Electro Mechanical and RTU Open Controls 50LC 14 24 Units 208 230V Shown...
Страница 35: ...35 Fig 47 Typical Power Wiring Diagram SystemVu Controls 50LC Unit 208 230V Shown...
Страница 36: ...36 Fig 48 Typical Power Wiring Diagram SystemVu Controls 50LC Unit 460V 575V Shown...
Страница 80: ......
Страница 81: ......