
55
Demand Controlled Ventilation (DCV)
Demand Controlled Ventilation (DCV) function requires a space
air CO
2
sensor be connected to the W7220 controller. The CO
2
sensor provides a 2 to 10 vdc signal proportional to the space CO
2
level. This sensor is available as a factory-installed option (located
in the unit’s return air plenum) or as a field-installed accessory.
See Fig. 1 for model number nomenclature; check Position #9 for
codes E, F, G or H indicating a factory-installed CO
2
sensor. The
W7220 automatically recognizes the connection of this sensor and
self-enables the DCV function after the Configuration period.
DCV with Single-Speed Fan System
During DCV, the outside air damper modulates between two user
configurations depending upon the signal level of the space or re
-
turn air CO
2
sensor representing the space occupancy level. The
lower of these two positions is referred to as the Minimum IAQ
Damper Position (designated VENTMIN) while the higher is re
-
ferred to as Economizer Minimum Position (designated MINI
-
MUM POSITION or VENTMAX). The VENTMIN position
should be set to an economizer position that brings in enough fresh
air to remove contaminants and CO
2
generated by sources other
than people; this airflow rate is designated Va. The VENTMAX
should be set to an economizer position that brings in enough fresh
air to remove contaminants and CO
2
generated by all sources in
-
cluding people at the design condition for maximum space occu
-
pancy; this airflow rate is designated Vbz. See Fig. 73.
Fig. 73 —
DCV Single-Speed System Setpoints
DCV with Two-Speed Fan System
Ventilation codes require that the same ventilation rates (Vbz and
Va, expressed as CFM) be provided regardless of supply fan
speed. When the supply fan speed is reduced, the internal static
pressure in the unit’s return plenum also decreases. If the same
outside air damper position is retained, the airflow rate through the
OA damper decreases below the Va and Vbz levels. To restore
ventilation rates to design levels, the damper positions VENTMIN
and VENTMAX must be automatically adjusted when the fan
speed changes. The W7220 provides this function when it is con
-
figured for 2-speed fan operation through a second set of damper
position setpoints.
During operation at High fan speed, the damper setpoint limits are
designated VENTMIN H and VENTMAX H. Damper operation
is same as described in the DCV with Single-Speed Fan System
section, above.
During operation at Low fan speed, the damper setpoint limits
change to VENTMIN L and VENTMAX L. These settings are
higher than the comparable High speed settings and cause the out
-
side air damper to open more to allow the same Va and Vbz air
-
flow rates to be admitted to the space.
Adjust the DCV setpoints VENTMAX H and VENTMAX L with
supply fan speed in High speed and Low speed respectively to
provide the design load ventilation airflow rate Vbz by measuring
outside air temperature, return air temperature and supply air tem
-
perature. Make damper position adjustments with at least 10°F
temperature difference between the outdoor and return-air tem
-
peratures. See Fig. 74.
To determine the damper setpoint position, perform the following
procedure for each condition setpoint, with mechanical cooling
OFF:
Calculate the appropriate supply air temperature using the follow
-
ing formula:
TS = (TO x Vbz/CFM) + TR x (CFM – Vbz)/CFM
TS = Supply Air Temperature
TO = Outdoor Air Temperature
Vbz = Design Maximum Ventilation CFM
CFM= Unit Supply Airflow Rate
TR = Return Air Temperature
As an example:
Unit Airflow Rate at High Speed is 4000 CFM
Ventilation CFM at design occupancy Vbz is 1200 CFM
TO = 60°F
TR = 75°F
Required TS = 60 x (1200/4000) + 75 x (4000 – 1200)/4000
=60 x 0.30 + 75 x 0.70 = 18.0 + 52.5
= 70.5
At the W7220 keypad, enter the parameter SETUP –> VENT
-
MAX H and adjust the setpoint value until the observed Supply
Air Temperature (MA TEMP) reaches 70.5. Press the
(Enter)
button to save this setpoint to controller memory.
When determining VENTMIN setpoints, substitute the value for
Va in place of Vbz in the formula.
DCV Setpoint
The SETPOINTS parameter DCV SET defines the space CO
2
level above which the DCV mode begins to open the outside air
damper beyond its VENTMIN ventilation lower limit. This
setpoint should be a minimum of 100 ppm greater than the out
-
door ambient CO
2
level to ensure the outside air will be capable of
diluting the space CO
2
level. A typical value for outdoor CO
2
is
400 ppm; adjust the setpoint DCV SET to 500 ppm if outdoor
CO
2
level is not known. The factory default value for DCV SET is
1100 ppm.
Economizer Occupancy Control
The 24-v signal that terminates at the W7220’s OCC input to place
the economizer control in Occupied mode when the supply fan
starts is routed through the rooftop unit’s Integrated Staging
Control (ISC) Board at the board’s OCCUPANCY jumper. To im
-
plement an occupancy control for the economizer operation, con
-
nect a contact set at ISC OCCUPANCY quick-connect terminals
and cut jumper JMP1. To allow automatic occupancy mode, close
the control contacts. To place the economizer in Unoccupied
mode, open the control contacts. See Fig. 75.
VENTILATION FOR PEOPLE
VENTILATION FOR SOURCES
INCREASING VENTILA
TION
VENTMAX
VENTMIN
100
700
INSIDE OUTSIDE CO
2
DIFFERENTIAL
Содержание WeatherExpert 50LC14
Страница 4: ...4 Fig 2 50LC Vertical Airflow Size 14...
Страница 5: ...5 Fig 3 50LC Horizontal Airflow Size 14...
Страница 6: ...6 Fig 4 50LC Back View and Condensate Drain Location Size 14...
Страница 7: ...7 Fig 5 50LC Corner Weights and Clearances Size 14...
Страница 8: ...8 Fig 6 50LC Bottom View Size 14...
Страница 9: ...9 Fig 7 50LC Vertical Airflow Sizes 17 20...
Страница 10: ...10 Fig 8 50LC Horizontal Airflow Sizes 17 20...
Страница 11: ...11 Fig 9 50LC Back View and Condensate Drain Location Sizes 17 20...
Страница 12: ...12 Fig 10 50LC Corner Weights and Clearances Sizes 17 20...
Страница 13: ...13 Fig 11 50LC Bottom View Sizes 17 20...
Страница 14: ...14 Fig 12 50LC Vertical Airflow Sizes 24 26...
Страница 15: ...15 Fig 13 50LC Horizontal Airflow Sizes 24 26...
Страница 16: ...16 Fig 14 50LC Back View and Condensate Drain Location Sizes 24 26...
Страница 17: ...17 Fig 15 50LC Corner Weights and Clearances Sizes 24 26...
Страница 18: ...18 Fig 16 50LC Bottom View Sizes 24 26...
Страница 21: ...21 Fig 19 Roof Curb Details 14 Size Unit...
Страница 22: ...22 Fig 20 Roof Curb Details 17 and 20 Size Units...
Страница 23: ...23 Fig 21 Roof Curb Details 24 and 26 Size Units...
Страница 30: ...30 Fig 42 50LC 14 26 Electro Mechanical Control Wiring Diagram...
Страница 31: ...31 Fig 43 50LC 14 26 RTU Open Control Wiring Diagram...
Страница 32: ...32 Fig 44 50LC 14 26 SystemVu Control Wiring Diagram...
Страница 33: ...33 Fig 45 Typical Power Wiring Diagram Electro Mechanical and RTU Open Controls 50LC 14 24 Units 208 230V Shown...
Страница 35: ...35 Fig 47 Typical Power Wiring Diagram SystemVu Controls 50LC Unit 208 230V Shown...
Страница 36: ...36 Fig 48 Typical Power Wiring Diagram SystemVu Controls 50LC Unit 460V 575V Shown...
Страница 80: ......
Страница 81: ......