71
c. Press
OK
. The display changes to:
d. Press
OK
again. The following display appears:
NOTE: If the bottom row displays a number other than 0.000,
press
OK
and use the ▲ (Up arrow) and ▼ (Down arrow) keys
to select 0.000.
e. Press ▼ (Down arrow key) once. The following dis
-
play appears:
NOTE: If the bottom row displays a number other than 60.000,
press
OK
and use the ▲ (Up arrow) and ▼ (Down arrow) keys
to select 60.000.
f. Press the
Back
key until the following display
appears:
g. Press ▼ (Down arrow key) once to move the high
-
light to the bottom row, then press
OK
. The following
display appears:
h. Press
OK
once to highlight the number in brackets.
Press
OK
again. The highlight moves to the current per
-
cent value. Use the ▲ (Up arrow) and ▼ (Down
arrow) keys and the following table to enter the
required Preset Reference values:
8. Set the Ramp Time:
a. Press the
Back
key until the following display
appears:
b. Press ▼ (Down arrow key) twice. The following dis
-
play appears:
c. Press
OK
. The following display appears:
d. Press
OK
again to highlight the bottom row; then use
the ▲ (Up arrow) and ▼ (Down arrow) keys to select
10.00s. Press
OK
again to set the selected Ramp up
Time.
e. Press ▼ (Down arrow key) once. The following dis
-
play appears:
f. Press
OK
again to highlight the bottom row; then use
the ▲ (Up arrow) and ▼ (Down arrow) keys to select
10.00s. Press
OK
again to set the selected Ramp Down
Time.
9. Set Limits:
a. Press the
Back
key until the following display
appears:
b. Press ▼ (Down arrow key) once. The following dis
-
play appears:
c. Press
OK
. The following display appears:
d. Press
OK
again. The following display appears:
e. Press ▼ (Down arrow key) once. The following dis
-
play appears:
f. Press ▼ (Down arrow key) again. The following dis
-
play appears:
NOTE: Press
OK
to highlight the HZ value, and then use the ▲
(Up arrow) and ▼ (Down arrow) keys to enter the required
values.
g. Press ▼ (Down arrow key) once. The following dis
-
play appears:
NOTE: Press
OK
to highlight the % value, and then use the ▲
(Up arrow) and ▼ (Down arrow) keys to enter the required
value. See Tables 19-23 for the proper value for this parameter.
Then press
OK
to set the selected value.
h. Press ▼ (Down arrow key) once. The following dis
-
play appears:
NOTE: Press
OK
to highlight the HZ value, and then use the ▲
(Up arrow) and ▼ (Down arrow) keys to enter the required
values.
10. Set Digital Inputs:
a. Press the
Back
key until the following display
appears:
3 —0* Reference Limits
3 —1* References
3 —02 Minimum Reference
0.000
3 —03 Maximum Reference
60.000
3 —0* Reference Limits
3 —1* References
3 —10 Preset Reference
[0]0.00%
[0]0.00%
Stop
[1]LL.LL%
, column labeled “Pre
-
set References 3-10[1]” for the proper % for each unit)
[2]MM.MM%
Medium Speed (see Tables 19-23, column labeled
“Preset References 3-10[2]” for the proper % for each
unit)
[3]100%
Override (High Speed)
[4]100%
High Speed (100% or close to 100% to achieve the
required CFM at high speed)
[5]100%
Stop
[6]100%
Stop
[7]100%
Stop
3 —0* Reference Limits
3 —1* References
3—1* References
3—4* Ramp 1
3 —41 Ramp 1 Ramp up Time
3.00s
3 —42 Ramp 1 Ramp Down Time
3.00s
2—** Brakes
3—** Reference/Ramps
3—** Reference/Ramps
4—** Limits/Warnings
4 —1* Motor Limits
4 —4* Adj. Warning 2
4 —10 Motor Speed Direction
[2] Both Directions
4—12 Motor Speed Low Limi...
0.0Hz
4—14 Motor Speed High Limi...
65.0Hz
4—18 Current Limit
110%
4—19 Max Output Frequency
65.0Hz
3—** Reference/Ramps
4—** Limits/Warnings
Содержание WeatherExpert 50LC14
Страница 4: ...4 Fig 2 50LC Vertical Airflow Size 14...
Страница 5: ...5 Fig 3 50LC Horizontal Airflow Size 14...
Страница 6: ...6 Fig 4 50LC Back View and Condensate Drain Location Size 14...
Страница 7: ...7 Fig 5 50LC Corner Weights and Clearances Size 14...
Страница 8: ...8 Fig 6 50LC Bottom View Size 14...
Страница 9: ...9 Fig 7 50LC Vertical Airflow Sizes 17 20...
Страница 10: ...10 Fig 8 50LC Horizontal Airflow Sizes 17 20...
Страница 11: ...11 Fig 9 50LC Back View and Condensate Drain Location Sizes 17 20...
Страница 12: ...12 Fig 10 50LC Corner Weights and Clearances Sizes 17 20...
Страница 13: ...13 Fig 11 50LC Bottom View Sizes 17 20...
Страница 14: ...14 Fig 12 50LC Vertical Airflow Sizes 24 26...
Страница 15: ...15 Fig 13 50LC Horizontal Airflow Sizes 24 26...
Страница 16: ...16 Fig 14 50LC Back View and Condensate Drain Location Sizes 24 26...
Страница 17: ...17 Fig 15 50LC Corner Weights and Clearances Sizes 24 26...
Страница 18: ...18 Fig 16 50LC Bottom View Sizes 24 26...
Страница 21: ...21 Fig 19 Roof Curb Details 14 Size Unit...
Страница 22: ...22 Fig 20 Roof Curb Details 17 and 20 Size Units...
Страница 23: ...23 Fig 21 Roof Curb Details 24 and 26 Size Units...
Страница 30: ...30 Fig 42 50LC 14 26 Electro Mechanical Control Wiring Diagram...
Страница 31: ...31 Fig 43 50LC 14 26 RTU Open Control Wiring Diagram...
Страница 32: ...32 Fig 44 50LC 14 26 SystemVu Control Wiring Diagram...
Страница 33: ...33 Fig 45 Typical Power Wiring Diagram Electro Mechanical and RTU Open Controls 50LC 14 24 Units 208 230V Shown...
Страница 35: ...35 Fig 47 Typical Power Wiring Diagram SystemVu Controls 50LC Unit 208 230V Shown...
Страница 36: ...36 Fig 48 Typical Power Wiring Diagram SystemVu Controls 50LC Unit 460V 575V Shown...
Страница 80: ......
Страница 81: ......