7–33
62-11637
00061
DOOR OPEN (DS1)
• ACTIVATION: DS1 is set to trigger an alarm if the switch is activated (opened or closed, depending on
switch type) for more than five seconds.
• UNIT CONTROL: May be configured as alarm only, alarm and force low engine speed, or alarm and shut-
down.
• RESET CONDITION:
Alarm Only: Auto reset after the switch has de-activated for more than five seconds.
Shutdown: Auto reset after three minutes (minimum off time for door open condition) and the switch has
de-activated for more than five seconds.
NOTE: Follow the steps below until a problem is found. Once a repair or correction has been made, the active
alarm should clear itself (refer to reset condition above). Operate the unit through the appropriate modes to see if
any active alarm occurs. Continue with the steps below as necessary.
CORRECTIVE ACTIONS:
IF A SWITCH IS INSTALLED
1.
Determine What DS1 is Activated By
DS1 may be connected to a compartment door or some other device. Locate the device used as DS1.
2.
Check to See if DS1 has Activated
Inspect device used to activate DS1. For example, compartment door must be closed, and switch
must be de-activated.
3.
Check Configuration for DS1
Verify that Configuration is set for the type of switch being used (i.e. when switch is activated, switch
contacts are closed; etc). Configuration must agree with switch type. Refer to
4.
Check Wiring
a. Visually inspect wiring to DS1 to make sure it is connected.
b. Visually inspect condition of switch. It must not be damaged, wet, corroded, etc.
c. Check circuit. (See wiring schematic
.) With the switch contacts closed, check for mini-
mum 11 VDC from 2SVM
−
14, through the wiring and switch back to 2SVM
−
25.
5.
Temporary Solution Tip
In the event of a defective switch that can not be repaired or replaced, and the switch is forcing the unit
into a shutdown or low speed, this action may be temporarily overridden by setting the correct Func-
tional Parameter. Set the Override Door Switch Shutdown Functional Parameter to YES.
IF A SWITCH IS NOT INSTALLED
1.
Check Configurations
Any switch/sensor not present in the unit should not be Configured “ON”. Correct Configurations.
2.
Check Connector
Locate and inspect the DS or REM 10 position connector for optional sensors and switches (see wiring
schematic
). Connector must have cap on. No corrosion or moisture inside connector. If
there is a problem with the DS connector and no switch is installed, the connector may be removed
and both wires separated, terminated and insulated with heat shrink. If there is no DS connector, there
is a problem with the REM connector and there are no remote sensors or switches in the unit, the con-
nector may be removed and each individual wire separated from the others, terminated and insulated
with heat shrink.