Sequence of Operation

 

 

 

 
 

RTU Open v5 

 

CARRIER CORPORATION ©2019   

Integration Guide 

 

All rights reserved 

 

33 

 

ZS Sensor 

– This alarm indicates a communication failure of a connected ZS sensor that had previously been 

actively communicating. The alarm is reset when normal ZS sensor communications resume, if power is cycled to 
the controller, or if the 

Shutdown

 point is set to 

Active

ZS Configuration

 – This alarm indicates that at least 1 ZS sensor is configured in the Sensor Binder properties 

and is not communicating. The alarm is reset when the configured ZS sensor is communicating or the 
configuration is changed to reflect the sensor is no longer connected to the Rnet. 

Space Temp Sensor

 – This alarm indicates an invalid sensor condition in a physically connected space 

temperature sensor (SPT Sensor/T5*).  Cooling, heating, and supply fan operation stop after the appropriate time 
guards. Normal operation resumes when the controller detects a valid sensor. 

Supply Air Temperature

 – This alarm indicates that the supply air temperature is outside the configured alarm 

limits. The alarm is reset to normal when the supply air temperature returns within the configured alarm limits 
plus a 3 °F (1.6. °C) hysteresis. This alarm is inhibited until the fan has been running for 15 minutes to allow 
for system stabilization after startup.    

Supply Air Temp Sensor

 – This alarm indicates a shorted or open circuit in the SAT input. Cooling, heating, and 

supply fan operation stops after the appropriate time guards. Normal operation resumes when the controller 
detects a valid sensor. 

Indoor Air Quality

 – The RTU Open generates an 

Indoor Air Quality

 alarm if the CO

2

 level exceeds the configured 

alarm limits. (This alarm is only shown when a valid indoor air quality sensor value is available).   

Indoor Air Quality Sensor

 – The RTU Open generates an 

Indoor Air Quality Sensor

 alarm if a valid sensor value is 

no longer available. For locally connected sensors, the mA input at the associated channel falls below 3.5 mA or 
rises above 21 mA. For network sensors, the controller is no longer receiving a value from the network. Cooling, 
heating, and supply fan continue to operate. However, the controller’s IAQ control function is disabled until the 
fault condition is corrected. 

Space Relative Humidity

 – The RTU Open generates a 

Space Relative Humidity

 alarm if the space humidity level 

exceeds the configured low or high alarm limits. (This alarm is only shown when a valid relative humidity sensor 
value is available). 

Space Relative Humidity Sensor

 – The RTU Open generates a 

Space Relative Humidity Sensor

 alarm if a valid 

sensor value is no longer available. For locally connected sensors, the mA input at the associated channel falls 
below 3.5 mA or rises above 21 mA. For network sensors, the controller is no longer receiving a value from the 
network.  Cooling, heating, and supply fan operation continues, however, the controller’s Humidi-MiZer™ binary 
output is disabled until the fault condition is corrected. 

Filter

 – If the RTU Open is configured to monitor the filter through a hardware input switch contact, it generates a 

Filter

 alarm if the associated input channel detects a dirty filter condition (opposite state of the 

Input

 “x” 

Switch 

Configuration

). Otherwise, if no hardware switch monitoring is used, the RTU Open generates a filter alarm when 

the accumulated runtime exceeds the 

Unit Configuration

 > 

Filter Service Alarm Timer

 value (when not set to 0). 

This alarm is most commonly used to indicate a filter replacement is due. Reset the filter service runtime 
accumulator by setting the 

Maintenance 

Reset Filter Runtime Alarm 

to 

On

, back to 

Off

, and clicking 

OK

 after 

each setting. Set 

Unit Configuration

 > 

Filter Service Alarm Timer

 value to 

to disable the filter service alarm 

function. 

Local OAT Sensor

 – This alarm indicates a shorted or open circuit in the locally connected OAT input.  

Outdoor Air Temp Sensor

 – This alarm indicates a valid OAT sensor value is no longer available. An alarm 

condition can occur from a failed locally connected sensor or if a network OAT value is no longer being received by 
the controller. Cooling, heating, and supply fan operation continues. OAT lockouts will not operate while the sensor 
is in alarm. Normal operation resumes when the controller detects a valid sensor. 

Economizer Operation

 – This alarm is active when an economizer fault is detected, as required by the CEC Title 

24 Economizer FDD logic. Once detected, this alarm will stay active until the 

Shutdown

 input is set to 

Active

 or the 

fan is stopped. 

Economizer

 – This point indicates the specific fault detected and announced by the Economizer Operation alarm 

above. Detected fault conditions include 

Failed to Fully Open

Failed to Open

Failed to Close

, and 

Stuck Open

 

 

Содержание RTU Open v5

Страница 1: ...U U O Op pe en n v v5 5 I In nt te eg gr ra at ti io on n G Gu ui id de e CARRIER CORPORATION 2019 A member of the United Technologies Corporation family Stock symbol UTX Catalog No 11 808 697 01 11 1...

Страница 2: ...ur local Carrier office Important changes are listed in Document revision history at the end of this document CARRIER CORPORATION 2019 All rights reserved throughout the world i Vu is a registered tra...

Страница 3: ...14 Troubleshooting N2 communication 15 LonWorks 16 To set up the RTU Open for the LonWorks Option Card Part LON OC 17 Commissioning the controller for LonWorks communication 18 Troubleshooting LonWor...

Страница 4: ...ts list for BACnet and Modbus 44 Network points list for N2 and LonWorks 52 Appendix B BACnet Protocol Implementation Conformance Statement 55 Appendix C Modbus Protocol Implementation Conformance Sta...

Страница 5: ...dicator BACnet and third party protocols On board DIP switches allow you to select the baud rate and choose one of the following protocols BACnet MS TP BACnet ARC156 Modbus Johnson N2 LonWorks Mixed s...

Страница 6: ...Introduction RTU Open v5 CARRIER CORPORATION 2019 Integration Guide All rights reserved 2...

Страница 7: ...ons handling warning WARNING When you handle the RTU Open Do not contaminate the printed circuit board with fingerprints moisture or any foreign material Do not touch components or leads Handle the bo...

Страница 8: ...age 11 Johnson N2 page 14 LonWorks page 16 The default setting is BACnet MS TP You set the protocol and baud rate using the SW3 DIP switches The rotary switches MSB SW1 and LSB SW2 set the board s net...

Страница 9: ...resses are 01 99 NOTE The rotary switches also determine the BACnet device instance of the controller on the BACnet network The BACnet device instance is automatically generated based on the scheme 16...

Страница 10: ...d not star wired Attach the drain shield wire to both ends of the network segment and through every controller NOTE Use the same polarity throughout the network segment 6 Turn on the RTU Open s power...

Страница 11: ...ised of both master and slave nodes Valid MAC addresses for master nodes are 0 127 and valid addresses for Slave nodes are 0 254 If the third party attempts to communicate to the controller but does n...

Страница 12: ...s BACnet PICS from the Carrier BACnet PICS website http www bacnetinternational net catalog index php m 28 You must get your BACnet Object list from the manufacturer The most common communication pro...

Страница 13: ...tches when the controller is on will not take effect until the power is cycled 2 Using the rotary switches MSB SW1 and LSB SW2 set a unique BACnet MS TP MAC address for the RTU Open Set the MSB SW1 sw...

Страница 14: ...on the RTU Open s power Troubleshooting ARC156 communication The most common communication problems result from not properly following the configuration steps outlined above in this manual Review all...

Страница 15: ...not take effect until the power is cycled 2 Using the rotary switches set a unique Modbus slave address for the RTU Open Set the MSB SW1 switch to the tens digit of the address and set the LSB SW2 sw...

Страница 16: ...2000 feet 610 meters or 32 nodes Devices should be daisy chained and not star wired Attach the drain shield wire to both ends of the network segment and through every controller NOTE Use the same pola...

Страница 17: ...per address Reading or writing to the proper point addresses on the controller Set for the same communication settings 8 Data bits No Parity and 1 Stop bit Speaking 2 wire 485 to the controller Softwa...

Страница 18: ...the address and set the LSB SW2 switch to the ones digit Valid N2 slave addresses are 01 99 EXAMPLE To set the N2 slave address to 01 point the arrow on the MSB SW1 switch to 0 and the arrow on the L...

Страница 19: ...all of the steps and use the following list to check your settings Verify accuracy of the following Hardware settings for N2 8 Data bits No Parity and 1 Stop bit Baud rate DIP switches DS2 and DS1 se...

Страница 20: ...onfirm settings obtain a Modstat of the device On the Equipment Touch click the link to the Modstat LonWorks WARNING When you handle the LonWorks Option Card Do not contaminate the printed circuit boa...

Страница 21: ...it unique on the LonWorks network 2 Set the SW3 DIP switches for LonWorks as follows 8 7 6 5 4 3 2 1 Off On On Off On Off Off On 3 Plug the LonWorks Option Card s ribbon cable into Comm Option port J...

Страница 22: ...ior to binding the controller s network variables to other LonWorks nodes Troubleshooting LonWorks communication The most common communication problems result from not properly following the configura...

Страница 23: ...lable only for BACnet MS TP systems Wire to a BACnet MS TP network connector and a 24 Vac power supply 3 Temporary or permanent interface 1 Requires a USB Link Part USB L 2 See the Equipment Touch Ins...

Страница 24: ...ccupancy state Occupied Unoccupied The RTU Open operates continuously in the Occupied mode until you configure an occupancy schedule An occupancy schedule may be A local schedule configured in the con...

Страница 25: ...ensor alarm Space Temp Sensor alarm The RTU Open does not include smoke control functions such as smoke purge zone pressurization or smoke ventilation The RTU Open may be configured to accept a Supply...

Страница 26: ...imers are employed to protect the equipment from short cycling There are fixed 3 minute minimum on times and 5 minute off times for each compressor output During compressor operation the RTU Open may...

Страница 27: ...l modulate to maintain the configured Minimum Cooling SAT limit when the unit is in an economizer only mode and will modulate closed only when the SAT drops below the Minimum Cooling SAT limit 5 F 2 8...

Страница 28: ...se If the FDD logic detects a decrease in damper position for example from 80 to 65 it expects to also detect an increase in SAT If the SAT failed to increase or no change in SAT is detected the FDD l...

Страница 29: ...ature rises at least 1 F 5 C above the Occupied Cooling Setpoint the supply fan starts The economizer damper opens as necessary to cool the space The RTU Open continues to operate in this mode until t...

Страница 30: ...the unit s fan The Optimal Start recovery period may begin as early as 4 hours prior to occupancy The time at which the setpoints move is based on the difference between the current space temperature...

Страница 31: ...CO2 is controlled on rooftop equipment with an economizer Indoor Air CO2 sequence is enabled by installing an air quality CO2 sensor A CO2 sensor may be terminated at the RTU Open or a subordinate zon...

Страница 32: ...the Maximum Heating SAT setpoint A heat stage turned off in this fashion may be started again after the normal time guard period has expired if the Supply Air Temperature has decreased below the Maxim...

Страница 33: ...y described for heating and cooling except that the Y1 and Y2 outputs are compressor outputs energizing mechanical heating or cooling depending on the state of the reversing valve W1 and W2 are used f...

Страница 34: ...lls below the active setpoint by a 5 fixed Hysteresis when a humidity sensor is used or when there is no longer a call for dehumidification where a humidistat is used See the base unit Humidi MiZer op...

Страница 35: ...A Compressor Safety Alarm is shown on Properties page Control Program tab Alarms and indicates that the equipment requires attention Cooling heating and supply fan outputs are not interrupted except w...

Страница 36: ...he RTU Open to monitor the base unit s compressor safety circuit This alarm indicates the base unit s compressor safety circuit is energized Cooling heating and supply fan outputs are not interrupted...

Страница 37: ...ty The RTU Open generates a Space Relative Humidity alarm if the space humidity level exceeds the configured low or high alarm limits This alarm is only shown when a valid relative humidity sensor val...

Страница 38: ...Fan Service Timer value to 0 disables the supply fan runtime alarm function Compressor 1 Runtime The RTU Open generates this alarm when the accumulated runtime exceeds the Unit Configuration Compresso...

Страница 39: ...ng and cooling requirements from all the zones based on their occupancy and demand The VVT Master scans the system continuously to determine if any zones are occupied Occupied zones are a higher prior...

Страница 40: ...er ventilation Linkage also provides a safety and system override function during any RTU heating mode Whenever the RTU Open is in a heating mode the control monitors the supply air temperature SAT No...

Страница 41: ...all zones modulate airflow to maintain the zone temperature at the appropriate occ unocc cooling setpoint PRESSURIZATION Air source supply fan is on usually as a result of a fire life safety input bei...

Страница 42: ...it operation If the problem occurs without the RTU Open connected then the operator should begin troubleshooting the unit equipment rather than the RTU Open or network Third party network may also hel...

Страница 43: ...t system errors or control programs halted 5 flashes per second Off Firmware transfer in progress Boot is running 7 flashes per second 7 flashes per second alternating with Run LED Ten second recovery...

Страница 44: ...nterference to radio communications Operation of this equipment in a residential area is likely to cause harmful interference in which case the user will be required to correct the interference at his...

Страница 45: ...BACnet system point is written to the controller uses the network value even when there is a local sensor as long as it is within the Min Max refresh times noted below BACnet writes to system points T...

Страница 46: ...lue LonWorks Default Value Recommended Write Rrefresh Time min max System Space Temperature 50 150 F 999 180 F 1 min 5 min System Space RH 1 100 999 15 96 5 min 10 min System Space AQ 200 9999 ppm 999...

Страница 47: ...ler Commanded Points Control Points Display Name Type Instance Object Name Display Name Type Instance Object Name System Space Temperature av 1902 system_spt Space Temperature Prime Variable av 2007 s...

Страница 48: ...fective Cool Setpoint R F eff_cl_stpt AV 3005 Input Register Float 55 High Space Temperature R 0 Normal 1 Alarm spt_hi_alarm BV 7011 Discrete Input 35 Low Space Temperature R 0 Normal 1 Alarm spt_lo_a...

Страница 49: ...ensor R 0 Normal 1 Alarm sprh_sensor_fail BV 7022 Discrete Input 45 Setpoint Adjustment R F stpt_adj AV 1006 Input Register Float 99 Effective Heat Setpoint R F eff_ht_stpt AV 3006 Input Register Floa...

Страница 50: ...lative Humidity Setpoint R W rh 95 unocc_dehum_stpt AV 3012 Holding Register Float 129 Setpoint R W F occ_ht_stpt AV 3002 Holding Register Float 19 Supply Air Temp Sensor R 0 Normal 1 Alarm loc_sat_se...

Страница 51: ...2 Runtime R 0 Normal 1 Alarm comp2_rntm_alarm BV 7015 Compressor 2 Test R W 0 Disable 1 Enable Inactive 0 comp2_test BV 81004 Compressor Safety Status R 0 Normal 1 Trouble comp_status BV 1008 Continuo...

Страница 52: ...10 Humidistat Input Status R 0 High 1 Low humstat_status BV 1006 IGC Override R 0 Off 1 Active igcovr_status BV 1022 Local OAT Sensor R 0 Normal 1 Alarm loc_oat_sensor_fail BV 7003 Occupancy Contact R...

Страница 53: ...003 Equipment Status R 1 Disabled 2 Test 3 Run mode_status MSV 2001 Fan Control R W 1 Single Speed 2 Two Speed 3 Variable Speed 3 fan_type MSV 9031 Fan Mode R W 1 Auto 2 Continuous 3 Always On 2 fan_m...

Страница 54: ...1 Always Occupied 2 BACnet Schedule 3 BAS On Off 4 Remote Occ Input 1 occ_source MSV 1002 Space sensor type R W 1 T55 2 T56 3 SPT Sensor 4 None 1 spt_type MSV 9001 Space Temp Source R 1 Sensor Failur...

Страница 55: ...2017 Min VFD Output R W 40 min_vfd_spd AV 3027 Stage 2 SAT Stpt R W F 57 stg_2_sat AV 83009 slidepot voltage reading R slidepot_volts AI 1012 Filter Runtime R hr filter_rntm AV 2015 Fan Off Delay R W...

Страница 56: ...nviDCVMaxPos Space Temperature Prime Variable R F ADF 48 SNVT_temp_p 105 nvoSpaceTemp HP Rev Cycle Lockout Temp R W F 3 ADF 30 SNVT_temp_p 105 nviHPRvClLk System Outdoor Air Temperature R W F 999 ADF...

Страница 57: ...1 SNVT_count_inc 9 nviBASOnOff System Space AQ R W ppm 999 ADF 39 SNVT_count_inc 9 nviSysSpAQ System Space RH R W 999 ADF 40 SNVT_lev_percent 81 nviSysSpRH Compressor Status R 0 Normal 1 Alarm BI 30...

Страница 58: ...SysEnth Optimal Start R W hr 1 ADF 61 SNVT_count_inc 9 nviOptmStart Power Fail Restart Delay R W seconds 5 ADF 58 SNVT_count_inc 9 nviUntStrDly Indoor Air Quality CO2 ppm R ppm ADF 31 SNVT_ppm 29 nvoI...

Страница 59: ...R CORPORATION 2019 Integration Guide All rights reserved 55 The PIC statements are updated regularly Please refer to the BACnet website http www bacnetinternational net catalog index php m 28 for the...

Страница 60: ...aud rates Data Bits Parity Stop Bits 2 wire EIA 485 9600 19200 38400 76800 8 None 1 Function Codes Purpose Used with Register Numbers 01 Read Coil Status Read Discrete Outputs 00001 65535 02 Read Inpu...

Страница 61: ...Integer UINT 0 65535 3 Read Holding Register 6 Preset Single Register 16 Preset Multiple Register Signed Integer SINT 32768 32767 3 Read Holding Register 6 Preset Single Register 16 Preset Multiple R...

Страница 62: ...ls The RTU Open controller speaks the Johnson N2 Open Protocol as described in the Metasys N2 System Protocol Specification for Vendors document revision 6 13 96 Further details on the N2 supported im...

Страница 63: ...n Conformance Statement RTU Open v5 CARRIER CORPORATION 2019 Integration Guide All rights reserved 59 Write Binary Output Write Internal Parameter Override Analog Input Override Binary Input Override...

Страница 64: ...ernal interface file XIF is also available so that any network management tool can design and configure the RTU Open prior to installation Contact your Carrier representative for this XIF file LonWork...

Страница 65: ...ng errors are not listed Date Topic Change description Code 11 19 19 Appendix A Network Points List Third party access to BACnet points in a controller New topic C TS JN E RD 8 29 19 Indoor Air CO2 Co...

Страница 66: ...CARRIER CORPORATION 2019 A member of the United Technologies Corporation family Stock symbol UTX Catalog No 11 808 697 01 11 19 2019...

Отзывы: