Appendix A: Network Points List for RTU Open
RTU Open v5
CARRIER CORPORATION ©2019
Integration Guide
All rights reserved
52
Network points list for N2 and LonWorks
N2
Lonworks
Point Name
Point
Access
Units
Default
Value
N2
Network
Point
Type
N2
Network
Point
Address
SNVT Type
SNVT Name
SA Vent / Temper
Setpoint
R/W
°F
65
ADF
77
Active Heat Stages
R
ADF
11
SNVT_count_inc(9)
nvoHtStgs
Effective Cool Setpoint
R
°F
ADF
22
SNVT_temp_p(105)
nvoEffCoolSP
High Space Temperature R
0=Normal
1=Alarm
BI
35
SNVT_switch(95)
nvoHiSpTemp
Low Space Temperature R
0=Normal
1=Alarm
BI
39
SNVT_switch(95)
nvoLoSpTmp
Supply Fan Relay State
R
0=Off
1=On
BI
23
Supply Fan Status
R
0=Off
1=On
BI
24
SNVT_switch(95)
nvoFanStatus
Economizer Output
R
%Open
ADF
20
SNVT_lev_percent(81) nvoEconOut
Outdoor Air Quality
Sensor
R
0=Normal
1=Alarm
BI
41
SNVT_switch(95)
nvoOAQSensor
DCV Max Vent Damper
Pos
R/W
%Open
50
ADF
18
SNVT_lev_percent(81) nviDCVMaxPos
Space Temperature -
Prime Variable
R
°F
ADF
48
SNVT_temp_p(105)
nvoSpaceTemp
HP Rev Cycle Lockout
Temp
R/W
°F
-3
ADF
30
SNVT_temp_p(105)
nviHPRvClLk
System Outdoor Air
Temperature
R/W
°F
-999
ADF
54
SNVT_temp_p(105)
nviSysOAT
Economizer Purge Min
Pos
R/W
%Open
40
ADF
5
SNVT_lev_percent(81) nvoEcnPrgMin
Active Compressor
Stages
R
ADF
10
SNVT_count_inc(9)
nvoCmpStages
System Mode
R
1=Off
2=Fan Only
3=Economizer Cooling
4=Cooling
5=Heating
6=Dehumidification
7=Test
8=Shutdown
9=Unocc Free Cooling
10=Fire Shutdown
11=IAQ Override
12=Pre-occ Purge
13=IGC Override
ADI
13
SNVT_count_inc(9)
nvoOpMode
Supply Air Temperature
R
°F
ADF
49
SNVT_temp_p(105)
nvoSAT
DCV Max Ctrl Setpoint
R/W
ppm
650
ADF
17
SNVT_ppm(29)
nviDCVMaxPPM
Occ Relative Humidity
Setpoint
R/W
%rh
60
ADF
36
SNVT_lev_percent(81) nviOcRHSP
Occupancy Status
R
0=Unoccupied
1=Occupied
BI
18
SNVT_switch(95)
nvoOccStatus
Optimal Start Type
R/W
1=None
2=Temp Compensated
3=Learning Adaptive
2
ADI
20
SNVT_count_inc(9)
nviOptStType
Setpoint
R/W
°F
ADF
8
SNVT_temp_p(105)
nviUnoccHtSP
Space Relative Humidity R
0=Normal
BI
45
SNVT_switch(95)
nvoSpRHSenr