Appendix A: Network Points List for RTU Open
RTU Open v5
CARRIER CORPORATION ©2019
Integration Guide
All rights reserved
47
BACnet
Modbus
Point Name
Point
Access
Units
Default
Value
BACnet Point Name
BACnet
Object ID
Modbus Register
Type
Modbus
Register #
T5x Override Duration
R/W
hr
1
ovr_dur
AV:9023
VFD Speed Test
R/W
%
0
vfd_spd_test
AV:81002
input_3
R
0=Off
1=On
di_3
BI:1003
input_4
R
0=Off
1=On
di_4
BI:1004
input_5
R
0=Off
1=On
di_5
BI:1005
input_8
R
0=Off
1=On
di_8
BI:1008
input_9
R
0=Off
1=On
di_9
BI:1009
Airside Linkage
R
0=Normal
1=Alarm
air_linkage_fail
BV:7030
Analog Input
Configuration
R
0=Normal
1=Alarm
ai_cfg_alarm
BV:7026
Compressor 1 Runtime
R
0=Normal
1=Alarm
comp1_rntm_alarm
BV:7014
Compressor 1 Relay
State
R
0=Off
1=On
comp_1
BV:2005
Compressor 1 Test
R/W
0=Disable
1=Enable
Inactive
(0)
comp1_test
BV:81005
Compressor 2 Relay
State
R
0=Off
1=On
comp_2
BV:2004
Compressor 2 Runtime
R
0=Normal
1=Alarm
comp2_rntm_alarm
BV:7015
Compressor 2 Test
R/W
0=Disable
1=Enable
Inactive
(0)
comp2_test
BV:81004
Compressor Safety
Status
R
0=Normal
1=Trouble
comp_status
BV:1008
Continuous Occupied
Exhaust
R/W
0=No
1=Yes
Inactive
(0)
occ_exh
BV:9002
DCV Control
R/W
Inactive
(0)
dcv_enable
BV:1027
Dehumidification Test
R/W
0=Disable
1=Enable
Inactive
(0)
dehum_test
BV:81006
Door Contact Status
R
0=Off
1=On
door_contact_status
BV:1010
Economizer Exists
R/W
0=No
1=Yes
Inactive
(0)
econ_exist
BV:99001
Enthalpy Status
R
0=High
1=Low
enthalpy_status
BV:1002
Factory Test
R/W
0=Off
1=On
Inactive
(0)
fac_test_enable
BV:91000
Factory Test Relay 1
Control
R/W
0=Off
1=On
Inactive
(0)
relay1_fac_test
BV:91001
Factory Test Relay 2
Control
R/W
0=Off
1=On
Inactive
(0)
relay2_fac_test
BV:91002
Factory Test Relay 3
Control
R/W
0=Off
1=On
Inactive
(0)
relay3_fac_test
BV:91003
Factory Test Relay 4
Control
R/W
0=Off
1=On
Inactive
(0)
relay4_fac_test
BV:91004
Factory Test Relay 5
Control
R/W
0=Off
1=On
Inactive
(0)
relay5_fac_test
BV:91005
Factory Test Relay 6
R/W
0=Off
Inactive
relay6_fac_test
BV:91006