background image

11

Combination ratings continued

See notes on pg. 13.

UNIT

SIZE-SERIES

INDOOR

UNIT

TOT. CAP.

BTUH

 FACTORY-

SUPPLIED 

ENHANCE-

MENT

SEER

EER

Standard

Rating

Carrier Gas Furnace 

or Accessory

TDR†

Accessory

TXV‡

042-30, 32

F(A,B)4AN(F,B,C)042

39,500

TDR

11.70

11.70

10.05

F(A,B)4AN(F,B,C)048

40,000

TDR

12.00

12.00

10.25

FC4BN(F,B)042**

38,500

TDR & TXV

11.50

9.90

FC4BN(F,B)048**

39,500

TDR & TXV

11.70

10.05

FC4BNB054**

40,500

TDR & TXV

12.20

10.65

FG3AAA048

40,000

NONE

11.70

11.70

10.20

40FKA/FK4CNB006**

40,500

TDR & TXV

13.50

11.60

40FKA/FK4CNF003**

38,500

TDR & TXV

12.50

10.85

40FKA/FK4CNF005**

40,000

TDR & TXV

13.00

11.30

FV4ANB006

40,500

TDR & TXV

13.70

13.70

11.60

FV4ANF003

38,500

TDR & TXV

12.70

12.70

10.85

FV4ANF005

40,500

TDR & TXV

13.20

13.20

11.30

FX4ANF042

38,500

TDR & TXV

11.70

11.70

10.05

FX4ANF048

39,500

TDR & TXV

12.00

12.00

10.20

COILS + 58MVP040-14 VARIABLE SPEED FURNACE

CC5A/CD5AA042

39,000

TDR

12.20

12.20

10.60

CC5A/CD5AW048

39,500

TDR

12.50

12.50

10.65

CK5A/CK5BA042

39,000

TDR

12.20

12.20

10.60

CK5A/CK5BW048

39,500

TDR

12.50

12.50

10.75

COILS + 58MVP060-14 VARIABLE SPEED FURNACE

CK3BA042

39,000

TDR

12.50

12.50

10.60

CK5A/CK5BN048

39,500

TDR

12.45

12.45

10.55

COILS + 58MVP080-14 VARIABLE SPEED FURNACE

CC5A/CD5AA042

39,000

TDR

12.50

12.50

10.70

CC5A/CD5AC048

39,000

TDR

12.50

12.50

10.65

CD5AA048

39,500

TDR

12.50

12.50

10.80

CK3BA042

39,000

TDR

12.50

12.50

10.75

CK3BA048

39,500

TDR

12.50

12.50

10.85

CK5A/CK5BA042

39,000

TDR

12.50

12.50

10.75

CK5A/CK5BA048

39,500

TDR

12.50

12.50

10.85

COILS + 58MVP080-20 VARIABLE SPEED FURNACE

CC5A/CD5AA042

39,000

TDR

12.20

12.20

10.60

CC5A/CD5AC048

39,000

TDR

12.20

12.20

10.50

CD5AA048

39,500

TDR

12.50

12.50

10.65

CK3BA042

39,000

TDR

12.20

12.20

10.60

CK3BA048

39,500

TDR

12.50

12.50

10.75

CK5A/CK5BA042

39,000

TDR

12.20

12.20

10.60

CK5A/CK5BA048

39,500

TDR

12.50

12.50

10.75

COILS + 58MVP100-20 VARIABLE SPEED FURNACE

CC5A/CD5AA042

39,000

TDR

12.50

12.50

10.90

CC5A/CD5AC048

39,000

TDR

12.50

12.50

10.80

CD5AA048

39,500

TDR

12.50

12.50

10.95

CK3BA042

39,000

TDR

12.50

12.50

10.90

CK3BA048

39,500

TDR

12.50

12.50

11.05

CK5A/CK5BA042

39,000

TDR

12.50

12.50

10.90

CK5A/CK5BA048

39,500

TDR

13.00

13.00

11.05

COILS + 58MVP120-20 VARIABLE SPEED FURNACE

CC5A/CD5AA042

39,000

TDR

12.50

12.50

10.90

CC5A/CK5AW048

39,500

TDR

12.50

12.50

11.00

CK5A/CK5BA042

39,000

TDR

12.50

12.50

10.90

CK5A/CK5BW048

39,500

TDR

12.50

12.50

11.00

COILS + 58U(H,X)V080-16 VARIABLE SPEED FURNACE

CC5A/CD5AA042

39,000

TDR

12.50

12.50

10.75

CC5A/CD5AC048

39,000

TDR

12.50

12.50

10.70

CD5AA048

39,500

TDR

12.50

12.50

10.85

CK3BA042

39,000

TDR

12.50

12.50

10.75

CK3BA048

39,500

TDR

12.50

12.50

10.90

CK5A/CK5BA042

39,000

TDR

12.50

12.50

10.75

CK5A/CK5BA048

39,500

TDR

12.50

12.50

10.90

COILS + 58U(H,X)V100-20 VARIABLE SPEED FURNACE

CC5A/CD5AA042

39,000

TDR

12.50

12.50

11.00

CC5A/CD5AW048

39,500

TDR

13.00

13.00

11.10

CK5A/CK5BA042

39,000

TDR

12.50

12.50

11.05

CK5A/CK5BW048

39,500

TDR

13.00

13.00

11.15

COILS + 58U(H,X)V120-20 VARIABLE SPEED FURNACE

CC5A/CD5AA042

39,000

TDR

12.50

12.50

11.00

CC5A/CD5AW048

39,500

TDR

13.00

13.00

11.10

CK5A/CK5BA042

39,000

TDR

12.50

12.50

11.00

CK5A/CK5BW048

39,500

TDR

13.00

13.00

11.15

048-30, 32

CK5A/CK5BA060*

46,000

NONE

12.00

12.00

10.40

CC5A/CD5AA060

45,000

NONE

11.70

11.70

10.15

CC5A/CD5AC048

44,000

NONE

11.70

11.70

10.05

CC5A/CD5AW048

45,000

NONE

11.70

11.70

10.15

CC5A/CD5AW060

46,500

NONE

12.00

12.00

10.35

CD5AA048

45,000

NONE

11.70

11.70

10.15

CE3AA048

45,000

NONE

11.70

11.70

10.25

CE3AA060

46,000

NONE

12.00

12.00

10.40

CF5AA048

44,000

NONE

11.70

11.70

10.20

Содержание Puron 38TZA

Страница 1: ...ust resistant quality appearance The coil is protected by an enhanced WeatherArmor heavy duty inlet grille Constructed of a coated 12 gage steel wire grid and with spacing of 3 8 in the guard helps to protect the coil from inclement weather vandalism and incidental damage It provides protection while not restrictingairflowandmaintainingeaseof coil inspection and cleaning Puron Environmentally Frie...

Страница 2: ...ns which include long line sets 50 to 175 ft or applications which require the system to operate at low outdoor temperatures below 55 F 12 8 C are approved under Carrier s standard guidelines Carrier Coils and Fan Coils to Complete the System Carrier specially designs both the outdoor product and indoor coil products to operate with assured reliability and performance A wide range of indoor coil o...

Страница 3: ...e Charge Lb 5 31 5 19 5 43 5 43 5 75 8 00 COND FAN Propeller Type Direct Drive Air Discharge Vertical Air Qty CFM 1800 2400 2400 2800 2800 3300 Motor HP 1 5 1 8 1 8 1 5 1 5 1 4 Motor RPM 825 825 825 825 825 1100 COND COIL Copper Tube Aluminum Plate Fin Face Area Sq ft 12 2 12 2 12 2 12 2 12 2 18 2 Fins per In 25 25 25 25 25 25 Rows 1 1 1 1 1 1 Circuits 2 2 2 2 2 3 VALVE CONNECT In ID Sweat Vapor 5...

Страница 4: ...g Fan Motor Size 060 KH45LG140 RCD Filter Drier Suction Line Sizes 024 036 KH45LG141 RCD Filter Drier Suction Line Sizes 042 060 KAALS0201LLS Liquid Line Solenoid Valve Sizes 024 060 KSASF0101AAA Support Feet All Sizes KAACF0801MED Coastal Filter All Sizes THERMOSTAT SUBBASE PKG DESCRIPTION TSTATCCNAC01 B Thermostat Auto Changeover Non Programmable F C 1 Stage Heat 1 Stage Cool TSTATCCPAC01 B Ther...

Страница 5: ...re controller is a cycle control device activated by a temperature sensor mounted on a header tube of the outdoor coil It is designed to cycle the outdoor fan motor in order to maintain condensing temperature within normal operating limits approximately 100 F 37 8 C high and 60 F 15 5 C low The control will maintain working head pressure at low ambient temperatures down to 0 F 17 8 C when properly...

Страница 6: ...d Amps NOTE Control circuit is 24 v on all units and requires external power source Copper wire must be used from service disconnect to unit All motors compressors contain internal overload protection Sound power dBA UNIT SIZE SERIES V PH OPER VOLTS COMPR FAN FLA MCA 60 C MIN WIRE SIZE 75 C MIN WIRE SIZE 60 C MAX LENGTH Ft 75 C MAX LENGTH Ft MAX FUSE OR CKT BKR AMPS Max Min LRA RLA 024 30 32 208 2...

Страница 7: ...t control is used max 125 F 2 Series designation is the 13th position of the unit model number 3 Center of gravity 4 NOTES A97084 DIMENSIONS IN UNIT SIZE SERIES UNIT DIMENSIONS MINIMUM MOUNTING PAD DIMENSIONS A B C D E F G H J K L M N 024 30 32 27 13 16 30 34 15 16 4 9 3 4 15 1 2 21 7 8 5 8 8 3 16 18 1 2 19 3 4 13 2 15 16 26 x 32 030 30 32 27 13 16 30 34 15 16 4 9 3 4 15 1 2 21 7 8 3 4 8 3 16 18 1...

Страница 8: ...0 TDR 12 50 12 50 11 00 CK5A CK5BW030 23 200 TDR 13 00 13 00 11 10 COILS 58MVP080 14 VARIABLE SPEED FURNACE CC5A CD5AW024 23 000 TDR 12 50 12 50 11 10 CC5A CD5AW030 23 200 TDR 13 00 13 00 11 20 CK5A CK5BW024 23 000 TDR 12 50 12 50 11 25 CK5A CK5BW030 23 200 TDR 13 00 13 00 11 30 COILS 58U H X V060 12 VARIABLE SPEED FURNACE CC5A CD5AA024 23 000 TDR 12 50 12 50 10 95 CC5A CD5AA030 23 600 TDR 13 00 1...

Страница 9: ...00 TDR 13 00 13 00 11 60 COILS 58U H X V060 12 VARIABLE SPEED FURNACE CC5A CD5AA030 27 800 TDR 12 50 12 50 11 00 CC5A CD5AA036 29 000 TDR 13 00 13 00 11 50 CC5A CD5AW030 27 800 TDR 12 50 12 50 11 00 CK3BA030 27 800 TDR 12 50 12 50 11 10 CK3BA036 29 000 TDR 13 00 13 00 11 55 CK5A CK5BA030 27 800 TDR 12 50 12 50 11 10 CK5A CK5BA036 29 000 TDR 13 00 13 00 11 55 CK5A CK5BN036 29 000 TDR 13 00 13 00 11...

Страница 10: ... 13 00 13 00 11 45 CK5A CK5BW036 34 600 TDR 13 00 13 00 11 40 COILS 58MVP120 20 VARIABLE SPEED FURNACE CC5A CD5AA042 34 600 TDR 13 00 13 00 11 40 CD5AW036 34 600 TDR 13 00 13 00 11 35 CK5A CK5BA042 34 600 TDR 13 00 13 00 11 45 CK5A CK5BW036 34 600 TDR 13 00 13 00 11 35 COILS 58U H X V060 12 VARIABLE SPEED FURNACE CC5A CD5AA036 34 600 TDR 12 50 12 50 11 10 CK3BA036 34 600 TDR 12 50 12 50 11 10 CK5A...

Страница 11: ...2 39 000 TDR 12 20 12 20 10 60 CK3BA048 39 500 TDR 12 50 12 50 10 75 CK5A CK5BA042 39 000 TDR 12 20 12 20 10 60 CK5A CK5BA048 39 500 TDR 12 50 12 50 10 75 COILS 58MVP100 20 VARIABLE SPEED FURNACE CC5A CD5AA042 39 000 TDR 12 50 12 50 10 90 CC5A CD5AC048 39 000 TDR 12 50 12 50 10 80 CD5AA048 39 500 TDR 12 50 12 50 10 95 CK3BA042 39 000 TDR 12 50 12 50 10 90 CK3BA048 39 500 TDR 12 50 12 50 11 05 CK5A...

Страница 12: ...12 00 10 60 COILS 58MVP100 20 VARIABLE SPEED FURNACE CC5A CD5AA060 44 500 TDR 12 00 12 00 10 55 CC5A CD5AC048 44 000 TDR 12 00 12 00 10 40 CC5A CD5AW060 45 500 TDR 12 50 12 50 10 85 CD5AA048 44 500 TDR 12 00 12 00 10 55 CK3BA048 44 500 TDR 12 00 12 00 10 60 CK3BA060 45 000 TDR 12 00 12 00 10 45 CK5A CK5BA048 44 500 TDR 12 00 12 00 10 60 CK5A CK5BA060 45 000 TDR 12 00 12 00 10 80 CK5A CK5BN060 46 0...

Страница 13: ...simulation procedures 3 Determine actual CFM values obtainable for your system by referring to fan performance data in fan coil or furnace coil literature 4 Do not apply with capillary tube coils as performance and reliability are significantly affected UNIT SIZE SERIES INDOOR UNIT TOT CAP BTUH FACTORY SUPPLIED ENHANCE MENT SEER EER Standard Rating Carrier Gas Furnace or Accessory TDR Accessory TX...

Страница 14: ... 22 4 12 1 2 85 20 9 11 6 3 17 67 25 8 18 0 1 85 24 8 17 7 2 07 23 4 17 1 2 29 22 1 16 7 2 55 20 7 16 2 2 82 18 3 15 3 3 10 63 23 5 17 5 1 83 22 5 17 0 2 04 21 1 16 5 2 26 19 4 15 7 2 50 18 2 15 3 2 77 16 2 14 4 3 05 62 23 1 21 9 1 83 22 2 21 4 2 03 20 9 20 8 2 26 20 2 20 2 2 51 18 9 18 9 2 79 17 2 17 2 3 08 57 22 6 22 6 1 82 21 8 21 8 2 03 21 0 21 0 2 26 20 2 20 2 2 52 19 1 19 1 2 79 17 1 17 1 3 ...

Страница 15: ... 26 28 6 28 6 2 49 27 0 27 0 2 74 26 1 26 1 3 04 24 6 24 6 3 36 21 9 21 9 3 71 Multipliers for Determining the Performance With Other Indoor Sections Indoor Section Size Cooling Indoor Section Size Cooling Capacity Power Capacity Power CC5A CD5AA 030 0 97 0 99 CK3BA 030 0 97 0 96 036 1 00 1 00 036 1 00 0 95 CC5A CD5AW 030 0 97 0 99 CK5A CK5BA 036 1 00 0 95 CD5AW 036 1 00 1 00 CK5A CK5BW 030 0 97 0...

Страница 16: ...ection Size Cooling Indoor Section Size Cooling Capacity Power Capacity Power CC5A CD5AA 036 1 00 1 00 COILS 58MVP080 14 VARIABLE SPEED FURNACE 042 1 00 1 00 CC5A CD5AA 042 0 99 0 93 CC5A CD5AW 042 0 99 1 00 CD5AW 036 0 99 0 93 CD5AW 036 1 00 1 00 CK3BA 042 0 99 0 93 CE3AA 036 0 99 1 00 CK5A CK5BA 042 0 99 0 93 042 1 00 1 00 CK5A CK5BW 036 0 99 0 93 CF5AA 036 0 99 1 00 COILS 58MVP080 20 VARIABLE S...

Страница 17: ...ormance With Other Indoor Sections Indoor Section Size Cooling Indoor Section Size Cooling Capacity Power Capacity Power CC5A CD5AC 048 0 99 1 00 CK3BA 042 0 98 0 94 CC5A CD5AW 042 0 99 1 00 048 0 99 0 94 048 1 00 1 00 CK5A CK5BA 042 0 98 0 94 CD5A CD5AA 048 1 00 1 00 048 0 99 0 94 CE3AA 042 0 99 1 00 COILS 58MVP080 20 VARIABLE SPEED FURNACE 048 1 00 1 00 CC5A CD5AA 042 0 98 0 95 CF5AA 048 0 99 1 ...

Страница 18: ...5 2 35 2 6 09 Multipliers for Determining the Performance With Other Indoor Sections Indoor Section Size Cooling Indoor Section Size Cooling Capacity Power Capacity Power CC5A CD5AA 060 0 98 0 99 CK5A CK5BA 060 0 98 0 98 CC5A CD5AC 048 0 96 0 98 CK5A CK5BN 060 1 00 0 98 CC5A CD5AW 048 0 98 0 99 COILS 58MVP100 20 VARIABLE SPEED FURNACE 060 1 01 1 00 CC5A CD5AA 060 0 97 0 95 CD5AA 048 0 98 0 99 CC5A...

Страница 19: ... 45 1 5 95 43 7 43 7 6 66 39 9 39 9 7 41 57 51 3 51 3 4 25 48 4 48 4 4 74 47 0 47 0 5 30 45 4 45 4 5 94 43 4 43 4 6 65 39 6 39 6 7 40 1800 72 67 2 33 5 4 60 64 8 32 7 5 12 61 9 31 8 5 70 58 6 30 8 6 35 54 6 29 4 7 03 50 5 28 1 7 82 67 62 9 43 6 4 52 60 1 42 6 5 02 57 0 41 5 5 59 53 7 40 3 6 22 50 1 39 1 6 92 44 0 36 7 7 64 63 58 6 42 9 4 46 55 0 41 3 4 94 51 2 39 7 5 47 49 2 38 8 6 11 44 4 36 8 6 ...

Страница 20: ...130 0 2 92 18 0 140 0 3 27 40 TCG SDT KW 32 1 73 9 1 43 30 4 83 4 1 62 28 7 93 0 1 83 27 0 103 0 2 06 25 2 112 0 2 32 23 5 122 0 2 61 21 7 131 0 2 93 19 8 141 0 3 28 45 TCG SDT KW 35 0 75 4 1 45 33 2 84 8 1 63 31 4 94 4 1 84 29 5 104 0 2 08 27 6 114 0 2 34 25 7 123 0 2 63 23 7 133 0 2 94 21 6 142 0 3 29 50 TCG SDT KW 38 2 77 0 1 47 36 2 86 4 1 65 34 2 95 8 1 86 32 2 105 0 2 09 30 1 115 0 2 36 28 0...

Страница 21: ... SDT KW 47 2 79 4 2 23 44 7 88 7 2 53 42 2 98 2 2 86 39 6 108 0 3 25 37 0 117 0 3 66 34 4 126 0 4 12 31 6 136 0 4 63 28 7 145 0 5 19 40 TCG SDT KW 51 5 81 4 2 28 48 8 90 6 2 58 46 0 99 9 2 92 43 3 109 0 3 30 40 4 119 0 3 72 37 6 128 0 4 18 34 5 137 0 4 68 31 3 146 0 5 23 45 TCG SDT KW 56 0 83 5 2 34 53 1 92 6 2 64 50 1 102 0 2 97 47 1 111 0 3 35 44 0 120 0 3 78 40 9 130 0 4 24 37 6 139 0 4 74 34 0...

Страница 22: ...ecting refrigerant tube lengths greater than 50 ft consult Residential Split System Application Guide line and Service Manual available from equipment distributor 7 If any refrigerant tubing is buried provide a 6 in vertical rise to the valve connections at the unit Refrigerant tub ing lengths up to 36 in may be buried without further consideration For buried lines longer than 3 ft consult your lo...

Страница 23: ...23 Typical installation A98600 AIR CLEANER FURNACE FURNACE COIL AIR CONDITIONER COMFORT VENTILATOR HUMIDIFIER COMFORT ZONE II EQUIPMENT CONTROLLER ...

Страница 24: ...pletion potential Puron is approved under the EPA s Significant New Alternatives Program SNAP Unit Cabinet Unit cabinet will be constructed of galvanized steel bonderized and coated with a powder coat paint Fans Condenser fan will be direct drive propeller type discharging air upward Air Cooled Split System Air Conditioner 38TZA 2 to 5 Tons Nominal Condenser fan motors will be totally enclosed 1 p...

Отзывы: