7
Description
Alarm relay output
circuit A
Alarm relay output
circuit B
Boiler relay output
Contact 1:
start/stop
Contact 2:
heat/cool or heat reclaim
selection
Contact 3:
demand limit selection
Contact 4:
demand limit selection
Contact 5:
setpoint selection
Control contact 6:
setpoint selection
User safety loop input
Connection to CCN
Connector/channel
J3 / CH24
J3 / CH24
J3 / CH25
J4 / CH8
J4 / CH9
J4 / CH10
J4 / CH10
J4 / CH8
J4 / CH9
J4 / CH11a
J12
Terminal
30A - 31A
30B - 31B
37 - 38
32 - 33
63 - 64
73 - 74
75 - 76
65 - 66
67 - 68
34 - 35
1 - 2 - 3
Board
Master NRCP-
BASE
Slave NRCP-
BASE
Master NRCP-
BASE
Master NRCP-
BASE
Master NRCP-
BASE
Master NRCP-
BASE
Slave
NRCP-BASE
Slave
NRCP-BASE
Slave
NRCP-BASE
Master
NRCP-BASE
Master
NRCP-BASE
Remarks
Indicates alarms, circuit A
Indicates alarms, circuit B
Boiler start/stop control output.
See section 5.13.
The contacts are used for unit start/stop and
heat/cool control. They are only taken into
account if the unit is under remote operation
control (rEM).
These dry contacts are used for demand
limit selection. See description of these
contacts in section 3.6.2.
The remote demand limit selection contact
is active whatever the operating type of the
unit.
These dry contacts are used for setpoint
selection.
They are only taken into account if the unit
is in remote control operating type (rEM).
See the description of these contacts in
sections 3.6.4.
This contact is mounted in series with the
water flow control contact. It can be used for
any customer safety loop that requires that
the unit is stopped, if it is open.
If it is unused this contact must be bridged.
A RS-485 bus is used for connection to the
CCN.
- Pin 1:
- Pin 2: ground
- Pin 3: signal -
Remarks
Volt-free contact 24 V a.c.
48 V d.c. max, 20 V a.c. or
min. 20 V d.c., 3 A max, 80
mA min, external power
supply.
Connector: 4 pin
WAGO 734-104 pitch 3.5.
One per board needed.
24 V a.c., 20 mA
Connector: 8 pin
WAGO 734-168, pitch 3.5
Connector: 3 pin
WAGO 231-303, pitch 5.08
DUAL-CIRCUIT UNITS
3.6.2 - Demand limit or setpoint volt-free contact for single-
circuit units
On single-circuit units contact 3 determines the selection of
demand limit or setpoint, based on the configuration (see User
Configuration 1 menu).
Demand limit selection
Setpoint selection
100%
Limit 1
Setpoint 1
Setpoint 2
(no limit)
Contact 3 Open
Closed
Open
Closed
3.6.3 - Demand limit volt-free contact for dual-circuit units
On dual-circuit units the operation of the demand limit
selection contacts is multiplexed. The demand limit setpoints are
adjustable in the setpoint menu (see section 4.3.8).
100%
Limit 1
Limit 2
Limit 3
(no limit)
Contact 3 Open
Closed
Open
Closed
Contact 4 Open
Open
Closed
Closed
3.6.4 - Water setpoint selection volt-free contact with
multiplexing for dual-circuit units
On dual-circuit units the operation of the cold water or hot
water setpoint selection contacts is multiplexed. The set-points
are adjustable in the setpoint menu (see section 4.3.8). Auto
means that the active setpoint is determined by the setpoint
schedule (see section 5.6.1).
Cooling mode
Setpoint 1
Setpoint 2
Setpoint 3
Auto
Contact 5
Open
Open
Closed
Closed
Contact 6
Open
Closed
Open
Closed
Heating mode
Setpoint 1
Setpoint 2
Setpoint 3
Auto
Contact 5
Open
Open
Closed
Closed
Contact 6
Open
Closed
Open
Closed