4.3.11.4 - Description of the User 2 Configuration sub-menu
This menu is only accessible if the unit is equipped with an
optional CCN/clock board
4.3.11.6 - Description of the Time Schedules sub-menus
The control provides two timer programs: schedule 1 and
schedule 2 that can be activated if the unit is equipped with an
optional CCN/clock board (if the CCN/clock board is not
installed, the two schedules are permanently in occupied
mode).
The first timer program (schedule #1) provides a means to
automatically switch the unit from an occupied mode to an
unoccupied mode: the unit is started during occupied periods.
The second timer program (schedule #2) provides a means to
automatically switch the active setpoint from an occupied
setpoint to an unoccupied setpoint: cooling setpoint 1 is used
during occupied periods, cooling or heating setpoint 2 during
unoccupied periods. Heating setpoint 3 is activated during
holiday periods. For additional information on set-point
activation see section 5.6.1.
Each schedule consists of eight time periods set by the operator.
These time periods can be flagged to be in effect or not in effect
on each day of the week plus a holiday period (see section
4.3.11.7 on public holidays). The day begins at 00.00 hours and
ends at 24.00 hours.
USER 1 CONFIGURATION SUB-MENU
ITEM
FORMAT
UNITS
DEFAULT
COMMENTS
0
USEr 2 Menu
When selected this item authorises return to the previous menu.
1[1]
YES/no
-
no
Periodic pump quick-start of the water pump(s)
Yes = the pump is started periodically when the unit is manually stopped.
No = periodic pump start is disabled
When the unit is manually stopped (e.g. during the winter season) the pump is started each day at 14.00
hours for 2 seconds. If two pumps are available, pump #1 is started on odd days and pump #2 on even days.
2 [1]
n
1
n
2
n
3
n
4
Night control mode - start time*
00:00 to 23:59
-
00:00
Authorises entering the time of day at which the night control mode starts. During this period the fan runs at
low speed (to reduce fan noise) if permitted by operating conditions, and unit capacity is limited to the
maximum night values.
3 [1]
n
1
n
2
n
3
n
4
Night control mode - end time*
00:00 to 23:59
-
00:00
Authorises entering the time of day at which the night control mode ends.
4 [1]
0 to 100
%
-
Night mode demand limit value.
Authorises configuration of the maximum capacity authorised during the night mode.
5 [1]
0 or 65 to 99
-
0
Schedule 1 clock number (for unit on/off schedule, see section 4.3.11.6).
0 = schedule in local operating mode
65 to 99 = schedule in CCN operating mode
6 [1]
0 or 65 to 99
-
0
Schedule 2 clock number (schedule for setpoint selection, see section 4.3.11.6).
0 = schedule in local operating mode
65 to 99 = schedule in CCN operating mode
7 [1]
1 to 239
-
1
CCN element address.
No two network elements can have the same element number and bus number at the same time.
8 [1]
0 to 239
-
0
CCN bus number.
No two network elements can have the same element number and bus number at the same time.
*
n
1
n
2
: hours (00 to 23). The first time the Enter button is continuously pressed, the first two characters in the 4-digit display flash so that hours can be adjusted.
n
3
n
4
: minutes (00 to 59). Continuous pressing of the Enter key again causes the last two characters to flash so that minutes can be adjusted.
4.3.11.5 - Description of Date and Time configuration sub-
menu
This menu is only accessible, if the unit is equipped with an
optional CCN/clock board.
DATE & TIME CONFIGURATION SUB-MENU
ITEM
FORMAT
COMMENTS
0
dAtE MEnu
When selected this item authorises return to the
previous menu.
1
n
1
n
2
n
3
n
4
Current time setting.
00:00 to 23:59
n
1
n
2
: hours (00 to 23). The first time the Enter button is
continuously pressed, the first two characters in the 4-
digit display flash so that hours can be adjusted.
n
3
n
4
: minutes (00 to 59). Continuous pressing of the
Enter key again causes the last two characters to flash
and minutes can be adjusted.
2
Current day of week setting.
«Mon»
Monday
«tUe»
Tuesday
«uEd»
Wednesday
«tHu»
Thursday
«FrI»
Friday
«SAt»
Saturday
«Sun»
Sunday
3
n
1
n
2
n
3
n
4
Current day and month setting.
01:01 to 31:12
n
1
n
2
:day (01 to 31). The first time the Enter button is
continuously pressed, the first two characters in the 4-
digit display flash so that day can be adjusted.
n
3
n
4
:month (01 to 12). Continuous pressing of the
Enter key again causes the last two characters to flash
so that month can be adjusted.
4
nnnn
Current year setting.