16
SETPOINTS MENU [2]
ITEM
FORMAT UNITS
RANGE
0
±nn.n
°C
See table below
1
±nn.n
°C
See table below
2
nnn
°C
See table below
3 [1]
nnn
°C
See table below
4 [1]
nn.n
°C
See table below
5
nnn
%
0 to 100
6 [1]
nnn
%
0 to 100
7 [1]
nnn
%
0 to 100
8 [1]
±nn.n
°C/min
0.1 to 1.1
9 [1]
±nn.n
°C
See table below
10 [1]
±nn.n
°C
See table below
11 [1]
±nn.n
°C
See table below
12 [1]
±nn.n
°C
See table below
13 [1]
±nn.n
°C
See table below
14 [1]
±nn.n
°C
-16 to 16
4.3.8 - Description of the Setpoints menu
1
This item is displayed in certain unit configurations only.
2
All points contained in this table can be modified.
*
Those setpoints can be used for entering or leaving water temperature control. By default the unit controls the evaporator entering fluid temperature.
Leaving fluid temperature control requires a parameter modification in the Service Configuration menu.
**
These parameters are only accessible when reset based on OAT or delta T has been selected in the User Configuration 1 menu. See section 4.3.11.3 & 5.6.2.
COMMENTS
This item lets you display and modify Cooling setpoint 1*
This item lets you display and modify Cooling setpoint 2*
This item lets you display and modify Heating setpoint 1*, only displayed for heat pumps.
This item lets you display and modify Heating setpoint 2*, only displayed for heat pumps.
This item lets you display and modify Heating setpoint 3*, only displayed for heat pumps.
Demand limit 1 setpoint. Limitation by volt-free contact. This item is used to define the maximum
capacity that the unit is authorised to use, if the demand limit contact(s) activate limit 1. Contact control
depends on the unit type and configuration. See sections 3.6.4 and 3.6.5.
Demand limit 2 setpoint. Limitation by volt-free contact. This item is used to define the maximum
capacity that the unit is authorised to use, if the demand limit contact(s) activate limit 2. Contact control
depends on the unit type and configuration. Displayed and used only for dual-circuit units. See section
3.6.5 for the contact control description.
Demand limit 3 setpoint. Limitation by volt-free contact. This item is used to define the maximum
capacity that the unit is authorised to use, if the demand limit contact(s) activate limit 3. Displayed and
used only for dual-circuit units. See section 3.6.5 for the contact control description.
Cooling or heating ramp loading rate. This parameter is only accessible if the ramp function is
validated in the User Configuration 1 menu. This item refers to the rates of temperature drop in °C in the
evaporator. When capacity loading is effectively limited by the ramp, mode 7 is active.
Zero reset threshold, cooling mode**
Full reset threshold, cooling mode**
Full reset value, cooling mode**
Zero reset threshold, heating mode**
Full reset threshold, heating mode**
Full reset value, heating mode**
4.3.6 - Description of the Temperatures menu
TEMPERATURES MENU [2]
ITEM
FORMAT
UNITS
COMMENTS
0
±nn.n
°C
Evaporator entering water temperature
1
±nn.n
°C
Evaporator leaving water temperature
2 [1]
±nn.n
°C
Condenser entering water temperature
3 [1]
±nn.n
°C
Condenser leaving water temperature
4
±nn.n
°C
Outdoor temperature
5
±nn.n
°C
Saturated discharge temperature, circuit A
6
±nn.n
°C
Saturated suction temperature, circuit A
7 [1]
±nn.n
°C
Saturated discharge temperature, circuit B
8 [1]
±nn.n
°C
Saturated suction temperature, circuit B
9 [1]
±nn.n
°C
Leaving water temperature, drycooler
10 [1]
±nn.n
°C
Chilled water system temperature. Used for
master/slave control.
1
This item is displayed in certain unit configurations only
2
Access to this menu is read-only.
4.3.7 - Description of the Pressures menu
PRESSURES MENU [2]
ITEM
FORMAT
UNITS
COMMENTS
0
nnnn
kPa
Discharge pressure, circuit A.
Relative pressure.
1
nnn
kPa
Suction pressure, circuit A.
Relative pressure.
2 [1]
nnnn
kPa
Discharge pressure, circuit B.
Relative pressure.
3 [1]
nnn
kPa
Suction pressure, circuit B.
Relative pressure.
1
This item is displayed in certain unit configurations only.
2
Access to this menu is read-only