19
SUB-MENU PERIOD CONFIGURATION*
Item
PERIOD 1 to 8
[PEriod X MEnu]*
0
Return to previous menu
1
Start of occupied period
2
End of occupied period
3
Selection Monday
4
Selection Tuesday
5
Selection Wednesday
6
Selection Thursday
7
Selection Friday
8
Selection Saturday
9
Selection Sunday
10
Selection holidays
SUB-MENU HOLIDAY CONFIGURATION*
Item
HOLIDAYS 1 to 16
[HoLidAy X MEnu]*
0
Return to previous menu
1
Start month holidays
3
Start day holidays
4
Number of days, holidays
*
only displayed if configuration requires.
NOTE: The items in brackets show what is displayed on the
user interface.
USER
[USEr]
CONFIGURATION
PERIOD 1
PERIOD 2
PERIOD 3
PERIOD 4
PERIOD 5
PERIOD 6
PERIOD 7
PERIOD 8
PERIOD 1
PERIOD 2
PERIOD 3
PERIOD 4
PERIOD 5
PERIOD 6
PERIOD 7
PERIOD 8
HOLIDAY 1
HOLIDAY 2
HOLIDAY 3
HOLIDAY 4
HOLIDAY 5
HOLIDAY 6
HOLIDAY 7
HOLIDAY 8
HOLIDAY 16
HOLIDAY 15
...
...
...
USER2
[USEr 2]
SCHEDULE 1
[SCHEduLE 1]*
SCHEDULE 2
[SCHEduLE 2]*
HOLIDAYS
[HOLIDAYS]*
HOUR + DATE
[dAtE]*
BROADCAST
[broAdCASE]*
USER1
[USEr 1]
4.3.10.3 - Tests
This function allows the user to test the outputs individually, if
the machine is completely shut down (LOFF). To carry out a
manual test use the arrow keys to access the output to be tested
and press the Enter key (longer than 2 seconds) to activate the
modification mode. The password is automatically requested, if it
has not previously been verified. The Outputs/Test LED on the
user interface begins to flash. Enter the desired test value and
again press Enter to start the test. 'TESt' is displayed on the 4-
digit display alternately with the value tested.
The Outputs/Test LED stops flashing. Press the Enter key or an
arrow key to stop the test.
4.3.11- Description of the configuration menu
4.3.11.1- General
This menu can be used to display and modify all configura-
tions: Factory, Service and User. Only the User Configuration can
be modified by the end-user. The Factory, Service and master/
slave configurations are not described in this document. A
configuration can only be modified if the unit is fully stopped
(LOFF).
The menus User 1 [USEr 1] and User 2 [USEr 2] are password-
protected. The other menus are directly accessible, except if
item 6 of the User 1 menu (password for all configurations) has
been validated.
4.3.11.2 - Password
A password must be entered in order to access the test function
or to modify a configuration. It is automatically requested, if
necessary: 'EntEr PASS' is displayed on the 4-digit display and
the configuration menu LED flashes, indicating that the modi-
fication mode is active. Press the arrow keys until the value '11'
is displayed on the 4-digit display. Press Enter to validate this.
The configuration menu LED stops flashing. If the password is
correct, 'Good' is displayed. If the password is incorrect, 'PASS
incorrEct' is displayed. The User password has a default value
of 11.
This value can be modified through the Service configuration.
The password can be entered if the unit is fully stopped, other-
wise 'ACCES dEniEd' (access denied) will be displayed on the
4-digit display. The controller automatically deactivates the
password after 5 minutes without activity (i.e. no buttons
pressed) or after powering up.
Содержание PRO-DIALOG PLUS 30RW