4–11
T-362
Configurable Functions
- Cd45 through Cd48 are user-selectable functions. The operator can change the value
of these functions to meet the operational needs of the container.
Cd45 Vent Position Sensor (VPS) Position
Cd45 displays positional values for the Vent Position Sensor (VPS). Values are to 240 for UPPER, 0 to
225 for LOWER. If a unit does not configured for a VPS, dashes will be displayed “-----”.
When configured for VPS, Cd45 displays the current VPS position in units of 5 CMH (displayed as “CM”)
or CFM (displayed as “CF”) depending on the selection of Cd46 (Airflow display units), Cd28 (Metric/
Imperial) or the pressing of the deg C/F key.
Cd45 will display whenever the control detects movement via the VPS unless AL50 is active. Cd45 will
display for 30 seconds, then time out and return to the normal display mode.
Cd46 Airflow Display Units
Cd46 selects the airflow units to be displayed by Cd45 if configured for Vent Position Sensor (VPS) or
displayed by “USER/FLO” under Cd43 if configured for Autoslide.
• CF = Cubic Feet per Minute
• CM = Cubic Meters per Hour
• bOth = Displays CF or CM depending on the setting of Cd28 (Metric/Imperial) or the pressing of the
degree C/F key.
Cd47 Variable Economy Temperature Setting
Cd47 controls the Variable Economy Temperature setting. This is applicable when Economy Mode
(CnF22) is set to 3-cust. Cd47 will show dashes “----” if the unit is not configured for Economy Mode.
When the unit has a perishable setpoint and Economy Mode is active, at the start of each cooling or
heating cycle, high speed evaporator fans will run for three minutes. After three minutes, the evaporator
fans will be switched to low speed any time that the supply temperature is /- 0.25°C of the setpoint
and the return temperature is less than or equal to the supply tempe the user selected Cd47
(values are 0.5°C - 4.0°C, default is 3.0°C).
Table 4–4 Controller Function Codes
Code Description
Содержание PrimeLINE 69NT40-561-200
Страница 12: ......
Страница 18: ......
Страница 100: ......
Страница 182: ......
Страница 183: ...8 1 T 362 SECTION 8 ELECTRICAL WIRING SCHEMATIC AND DIAGRAMS Figure 8 1 LEGEND Standard Unit Configuration ...
Страница 184: ...T 362 8 2 ELECTRICAL WIRING SCHEMATIC AND DIAGRAMS Figure 8 2 Schematic Diagram ...
Страница 185: ...8 3 T 362 ELECTRICAL WIRING SCHEMATIC AND DIAGRAMS Figure 8 3 Unit Wiring Diagram Sheet 1 of 2 ...
Страница 186: ...T 362 8 4 ELECTRICAL WIRING SCHEMATIC AND DIAGRAMS Figure 8 4 Unit Wiring Diagram Sheet 2 of 2 ...
Страница 187: ...8 5 T 362 ELECTRICAL WIRING SCHEMATIC AND DIAGRAMS Figure 8 5 Legend Unit With Auto Transformer ...
Страница 188: ...T 362 8 6 ELECTRICAL WIRING SCHEMATIC AND DIAGRAMS Figure 8 6 Schematic Diagram Unit With Auto Transformer ...