42

The Average Occupied Heat Set Point displays the

Occupied Heat set point from the Linkage Thermostat.
Average Occupied
Heat Set Point:

Display Units:

Degrees F (Degrees C) 

Display Range:

0.0 to 99.9

Default Value:

0.0

Network Access: None

The Average Occupied Cool Set Point displays the Occu-

pied Cool set point from the Linkage Thermostat.
Average Occupied
Cool Set Point:

Display Units:

Degrees F (Degrees C) 

Display Range:

0.0 to 99.9

Default Value:

0.0

Network Access: None

The Average Unoccupied Heat Set Point displays the Unoc-

cupied heat set point from the Linkage Thermostat.
Average Unoccupied
Heat Set Point:

Display Units:

Degrees F (Degrees C) 

Display Range:

0.0 to 99.9

Default Value:

0.0

Network Access: None

The Average Unoccupied Cool Set Point displays the Unoc-

cupied cool set point from the Linkage Thermostat.
Average Unoccupied
Cool Set Point:

Display Units:

Degrees F (Degrees C) 

Display Range:

0.0 to 99.9

Default Value:

0.0

Network Access: None

The Average Zone Temperature displays the space tempera-

ture from the Linkage Thermostat.
Average Zone
Temperature:

Display Units:

Degrees F (Degrees C) 

Display Range:

0.0 to 99.9

Default Value:

0.0

Network Access: None

The Average Occupied Zone Temperature displays the

space temperature from the Linkage Thermostat during occu-
pied periods.
Average Occupied
Zone Temperature: Display Units:

Degrees F (Degrees C) 

Display Range:

0.0 to 99.9

Default Value:

0.0

Network Access: None

The Occupancy Status point displays a 1 if occupancy is re-

ported by the Linkage Thermostat. The Occupancy Status
point displays a 0 if occupancy is not reported by the Linkage
Thermostat.
Occupancy
Status:

Display Range:

0, 1

Default Value:

0

Network Access: None

Table 17 — Maintenance

NOTE: 

Bold

 values indicate points that can be forced through communications.

DESCRIPTION

VALUE

UNITS

STATUS

FORCE

NAME

Thermostat Control

No

TSTAT

Occupied

Yes

OCCUP

Timed Override in Effect

No

TIMOV

Start Bias Time

0

min

STRTBIAS

Heat

No

HEAT

Cool

No

COOL

IAQ Control

No

IAQCL

Demand Limit

No

DEMLT

Temp Compensated Start

No

TCSTR

IAQ Pre-Occupancy Purge

No

IQPRG

Unoccupied Free Cool

No

NTFCL

Fire Shutdown

No

FIRES

Linkage Control

No

DAVCL

Field/Startup Test

No

FIELD

Heat Submaster Ref

40.0

dF

SHSR

Cool Submaster Ref

150.0

dF

CCSR

Economizer Submaster Ref

120.0

dF

ECONSR

Economizer Submastr Gain

0.00

ECONGN

Compressor Starts

0.00

CMPST

Compressor 1 Runtime

0.00

HOURS

CM1RT

Compressor 2 Runtime

0.00

HOURS

CM2RT

Supply Fan Runtime

17.00

HOURS

FANRT

Linkage Thermostat

Linkage Status

2

LINKSTAT

Supervisory Element

0

SUPE-ADR

Supervisory Bus

0

SUPE-BUS

Supervisory Block

0

BLOCKNUM

Average Occ Heat Setpt

0.0

dF

OCLOSTPT

Average Occ Cool Setpt

0.0

dF

OCHISTPT

Average Unoc Heat Setpt

0.0

dF

UNLOSTPT

Average Unoc Cool Setpt

0.0

dF

UNHISTPT

Average Zone Temp

0.0

dF

AZT

Average Occ Zone Temp

0.0

dF

AOZT

Occupancy Status(1=occ)

1

OCCSTAT

Содержание PREMIERLINK 33CSPREMLK

Страница 1: ...nts Display Screen 28 Thermostat Control Input Screen 30 Alarm Service Configuration Screen 30 Controller Identification Screen 31 Holiday Configuration Screen 31 Occupancy Configuration Screen 32 Set...

Страница 2: ...on 33ZCSENCO2 sensor is an indoor wall mounted sensor with an LED light emitting diode display 33ZCT55CO2 sensor is an indoor wall mounted sensor without display The CO2 sensor also includes a space t...

Страница 3: ...de 3 Use 4 connector Molex with red white and black wires to connect the communication wires Verify the color codes in Table 2 to ensure the Red wire connects to Terminal 1 Connect the White ground wi...

Страница 4: ...U YEL RED ORN PNK PremierLink Connections 40RM Connections 38AKS Terminal Board TB2 W2 R Y1 Y2 W1 G C X WHT WHT IFC C2 C1 40RM 40RMQ 40RMS HEAT ACCESSORY W2 W1 C 4 10 9 8 3 2 1 CCSV CCR CR2 CCR LLSV C...

Страница 5: ...T FOR DUAL TRANSFORMER EQUIPTMENT RELAYS WHT BLU YEL RED ORN PNK PremierLink Connections 40RM Connections 38AKS Terminal Board TB3 W2 R Y1 Y2 W1 G C X WHT WHT IFC C2 C1 CCR 40RM 40RMQ 40RMS HEAT ACCES...

Страница 6: ...S3 EXH RVS RED RED J8 J1 PWR CUT TO ISOLATE CONTROLLER POWER CUT FOR DUAL TRANSFORMER EQUIPTMENT RELAYS WHT BLU YEL RED ORN PNK PremierLink Connections 38AH Connections ACCESSORY RELAY PACKAGE IFR CR2...

Страница 7: ...heat pump units 2 Configure AUXOUT to 3 for reversing valve 3 Configure PremierLink control for 2 stage heat and single stage cool 4 If IAQ is high priority wire HS2 to W1 If not wire HS1 to W1 Fig 2G...

Страница 8: ...ay 24 VAC 1A J8 9 HEAT STAGE 2 HS2 DO Relay 24 VAC 1A J8 6 HEAT 3 EXHAUST REVERSING VALVE HS3 EXH RVS DO Relay 24 VAC 1A J8 3 AI Analog Input DI Digital Input DO Digital Output RED RED BRN GRN FAN CMP...

Страница 9: ...tal screws field supplied 6 Use 20 gage wire to connect the sensor to the controller The wire is suitable for distances of up to 500 ft Use a three conductor shielded cable for the sensor and set poin...

Страница 10: ...uter jacket of the cable Do not pull or draw cable with a force that may harm the physical or electrical properties Avoid splices in any control wiring Perform the following steps to connect the SAT s...

Страница 11: ...is recommended For installation where it is not necessary to reach the control it may be mounted higher on the wall or on the ceiling provided the location represents a good sampling of air Wiring the...

Страница 12: ...LK SENSOR 2 SENSOR 1 RED RED BLK SENSOR 3 SENSOR 4 BLK BLK RED RED RED BLK BLK SENSOR 8 SENSOR 9 SENSOR 5 RED BLK SENSOR 6 SENSOR 7 BLK RED SPACE TEMPERATURE AVERAGING 4 SENSOR APPLICATION SPACE TEMPE...

Страница 13: ...5SPT 33ZCT56SPT 33ZCT58SPT Space Temperature Sensors 33ZCSENSAT Supply Air Temperature Sensor 33ZCSENCO2 Outdoor and 33ZCT55CO2 33ZCT56CO2 Indoor Air Quality Sensors OAT Outdoor Air Temperature Sensor...

Страница 14: ...O 2 Sensor 33ZCT55CO2 33ZCT56CO2 NOTE No wire is connected to connector J 5 pin 4 You must relocate a wire from an unused terminal Typically one of the red wires from connector J 4 may be used for thi...

Страница 15: ...red wires from J4 connector to prevent 24 vac shorting other components or ground Inputs on J4 are 24 vac Red leads are voltage source Fig 9 PremierLink Controller Sensor Wiring With Programmable or N...

Страница 16: ...move red wire from J4 9 to prevent 24 vac shorting out other components or ground Inputs on J4 are 24 vac Red leads are voltage source Fig 10 PremierLink Field Installed Controller Sensor Wiring Discr...

Страница 17: ...3 2 1 2 1 H G 24 VAC OR 24 VDC NC ALARM RELAY CONTACTS COM NO 0 10VDC SIG COM J5 3 4 20mA J5 2 Fig 12 Outdoor Air Quality CO2 Sensor 33ZCSENCO2 Typical Wiring Diagram Fig 13 Outdoor Air Quality Sensor...

Страница 18: ...control the enthalpy switch receiver option and the outdoor and return air sensor option Either option can be used to indicate when the outdoor air is suitable for free cooling ENTHALPY SWITCH RECEIVE...

Страница 19: ...he indoor enthalpy The LOW Enthalpy terminal is energized when the outdoor enthalpy is lower than the indoor enthalpy The relay output is wired to the unit economizer which will open or close dependin...

Страница 20: ...enthalpy sensor will not calculate enthalpy OUTDOOR AND RETURN AIR ENTHALPY SEN SORS The differential enthalpy control is supplied as a field installed accessory to be used with the Economizer damp e...

Страница 21: ...e and remove 1 2 in of insulation from each conductor 6 Connect the RED wire to spade connector on the sensor Connect the BLK wire to S spade connector on the sensor Use wire nuts or closed end crimp...

Страница 22: ...emove power from unit 2 Remove the logic module from the actuator and discard 3 Mount the adapter onto the actuator by gently pushing the adapter onto terminals P1 and P of actuator 4 NOTE Be sure the...

Страница 23: ...ierLink Controller is grounded and actuator is grounded on common side then common wire from PremierLink controller J9 2 is not needed Fig 25 PremierLink Controller Wiring Differential Enthalpy Contro...

Страница 24: ...erLink controller connect the pink wire on actuator to purple wire on PremierLink J9 1 See Fig 30A For the Belimo Actuator connect the white wire on the ac tuator to J9 1 on the PremierLink controller...

Страница 25: ...UATOR 50TJ400812 M9206 GGC 2 ECONOMIZER 12 PIN HARNESS RED 24 VAC 1 2 3 4 5 BRN TRANSFORMER GROUND 6 7 8 9 10 11 12 PNK PL6 4 20mA TO J9 1 ON PREMIERLINK CONTROLLER 12 PIN FEMALE MOLEX CONNECTOR 12 8...

Страница 26: ...the power has been restored To enable the feature again the switch must be put back to the 0 position and power must be restored this prevents subsequent resets to factory defaults if the switch is l...

Страница 27: ...ator See the base unit controls and troubleshooting guide for more information Pressing any key while in the default display mode will cause the Navigator to enter its manual mode In this mode all sub...

Страница 28: ...lt Value 0 0 Display Range 40 0 to 245 0 Network Access Read Write OUTDOOR AIR TEMPERATURE Temperature of the air leaving the unit downstream of any cool or heat sources measured by a 10K thermistor T...

Страница 29: ...er timer value to zero will provide the same function The value of the timer is stored in EEPROM to protect it in the event of a power failure This is done periodically every 24 hours The filter timer...

Страница 30: ...wn parts per million implied Default Value 0 Display Range 0 to 5000 Network Access Read Write FIRE SHUTDOWN While in sensor control mode this point can be used to receive a signal from a smoke detect...

Страница 31: ...ality Low Limit Display Units PPM implied Display Range 0 0 to 5000 0 Default Value 0 0 Indoor Air Quality High Limit Display Units PPM implied Display Range 0 0 to 5000 0 Default Value 1200 0 Table 9...

Страница 32: ...mes will take effect on a day configured as a holiday A zero means the schedule period will not apply to that day Day of week Range 0 or 1 Default Values 11111111 for period 1 00000000 for the rest of...

Страница 33: ...pecifies the value for Purge Minimum Damper Position for High Outdoor Air temperature conditions IAQ Pre Occupancy Purge Algorithm shall use this value whenever Outdoor Air Temperature is above or at...

Страница 34: ...e 3 0 Derivative Gain Range 20 0 to 20 0 Default Value 5 0 Starting Value Units Degrees F Range 40 0 to 120 0 Default Value 75 0 STAGED HEATING The Staged Heating function is used for two position val...

Страница 35: ...be sent to the device The sign of the submaster gain limit determines the direction in which the output will be driven in response to a given error The gain is expressed in percent change in output p...

Страница 36: ...and the supply air temperature goes below Lockout Temperature set point the compressor will cycle to maintain the supply air set point The minimum on and off times and stage up and down timers will st...

Страница 37: ...ing capacity is limited When Demand Limit option is enabled the control will re spond to the Loadshed Controller commands such as Redline Alert Shed Unshed and Redline Cancel Demand Limiting Range Dis...

Страница 38: ...sed by bringing in too much outdoor air to maintain IAQ set point When an override condition takes place IAQ control is disabled and Economizer Mini mum Position is set to the user configured value MD...

Страница 39: ...rk Access None OVERRIDE DURATION The Override Duration point displays the number of minutes remaining for an occupancy override which is in effect If the override duration value down loaded is in hour...

Страница 40: ...TIMED OVERRIDE IN EFFECT The Timed Override In Effect point shows if a timed override is currently in effect Timed Override in Effect Display Range No Yes Default Value No Network Access Read Only STA...

Страница 41: ...omizer Submaster Reference Display Units Degrees F Degrees C Display Range 48 to 120 Default Value 120 Network Access Read Only ECONOMIZER SUBMASTER GAIN Displays the cur rent Submaster gain multiplie...

Страница 42: ...play Units Degrees F Degrees C Display Range 0 0 to 99 9 Default Value 0 0 Network Access None The Occupancy Status point displays a 1 if occupancy is re ported by the Linkage Thermostat The Occupancy...

Страница 43: ......

Страница 44: ...inue or change at any time specifications or designs without notice and without incurring obligations PC 111 Catalog No 533 80072 Printed in U S A Form 38 54SI Pg 44 11 02 Replaces 38 52SI Book 1 4 Ta...

Отзывы: