background image

29

Table 7 — Points Display

NOTE: 

Bold

 values indicate points that can be forced through communications.

SUPPLY FAN STATUS — This  point  displays  the  Supply
Fan status if controller is configured to receive input from the
Supply Fan. Otherwise this point will display the output state
of the Supply Fan Relay. This mode can only be used when the
controller is in sensor control mode.
Supply Fan
Status:

Display Units:

Discrete ASCII

Default Value:

Off

Display Range:

Off/On

Network Access: Read Only

ECONOMIZER DAMPER POSITION — This  point  dis-
plays the current commanded damper position of the
economizer 4 to 20 mA on the J-9 connector. The 4 to 20 mA
signal is scaled linearly over the range of 0 to 100% of the Sup-
ply Fan Relay.
Economizer
Position:

Display  Units:

% Open

Default Value:

0

Display Range:

0 to 100

Network Access: Read/Write

CURRENT MINIMUM DAMPER POSITION — This point
displays the current minimum damper position if an Indoor Air
Quality routine is not active. If an Indoor Air Quality sensor is
installed and the differential air quality set point has been
exceeded, this point will display the current calculated mini-
mum position deemed necessary to maintain the air quality in
the space.
Current Minimum
Damper Position: Display  Units:

% Open

Default Value:

0

Display Range:

0 to 100

Network Access: Read Only

FILTER STATUS — The filter status point will be shown as
“CLEAN” until the run time of the fan exceeds the configured
Filter Timer Hours. When the user-configured Filter Timer
Hours has been exceeded, the Filter Status will display
“DIRTY” and a CCN alarm will be generated. Forcing the
point to “CLEAN” will clear the alarm condition and will reset
the timer. (Setting the configured filter timer value to zero will
provide the same function.) The value of the timer is stored in
EEPROM to protect it in the event of a power failure. This is
done periodically every 24 hours. The filter timer function only
operates if the configured filter timer value (FLTTMR) is a
non-zero number.
Filter Status:

Display Units: 

Discrete ASCII

Default Value:

Clean

Display Range:

Clean/Dirty

Network Access: Read/Write 

REMOTE OCCUPIED 

MODE 

— This point displays the

status of the remote time clock input. This input is only avail-
able when the controller is being used in sensor control mode.
When the Remote Start point is on, and the zone controller is
not controlled by a Linkage Thermostat, the controller will
function in an occupied mode. When the Remote Start point is
off, the controller will revert to its own occupancy schedule.
Remote
Occupied Mode: Display  Units:

Discrete ASCII

Default Value:

Off

Display Range:

Off/On

Network Access: Read/Write

HEAT STAGE 1 — The Heat Stage 1 point provides the state
of the Heating 1 output.
Heating Stage 1: Display Units:

Discrete ASCII

Default Value:

Off

Display Range:

Off/On

Network Access: Read Only

DESCRIPTION

VALUE

UNITS

STATUS

FORCE

NAME

Space Temperature

72.2

dF

SPT

Supply Air Temperature

67.1

dF

SAT

Outdoor Air Temperature

48.8

dF

OAT

Control Setpoint

0.0

dF

CLSP

Cooling % Total Capacity

0

%

CCAP

Heating % Total Capacity

0

%

HCAP

Economizer Active

Yes

ECOS

Supply Fan Relay

On

SF

Supply Fan Status

On

SFS

Economizer Position

26.2

%

ECONPOS

Current Min Damper Pos

20

%

IQMP

Filter Status

Clean

FLTS

Remote Occupied Mode

Off

RMTOCC

Heat Stage 1

Off

HS1

Heat Stage 2

Off

HS2

Heat 3/Exhaust/Rev Valve

Off

H3_EX_RV

Enthalpy

Low

ENTH

Indoor Air Quality

367.9

IAQI

Indoor Air Quality Setpt

1050.0

IAQS

Outdoor Air Quality

0.0

Sensor failure

OAQ

Fire Shutdown

Normal

FSD

SPT Offset

0.0

^F

STO

Compressor 1

Off

CMP1

Compressor 2

Off

CMP2

Compressor Safety

Off

CMPSAFE

Содержание PREMIERLINK 33CSPREMLK

Страница 1: ...nts Display Screen 28 Thermostat Control Input Screen 30 Alarm Service Configuration Screen 30 Controller Identification Screen 31 Holiday Configuration Screen 31 Occupancy Configuration Screen 32 Set...

Страница 2: ...on 33ZCSENCO2 sensor is an indoor wall mounted sensor with an LED light emitting diode display 33ZCT55CO2 sensor is an indoor wall mounted sensor without display The CO2 sensor also includes a space t...

Страница 3: ...de 3 Use 4 connector Molex with red white and black wires to connect the communication wires Verify the color codes in Table 2 to ensure the Red wire connects to Terminal 1 Connect the White ground wi...

Страница 4: ...U YEL RED ORN PNK PremierLink Connections 40RM Connections 38AKS Terminal Board TB2 W2 R Y1 Y2 W1 G C X WHT WHT IFC C2 C1 40RM 40RMQ 40RMS HEAT ACCESSORY W2 W1 C 4 10 9 8 3 2 1 CCSV CCR CR2 CCR LLSV C...

Страница 5: ...T FOR DUAL TRANSFORMER EQUIPTMENT RELAYS WHT BLU YEL RED ORN PNK PremierLink Connections 40RM Connections 38AKS Terminal Board TB3 W2 R Y1 Y2 W1 G C X WHT WHT IFC C2 C1 CCR 40RM 40RMQ 40RMS HEAT ACCES...

Страница 6: ...S3 EXH RVS RED RED J8 J1 PWR CUT TO ISOLATE CONTROLLER POWER CUT FOR DUAL TRANSFORMER EQUIPTMENT RELAYS WHT BLU YEL RED ORN PNK PremierLink Connections 38AH Connections ACCESSORY RELAY PACKAGE IFR CR2...

Страница 7: ...heat pump units 2 Configure AUXOUT to 3 for reversing valve 3 Configure PremierLink control for 2 stage heat and single stage cool 4 If IAQ is high priority wire HS2 to W1 If not wire HS1 to W1 Fig 2G...

Страница 8: ...ay 24 VAC 1A J8 9 HEAT STAGE 2 HS2 DO Relay 24 VAC 1A J8 6 HEAT 3 EXHAUST REVERSING VALVE HS3 EXH RVS DO Relay 24 VAC 1A J8 3 AI Analog Input DI Digital Input DO Digital Output RED RED BRN GRN FAN CMP...

Страница 9: ...tal screws field supplied 6 Use 20 gage wire to connect the sensor to the controller The wire is suitable for distances of up to 500 ft Use a three conductor shielded cable for the sensor and set poin...

Страница 10: ...uter jacket of the cable Do not pull or draw cable with a force that may harm the physical or electrical properties Avoid splices in any control wiring Perform the following steps to connect the SAT s...

Страница 11: ...is recommended For installation where it is not necessary to reach the control it may be mounted higher on the wall or on the ceiling provided the location represents a good sampling of air Wiring the...

Страница 12: ...LK SENSOR 2 SENSOR 1 RED RED BLK SENSOR 3 SENSOR 4 BLK BLK RED RED RED BLK BLK SENSOR 8 SENSOR 9 SENSOR 5 RED BLK SENSOR 6 SENSOR 7 BLK RED SPACE TEMPERATURE AVERAGING 4 SENSOR APPLICATION SPACE TEMPE...

Страница 13: ...5SPT 33ZCT56SPT 33ZCT58SPT Space Temperature Sensors 33ZCSENSAT Supply Air Temperature Sensor 33ZCSENCO2 Outdoor and 33ZCT55CO2 33ZCT56CO2 Indoor Air Quality Sensors OAT Outdoor Air Temperature Sensor...

Страница 14: ...O 2 Sensor 33ZCT55CO2 33ZCT56CO2 NOTE No wire is connected to connector J 5 pin 4 You must relocate a wire from an unused terminal Typically one of the red wires from connector J 4 may be used for thi...

Страница 15: ...red wires from J4 connector to prevent 24 vac shorting other components or ground Inputs on J4 are 24 vac Red leads are voltage source Fig 9 PremierLink Controller Sensor Wiring With Programmable or N...

Страница 16: ...move red wire from J4 9 to prevent 24 vac shorting out other components or ground Inputs on J4 are 24 vac Red leads are voltage source Fig 10 PremierLink Field Installed Controller Sensor Wiring Discr...

Страница 17: ...3 2 1 2 1 H G 24 VAC OR 24 VDC NC ALARM RELAY CONTACTS COM NO 0 10VDC SIG COM J5 3 4 20mA J5 2 Fig 12 Outdoor Air Quality CO2 Sensor 33ZCSENCO2 Typical Wiring Diagram Fig 13 Outdoor Air Quality Sensor...

Страница 18: ...control the enthalpy switch receiver option and the outdoor and return air sensor option Either option can be used to indicate when the outdoor air is suitable for free cooling ENTHALPY SWITCH RECEIVE...

Страница 19: ...he indoor enthalpy The LOW Enthalpy terminal is energized when the outdoor enthalpy is lower than the indoor enthalpy The relay output is wired to the unit economizer which will open or close dependin...

Страница 20: ...enthalpy sensor will not calculate enthalpy OUTDOOR AND RETURN AIR ENTHALPY SEN SORS The differential enthalpy control is supplied as a field installed accessory to be used with the Economizer damp e...

Страница 21: ...e and remove 1 2 in of insulation from each conductor 6 Connect the RED wire to spade connector on the sensor Connect the BLK wire to S spade connector on the sensor Use wire nuts or closed end crimp...

Страница 22: ...emove power from unit 2 Remove the logic module from the actuator and discard 3 Mount the adapter onto the actuator by gently pushing the adapter onto terminals P1 and P of actuator 4 NOTE Be sure the...

Страница 23: ...ierLink Controller is grounded and actuator is grounded on common side then common wire from PremierLink controller J9 2 is not needed Fig 25 PremierLink Controller Wiring Differential Enthalpy Contro...

Страница 24: ...erLink controller connect the pink wire on actuator to purple wire on PremierLink J9 1 See Fig 30A For the Belimo Actuator connect the white wire on the ac tuator to J9 1 on the PremierLink controller...

Страница 25: ...UATOR 50TJ400812 M9206 GGC 2 ECONOMIZER 12 PIN HARNESS RED 24 VAC 1 2 3 4 5 BRN TRANSFORMER GROUND 6 7 8 9 10 11 12 PNK PL6 4 20mA TO J9 1 ON PREMIERLINK CONTROLLER 12 PIN FEMALE MOLEX CONNECTOR 12 8...

Страница 26: ...the power has been restored To enable the feature again the switch must be put back to the 0 position and power must be restored this prevents subsequent resets to factory defaults if the switch is l...

Страница 27: ...ator See the base unit controls and troubleshooting guide for more information Pressing any key while in the default display mode will cause the Navigator to enter its manual mode In this mode all sub...

Страница 28: ...lt Value 0 0 Display Range 40 0 to 245 0 Network Access Read Write OUTDOOR AIR TEMPERATURE Temperature of the air leaving the unit downstream of any cool or heat sources measured by a 10K thermistor T...

Страница 29: ...er timer value to zero will provide the same function The value of the timer is stored in EEPROM to protect it in the event of a power failure This is done periodically every 24 hours The filter timer...

Страница 30: ...wn parts per million implied Default Value 0 Display Range 0 to 5000 Network Access Read Write FIRE SHUTDOWN While in sensor control mode this point can be used to receive a signal from a smoke detect...

Страница 31: ...ality Low Limit Display Units PPM implied Display Range 0 0 to 5000 0 Default Value 0 0 Indoor Air Quality High Limit Display Units PPM implied Display Range 0 0 to 5000 0 Default Value 1200 0 Table 9...

Страница 32: ...mes will take effect on a day configured as a holiday A zero means the schedule period will not apply to that day Day of week Range 0 or 1 Default Values 11111111 for period 1 00000000 for the rest of...

Страница 33: ...pecifies the value for Purge Minimum Damper Position for High Outdoor Air temperature conditions IAQ Pre Occupancy Purge Algorithm shall use this value whenever Outdoor Air Temperature is above or at...

Страница 34: ...e 3 0 Derivative Gain Range 20 0 to 20 0 Default Value 5 0 Starting Value Units Degrees F Range 40 0 to 120 0 Default Value 75 0 STAGED HEATING The Staged Heating function is used for two position val...

Страница 35: ...be sent to the device The sign of the submaster gain limit determines the direction in which the output will be driven in response to a given error The gain is expressed in percent change in output p...

Страница 36: ...and the supply air temperature goes below Lockout Temperature set point the compressor will cycle to maintain the supply air set point The minimum on and off times and stage up and down timers will st...

Страница 37: ...ing capacity is limited When Demand Limit option is enabled the control will re spond to the Loadshed Controller commands such as Redline Alert Shed Unshed and Redline Cancel Demand Limiting Range Dis...

Страница 38: ...sed by bringing in too much outdoor air to maintain IAQ set point When an override condition takes place IAQ control is disabled and Economizer Mini mum Position is set to the user configured value MD...

Страница 39: ...rk Access None OVERRIDE DURATION The Override Duration point displays the number of minutes remaining for an occupancy override which is in effect If the override duration value down loaded is in hour...

Страница 40: ...TIMED OVERRIDE IN EFFECT The Timed Override In Effect point shows if a timed override is currently in effect Timed Override in Effect Display Range No Yes Default Value No Network Access Read Only STA...

Страница 41: ...omizer Submaster Reference Display Units Degrees F Degrees C Display Range 48 to 120 Default Value 120 Network Access Read Only ECONOMIZER SUBMASTER GAIN Displays the cur rent Submaster gain multiplie...

Страница 42: ...play Units Degrees F Degrees C Display Range 0 0 to 99 9 Default Value 0 0 Network Access None The Occupancy Status point displays a 1 if occupancy is re ported by the Linkage Thermostat The Occupancy...

Страница 43: ......

Страница 44: ...inue or change at any time specifications or designs without notice and without incurring obligations PC 111 Catalog No 533 80072 Printed in U S A Form 38 54SI Pg 44 11 02 Replaces 38 52SI Book 1 4 Ta...

Отзывы: