Table 3 — 19XB Storage Tank Rated Dry Weight and Refrigerant Capacity

English

SIZE CODE

TANK OD

(in.)

DRY WEIGHT*

(lb)

MAXIMUM REFRIGERANT CAPACITY (lb)

ASHRAE/ANSI 15

UL 1963

R-22

R-134a

R-22

R-134a

0428

24.00

2380

1842

1860

1704

1716

0452

27.25

3460

3527

3563

3264

3286

SI

SIZE CODE

TANK OD

(mm)

DRY WEIGHT*

(kg)

MAXIMUM REFRIGERANT CAPACITY (kg)

ASHRAE/ANSI 15

UL 1963

R-22

R-134a

R-22

R-134a

0428

610

1080

836

844

773

778

0452

592

1569

1600

1616

1481

1491

LEGEND

ANSI

— American National Standards Institute

ASHRAE — American Society of Heating, Refrigeration,

and Air Conditioning Engineers

UL

— Underwriters’ Laboratories

*The above dry weight includes the pumpout unit weight of 210 lbs (95 kg).

Make Piping Connections —

Figure 6 represents typi-

cal pumpout unit/chiller piping connections. Standard con-
nections for

1

2

-in. OD copper tubing are provided. Install

the field-supplied FPT tee with pipe plug in the piping as
shown in Fig. 6. This tee is used for refrigerant charging.

NOTE: If any field piping runs exceed 50 ft in length, use

7

8

-in. OD copper tubing to minimize pressure drop.

Pumpout unit water piping connections are shown in

Fig. 6. Both connections are

1

2

-in. NPT (female). A shutoff

valve should be installed in the water line. Provide a means
for blowing water from the condenser coil at winter shut-
down to prevent freeze-up damage. Refer to the Job Data for
water piping particulars.

INSTALL VENT PIPING TO RELIEF DEVICES — The
pumpout storage tank is factory-equipped with relief de-
vices. Refer to Fig. 5 and Table 2 for size and location of the
relief devices. Vent the relief devices to the outdoors in ac-
cordance with ANSI/ASHRAE 15 Safety Code (latest edi-
tion) for Mechanical Refrigeration and all other applicable
codes. Relief devices are set to relieve at 300 psig
(2068 kPa).

Refrigerant discharged into confined spaces can dis-
place oxygen and cause asphyxiation.

1. If relief devices are manifolded, the cross-sectional area

of the relief pipe must at least equal the sum of the areas
required for individual relief pipes.

2. Provide a pipe plug near outlet side of each relief device

for leak testing. Provide pipe fittings that allow vent pip-
ing to be disconnected periodically for inspection of valve
mechanism.

3. Piping to relief devices must not apply stress to the de-

vice. Adequately support piping. A length of flexible tub-
ing or piping near the device is essential on spring-
isolated machines.

4. Cover the outdoor vent with a rain cap and place a con-

densation drain at the low point in the vent piping to pre-
vent water build-up on the atmospheric side of the relief
device.

Make Electrical Connections —

See nameplate on

compressor of pumpout unit and Table 1 for motor electrical
data. Wire unit according to the diagram inside the control
box.

Fig. 7 is the wiring schematic for a complete system that

includes the 19XB storage tank and the pumpout unit.
Fig. 8 is the wiring schematic for the pumpout unit. Use this
schematic for installations that do not include an auxiliary
pumpout storage tank.

NOTE: Use copper conductors only.

7

Содержание POSITIVE PRESSURE STORAGE SYSTEM 19XB

Страница 1: ...FLUSH EYES with water and consult a physician NEVER APPLY an open flame or live steam to a refrigerant cyl inder Dangerous overpressure can result When necessary to heat refrigerant use only warm 110...

Страница 2: ...a free standing unit that can be used with chillers that have an existing storage tank or with chillers that have isolation valves that permit built in refrigerant storage The 19XB PPS systems are fac...

Страница 3: ...u ft LEGEND LRA Locked Rotor Amps RLA Rated Load Amps NOTES 1 All storage vessels are 300 psig 2068 kPa designs per the ASME American Society of Mechanical Engineers Boiler Pressure Vessel Code Sectio...

Страница 4: ...CTIONS FIELD PIPING REFRIGERANT INLET VALVE VENT VALVE CONTROL BOX WIRING BY CONTRACTOR COMPRESSOR VALVES VALVES 19EA PUMPOUT UNIT 19EA CONTROL BOX INTERIOR 19EA PUMPOUT UNITS Fig 1 19XB Positive Pres...

Страница 5: ...lg 4 required Fig 2 19EA Pumpout Unit Typical Chiller Mount Fig 3 Pumpout Unit Contact Surfaces and Dimensions ELECTRICAL CONNECTION OPTION LIST TRADE SIZE QTY LOCATION 1 2 1 TOP 3 4 1 BOTTOM 1 1 MIDD...

Страница 6: ...udes the compressor condenser control box and the oil separator NOTES 1 The motor is hermetic with thermal protection 2 The control box is mounted and wired with a fuse on off switch according to NEMA...

Страница 7: ...e pumpout storage tank is factory equipped with relief de vices Refer to Fig 5 and Table 2 for size and location of the relief devices Vent the relief devices to the outdoors in ac cordance with ANSI...

Страница 8: ...R S T 0428 3175 2997 1448 730 365 945 1499 1121 1118 849 965 89 1442 505 491 1111 1530 0452 4553 4382 1546 826 413 1027 2191 1219 1216 948 1064 86 2172 528 497 1118 1537 NOTES 1 Denotes center of gra...

Страница 9: ...ng the reading adjusting and servicing of the equipment If the distance from the chiller to the pumpout unit is over 50 ft then 7 8 in OD tubing min must be used Provisions should be made for adjustme...

Страница 10: ...Overload Term Pumpdown Term Pumpdown Comp r Term Fig 7 19XB Pumpout System Wiring Schematic LEGEND C Contactor Fu Fuse 3 Amps HP High Pressure Cutout L Compressor Motor Voltage Line 3 phase LL Low Li...

Страница 11: ...t capacity refer to Table 2 OPERATION Overview Transferring refrigerant from one vessel to another is accomplished by using either gravity or pressure differential A difference in elevation between 2...

Страница 12: ...isolated chillers may place severe stress on external pip ing if springs on the chiller have not been blocked in both up and down directions 3 Open the refrigerant inlet valve Fig 9 on the pumpout com...

Страница 13: ...out condenser water i Run the pumpout compressor until the storage tank pres sure reaches 5 psig 34 kPa 18 in Hg 41 kPa absolute j Turn off the pumpout compressor k Close valves 1a 1b 2 5 and 6 VALVE...

Страница 14: ...tep 3e un til the chiller pressure is reduced to 18 in Hg 41 kPa absolute CHILLERS WITH ISOLATION VALVES The valves re ferred to in the following instructions are shown in Fig 9 and 11 Valve 7 remains...

Страница 15: ...e up 5 Leak test to ensure chiller vessel integrity 6 Open valve 5 fully VALVE 1a 1b 2 3 4 5 8 11 CONDITION C C C C 7 Close valves 1a 1b 3 and 5 8 Open chiller isolation valve 11 and any other isolati...

Страница 16: ...ine model number and serial number name quantity and part number of the part required delivery address and method of shipment TROUBLESHOOTING Information on troubleshooting for the PPS is included in...

Отзывы: