Carrier POSITIVE PRESSURE STORAGE SYSTEM 19XB Скачать руководство пользователя страница 15

d. Close valve 1a.
e. Turn off pumpout compressor.
f. Close valves 1b, 3, and 4.

VALVE

1a

1b

2

3

4

5

8

11

CONDITION

C

C

C

C

C

C

C

C

g. Turn off pumpout condenser water.
h. Turn off chiller water pumps and lock out chiller

compressor.

Transfer All Refrigerant to Chiller Cooler Vessel:
1. Push refrigerant into the chiller cooler vessel.

a. Turn on the chiller water pumps and monitor the chiller

pressure.

b. Valve positions:

VALVE

1a

1b

2

3

4

5

8

11

CONDITION

C

C

C

c. Equalize the refrigerant in the chiller cooler and

condenser.

d. Turn off chiller water pumps and pumpout condenser

water.

e. Turn on pumpout compressor to push refrigerant out

of the chiller condenser.

f. When all liquid is out of the chiller condenser, close

valve 11 and any other liquid isolation valves on the
chiller.

g. Turn off the pumpout compressor.

2. Evacuate gas from chiller condenser vessel.

a. Turn on chiller water pumps.
b. Make sure that pumpout valves 3 and 4 are closed and

valves 2 and 5 are open.

VALVE

1a

1b

2

3

4

5

8

11

CONDITION

C

C

C

C

c. Turn on pumpout condenser water.
d. Run the pumpout compressor until the chiller con-

denser reaches 18 in. Hg (41 kPa absolute). Monitor
pressure at the chiller control panel and refrigerant gages.

e. Close valve 1b.
f. Turn off pumpout compressor.
g. Close valves 1a, 2, and 5.

VALVE

1a

1b

2

3

4

5

8

11

CONDITION

C

C

C

C

C

C

C

C

h. Turn off pumpout condenser water.
i. Turn off chiller water pumps and lock out chiller com-

pressor.

Return Refrigerant to Normal Operating Conditions
1. Be sure that the chiller vessel that was opened has been

evacuated.

2. Turn on chiller water pumps.
3. Open valves 1a, 1b, and 3.

VALVE

1a

1b

2

3

4

5

8

11

CONDITION

C

C

C

C

C

4. Crack open valve 5, gradually increasing pressure in the

evacuated chiller vessel to 60 psig (414 kPa), [30 psig
(207 kPa)]. Feed refrigerant slowly to prevent tube
freeze-up.

5. Leak test to ensure chiller vessel integrity.

6. Open valve 5 fully.

VALVE

1a

1b

2

3

4

5

8

11

CONDITION

C

C

C

C

7. Close valves 1a, 1b, 3, and 5.
8. Open chiller isolation valve 11 and any other isolation

valves, if present.

VALVE

1a

1b

2

3

4

5

8

11

CONDITION

C

C

C

C

C

C

C

9. Turn off chiller water pumps.

DISTILLING THE REFRIGERANT
1. Transfer the refrigerant from the chiller to the pumpout

storage tank as described in the Transfer the Refrigerant
from Chiller to Pumpout Storage Tank section.

2. Equalize the refrigerant pressure.

a. Turn on chiller water pumps and monitor chiller

pressures.

b. Close pumpout and storage tank valves 2, 4, 5, 8, and

10, and close chiller charging valve 7; open chiller iso-
lation valve 11 and any other chiller isolation valves,
if present.

c. Open pumpout and storage tank valves 3 and 6; open

chiller valves 1a and 1b.

VALVE

1a

1b

2

3

4

5

6

7

8

10

11

CONDITION

C

C

C

C

C

C

d. Gradually crack open valve 5 to increase chiller pres-

sure to 60 psig (414 kPa), [30 psig (207 kPa)]. Slowly
feed refrigerant to prevent freeze-up.

e. Open valve 5 fully after the chiller pressure rises above

the freezing point of the refrigerant. Let the storage
tank and chiller pressure equalize.

3. Transfer remaining refrigerant.

a. Close valve 3.
b. Open valve 2.

VALVE

1a

1b

2

3

4

5

6

7

8

10

11

CONDITION

C

C

C

C

C

c. Turn on pumpout condenser water.
d. Run the pumpout compressor until the storage tank

pressure reaches 5 psig (34 kPa), 18 in. Hg (41 kPa
absolute).

e. Turn off the pumpout compressor.
f. Close valves 1a, 1b, 2, 5, and 6.
g. Turn off pumpout condenser water.

VALVE

1a

1b

2

3

4

5

6

7

8

10

11

CONDITION

C

C

C

C

C

C

C

C

C

C

4. Drain the contaminants from the bottom of the storage

tank into a container. Dispose of contaminants safely.

MAINTENANCE

Periodic maintenance is necessary to keep all components

functioning as designed. A maintenance log is recom-
mended to ensure a proper maintenance schedule is
followed.

Pumpout Unit —

For maintenance details, refer to the

06D, 07D Installation, Start-Up, and Service Instructions.

15

Содержание POSITIVE PRESSURE STORAGE SYSTEM 19XB

Страница 1: ...FLUSH EYES with water and consult a physician NEVER APPLY an open flame or live steam to a refrigerant cyl inder Dangerous overpressure can result When necessary to heat refrigerant use only warm 110...

Страница 2: ...a free standing unit that can be used with chillers that have an existing storage tank or with chillers that have isolation valves that permit built in refrigerant storage The 19XB PPS systems are fac...

Страница 3: ...u ft LEGEND LRA Locked Rotor Amps RLA Rated Load Amps NOTES 1 All storage vessels are 300 psig 2068 kPa designs per the ASME American Society of Mechanical Engineers Boiler Pressure Vessel Code Sectio...

Страница 4: ...CTIONS FIELD PIPING REFRIGERANT INLET VALVE VENT VALVE CONTROL BOX WIRING BY CONTRACTOR COMPRESSOR VALVES VALVES 19EA PUMPOUT UNIT 19EA CONTROL BOX INTERIOR 19EA PUMPOUT UNITS Fig 1 19XB Positive Pres...

Страница 5: ...lg 4 required Fig 2 19EA Pumpout Unit Typical Chiller Mount Fig 3 Pumpout Unit Contact Surfaces and Dimensions ELECTRICAL CONNECTION OPTION LIST TRADE SIZE QTY LOCATION 1 2 1 TOP 3 4 1 BOTTOM 1 1 MIDD...

Страница 6: ...udes the compressor condenser control box and the oil separator NOTES 1 The motor is hermetic with thermal protection 2 The control box is mounted and wired with a fuse on off switch according to NEMA...

Страница 7: ...e pumpout storage tank is factory equipped with relief de vices Refer to Fig 5 and Table 2 for size and location of the relief devices Vent the relief devices to the outdoors in ac cordance with ANSI...

Страница 8: ...R S T 0428 3175 2997 1448 730 365 945 1499 1121 1118 849 965 89 1442 505 491 1111 1530 0452 4553 4382 1546 826 413 1027 2191 1219 1216 948 1064 86 2172 528 497 1118 1537 NOTES 1 Denotes center of gra...

Страница 9: ...ng the reading adjusting and servicing of the equipment If the distance from the chiller to the pumpout unit is over 50 ft then 7 8 in OD tubing min must be used Provisions should be made for adjustme...

Страница 10: ...Overload Term Pumpdown Term Pumpdown Comp r Term Fig 7 19XB Pumpout System Wiring Schematic LEGEND C Contactor Fu Fuse 3 Amps HP High Pressure Cutout L Compressor Motor Voltage Line 3 phase LL Low Li...

Страница 11: ...t capacity refer to Table 2 OPERATION Overview Transferring refrigerant from one vessel to another is accomplished by using either gravity or pressure differential A difference in elevation between 2...

Страница 12: ...isolated chillers may place severe stress on external pip ing if springs on the chiller have not been blocked in both up and down directions 3 Open the refrigerant inlet valve Fig 9 on the pumpout com...

Страница 13: ...out condenser water i Run the pumpout compressor until the storage tank pres sure reaches 5 psig 34 kPa 18 in Hg 41 kPa absolute j Turn off the pumpout compressor k Close valves 1a 1b 2 5 and 6 VALVE...

Страница 14: ...tep 3e un til the chiller pressure is reduced to 18 in Hg 41 kPa absolute CHILLERS WITH ISOLATION VALVES The valves re ferred to in the following instructions are shown in Fig 9 and 11 Valve 7 remains...

Страница 15: ...e up 5 Leak test to ensure chiller vessel integrity 6 Open valve 5 fully VALVE 1a 1b 2 3 4 5 8 11 CONDITION C C C C 7 Close valves 1a 1b 3 and 5 8 Open chiller isolation valve 11 and any other isolati...

Страница 16: ...ine model number and serial number name quantity and part number of the part required delivery address and method of shipment TROUBLESHOOTING Information on troubleshooting for the PPS is included in...

Отзывы: