PUMPOUT COMPRESSOR OIL CHARGE — Use oil con-
forming to Carrier specifications for reciprocating compres-
sor use. Oil requirements are listed in Table 6.

Table 6 — Pumpout Compressor Oil Requirements

REFRIGERANT

ISO

VISCOSITY

CARRIER

SPECIFICATION

NO.

CARRIER

PART NO.

R-22

86

PP49-7

PP23BZ101

R-134a

68

PP47-31

PP23BZ103

The total oil charge, 4.5 pints (2.6 L), consists of 3.5 pints

(2.0 L) for the compressor and one additional pint (0.6 L)
for the oil separator.

Oil should be visible in one of the pumpout compressor

sight glasses both during operation and at shutdown. Always
check the oil level before operating the pumpout compres-
sor. Before adding or changing oil, relieve the refrigerant
pressure as follows:
1. Attach a pressure gage to the gage port of either pumpout

compressor service valve (Fig. 10).

2. Close the suction service valve and open the discharge

line to the pumpout storage tank or the chiller.

3. Operate the compressor until the crankcase pressure drops

to 2 psig (13 kPa).

4. Stop the pumpout compressor and isolate the pumpout

system by closing the discharge service valve.

5. Slowly remove the oil return line connection (Fig. 9). Add

oil as required.

6. Replace the connections and reopen the pumpout com-

pressor service valves.

Storage Tank —

To prevent moisture and contami-

nants from entering the storage tank, maintain positive pres-
sure in the tank when not transferring refrigerant. Leak test
the storage tank according to your normal vessel leak test
procedures and schedule.

Ordering Replacement Parts —

The following in-

formation must accompany an order for Carrier-specified parts:
• machine model number and serial number
• name, quantity, and part number of the part required
• delivery address and method of shipment

TROUBLESHOOTING

Information on troubleshooting for the PPS is included in

Table 7.

Table 7 — Troubleshooting

SYMPTOM

PROBABLE CAUSE

REMEDY

Compressor does not run

Main power line open

Replace fuse or reset circuit breaker.

Loose terminal connection

Check connections.

Improperly wired controls

Check wiring and rewire.

Low line voltage

Check line voltage; determine location of voltage drop.

Compressor motor defective

Check motor winding for open or short. Replace compressor if
necessary.

Seized compressor

Replace compressor.

High level gage alarm

Check refrigerant level and remove excess.

Compressor cycles on
high-pressure control

High-pressure control erratic in action

Check capillary tube for pinches. Set control as required..

Discharge valve partially closed.

Open valve.

Air in system

Purge system.

Condenser scaled.

Clean condenser.

Condenser water pump or fans not operat-
ing.

Start pump or fans.

Unit operates too long

Isolation valves partially open

Close valves.

System Noises

Piping vibrations

Support piping as required. Check for loose pipe connectors.

Compressor noisy

Check valve plates for valve noise. Replace compressor (worn
bearings). Check for loose compressor holddown bolts.

Insufficient compressor oil

Add oil.

Compressor Loses Oil

Leak in system

Locate and repair leak.

Plugged or stuck compressor oil return
check valve

Repair or replace valve.

Dirty accumulator

Clean accumulator.

Copyright 1996 Carrier Corporation

Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.

Book 2
Tab

5a

PC 211

Catalog No. 531-927

Printed in U.S.A.

Form 19XB-1SI

Pg 16

6-96

Replaces: New

Содержание POSITIVE PRESSURE STORAGE SYSTEM 19XB

Страница 1: ...FLUSH EYES with water and consult a physician NEVER APPLY an open flame or live steam to a refrigerant cyl inder Dangerous overpressure can result When necessary to heat refrigerant use only warm 110...

Страница 2: ...a free standing unit that can be used with chillers that have an existing storage tank or with chillers that have isolation valves that permit built in refrigerant storage The 19XB PPS systems are fac...

Страница 3: ...u ft LEGEND LRA Locked Rotor Amps RLA Rated Load Amps NOTES 1 All storage vessels are 300 psig 2068 kPa designs per the ASME American Society of Mechanical Engineers Boiler Pressure Vessel Code Sectio...

Страница 4: ...CTIONS FIELD PIPING REFRIGERANT INLET VALVE VENT VALVE CONTROL BOX WIRING BY CONTRACTOR COMPRESSOR VALVES VALVES 19EA PUMPOUT UNIT 19EA CONTROL BOX INTERIOR 19EA PUMPOUT UNITS Fig 1 19XB Positive Pres...

Страница 5: ...lg 4 required Fig 2 19EA Pumpout Unit Typical Chiller Mount Fig 3 Pumpout Unit Contact Surfaces and Dimensions ELECTRICAL CONNECTION OPTION LIST TRADE SIZE QTY LOCATION 1 2 1 TOP 3 4 1 BOTTOM 1 1 MIDD...

Страница 6: ...udes the compressor condenser control box and the oil separator NOTES 1 The motor is hermetic with thermal protection 2 The control box is mounted and wired with a fuse on off switch according to NEMA...

Страница 7: ...e pumpout storage tank is factory equipped with relief de vices Refer to Fig 5 and Table 2 for size and location of the relief devices Vent the relief devices to the outdoors in ac cordance with ANSI...

Страница 8: ...R S T 0428 3175 2997 1448 730 365 945 1499 1121 1118 849 965 89 1442 505 491 1111 1530 0452 4553 4382 1546 826 413 1027 2191 1219 1216 948 1064 86 2172 528 497 1118 1537 NOTES 1 Denotes center of gra...

Страница 9: ...ng the reading adjusting and servicing of the equipment If the distance from the chiller to the pumpout unit is over 50 ft then 7 8 in OD tubing min must be used Provisions should be made for adjustme...

Страница 10: ...Overload Term Pumpdown Term Pumpdown Comp r Term Fig 7 19XB Pumpout System Wiring Schematic LEGEND C Contactor Fu Fuse 3 Amps HP High Pressure Cutout L Compressor Motor Voltage Line 3 phase LL Low Li...

Страница 11: ...t capacity refer to Table 2 OPERATION Overview Transferring refrigerant from one vessel to another is accomplished by using either gravity or pressure differential A difference in elevation between 2...

Страница 12: ...isolated chillers may place severe stress on external pip ing if springs on the chiller have not been blocked in both up and down directions 3 Open the refrigerant inlet valve Fig 9 on the pumpout com...

Страница 13: ...out condenser water i Run the pumpout compressor until the storage tank pres sure reaches 5 psig 34 kPa 18 in Hg 41 kPa absolute j Turn off the pumpout compressor k Close valves 1a 1b 2 5 and 6 VALVE...

Страница 14: ...tep 3e un til the chiller pressure is reduced to 18 in Hg 41 kPa absolute CHILLERS WITH ISOLATION VALVES The valves re ferred to in the following instructions are shown in Fig 9 and 11 Valve 7 remains...

Страница 15: ...e up 5 Leak test to ensure chiller vessel integrity 6 Open valve 5 fully VALVE 1a 1b 2 3 4 5 8 11 CONDITION C C C C 7 Close valves 1a 1b 3 and 5 8 Open chiller isolation valve 11 and any other isolati...

Страница 16: ...ine model number and serial number name quantity and part number of the part required delivery address and method of shipment TROUBLESHOOTING Information on troubleshooting for the PPS is included in...

Отзывы: