Carrier POSITIVE PRESSURE STORAGE SYSTEM 19XB Скачать руководство пользователя страница 14

3. Remove any remaining refrigerant.

a. Turn on chiller water pumps.
b. Turn on pumpout condenser water.
c. Place valves in the following positions:

VALVE

1a

1b

2

3

4

5

6

7

8

10

11

CONDITION

C

C

C

C

C

d. Run the pumpout compressor until the chiller pres-

sure reaches 60 psig (414 kPa), [30 psig (207 kPa)];
then, shut off the pumpout compressor. Warm chiller
condenser water will boil off any entrapped liquid re-
frigerant and chiller pressure will rise.

e. When chiller pressure rises to 70 psig (483 kPa),

[40 psig (276 kPa)]; turn on the pumpout compressor
until the pressure again reaches 60 psig (414 kPa)
[30 psig (207 kPa)]; then, turn off the pumpout com-
pressor. Repeat this process until the chiller pressure
no longer rises; then, turn on the pumpout compressor
and pump out until the chiller pressure reaches
18 in. Hg (41 kPa absolute).

f. Close valves 1a, 1b, 3, 4, and 6.

VALVE

1a

1b

2

3

4

5

6

7

8

10

11

CONDITION

C

C

C

C

C

C

C

C

C

C

g. Turn off the pumpout condenser water.

4. Establish vacuum for service. To conserve refrigerant, op-

erate the pumpout compressor as described in Step 3e un-
til the chiller pressure is reduced to 18 in. Hg (41 kPa
absolute).

CHILLERS WITH ISOLATION VALVES — The valves re-
ferred to in the following instructions are shown in Fig. 9
and 11. Valve 7 remains closed.

Transfer All Refrigerant to Chiller Condenser Vessel:
1. Push refrigerant into chiller condenser vessel.

a. Turn on the chiller water pumps and monitor the chiller

pressure.

b. Valve positions:

VALVE

1a

1b

2

3

4

5

8

11

CONDITION

C

C

C

c. Equalize the refrigerant in the chiller cooler and

condenser.

d. Turn off chiller water pumps and pumpout condenser

water supply.

e. Turn on pumpout compressor to push liquid out of the

chiller cooler vessel.

f. When all liquid has been pushed into the chiller con-

denser vessel, close the cooler refrigerant isolation valve
(11).

g. Turn on the chiller water pumps.
h. Turn off the pumpout compressor.

2. Evacuate gas from chiller cooler vessel.

a. Close pumpout valves 2 and 5; open valves 3 and 4.

VALVE

1a

1b

2

3

4

5

8

11

CONDITION

C

C

C

C

b. Turn on pumpout condenser water.
c. Run pumpout compressor until the chiller cooler ves-

sel pressure reaches 18 in. Hg vac (41 kPa absolute).
Monitor pressures on the chiller control panel and on
refrigerant gages.

Fig. 11 — Valve Locations for 19XB Pumpout Unit Without Storage Tank

14

Содержание POSITIVE PRESSURE STORAGE SYSTEM 19XB

Страница 1: ...FLUSH EYES with water and consult a physician NEVER APPLY an open flame or live steam to a refrigerant cyl inder Dangerous overpressure can result When necessary to heat refrigerant use only warm 110...

Страница 2: ...a free standing unit that can be used with chillers that have an existing storage tank or with chillers that have isolation valves that permit built in refrigerant storage The 19XB PPS systems are fac...

Страница 3: ...u ft LEGEND LRA Locked Rotor Amps RLA Rated Load Amps NOTES 1 All storage vessels are 300 psig 2068 kPa designs per the ASME American Society of Mechanical Engineers Boiler Pressure Vessel Code Sectio...

Страница 4: ...CTIONS FIELD PIPING REFRIGERANT INLET VALVE VENT VALVE CONTROL BOX WIRING BY CONTRACTOR COMPRESSOR VALVES VALVES 19EA PUMPOUT UNIT 19EA CONTROL BOX INTERIOR 19EA PUMPOUT UNITS Fig 1 19XB Positive Pres...

Страница 5: ...lg 4 required Fig 2 19EA Pumpout Unit Typical Chiller Mount Fig 3 Pumpout Unit Contact Surfaces and Dimensions ELECTRICAL CONNECTION OPTION LIST TRADE SIZE QTY LOCATION 1 2 1 TOP 3 4 1 BOTTOM 1 1 MIDD...

Страница 6: ...udes the compressor condenser control box and the oil separator NOTES 1 The motor is hermetic with thermal protection 2 The control box is mounted and wired with a fuse on off switch according to NEMA...

Страница 7: ...e pumpout storage tank is factory equipped with relief de vices Refer to Fig 5 and Table 2 for size and location of the relief devices Vent the relief devices to the outdoors in ac cordance with ANSI...

Страница 8: ...R S T 0428 3175 2997 1448 730 365 945 1499 1121 1118 849 965 89 1442 505 491 1111 1530 0452 4553 4382 1546 826 413 1027 2191 1219 1216 948 1064 86 2172 528 497 1118 1537 NOTES 1 Denotes center of gra...

Страница 9: ...ng the reading adjusting and servicing of the equipment If the distance from the chiller to the pumpout unit is over 50 ft then 7 8 in OD tubing min must be used Provisions should be made for adjustme...

Страница 10: ...Overload Term Pumpdown Term Pumpdown Comp r Term Fig 7 19XB Pumpout System Wiring Schematic LEGEND C Contactor Fu Fuse 3 Amps HP High Pressure Cutout L Compressor Motor Voltage Line 3 phase LL Low Li...

Страница 11: ...t capacity refer to Table 2 OPERATION Overview Transferring refrigerant from one vessel to another is accomplished by using either gravity or pressure differential A difference in elevation between 2...

Страница 12: ...isolated chillers may place severe stress on external pip ing if springs on the chiller have not been blocked in both up and down directions 3 Open the refrigerant inlet valve Fig 9 on the pumpout com...

Страница 13: ...out condenser water i Run the pumpout compressor until the storage tank pres sure reaches 5 psig 34 kPa 18 in Hg 41 kPa absolute j Turn off the pumpout compressor k Close valves 1a 1b 2 5 and 6 VALVE...

Страница 14: ...tep 3e un til the chiller pressure is reduced to 18 in Hg 41 kPa absolute CHILLERS WITH ISOLATION VALVES The valves re ferred to in the following instructions are shown in Fig 9 and 11 Valve 7 remains...

Страница 15: ...e up 5 Leak test to ensure chiller vessel integrity 6 Open valve 5 fully VALVE 1a 1b 2 3 4 5 8 11 CONDITION C C C C 7 Close valves 1a 1b 3 and 5 8 Open chiller isolation valve 11 and any other isolati...

Страница 16: ...ine model number and serial number name quantity and part number of the part required delivery address and method of shipment TROUBLESHOOTING Information on troubleshooting for the PPS is included in...

Отзывы: