background image

Installation, Operating, and Maintenance

Instructions

For Use With Positive Pressure Chillers

SAFETY CONSIDERATIONS

Positive pressure storage systems are designed to pro-
vide safe and reliable service when operated within de-
sign specifications. When operating this equipment, use
good judgment and safety precautions to avoid damage
to equipment and property or injury to personnel.
Be sure you understand and follow the procedures and
safety precautions contained in this guide.

DO NOT VENT refrigerant relief valves within a building. Outlet
from rupture disc or relief valve must be vented outdoors in ac-
cordance with the latest edition of ASHRAE 15 (American Society
of Heating, Refrigeration, and Air Conditioning Engineers). The
accumulation of refrigerant in an enclosed space can displace oxy-
gen and cause asphyxiation.
PROVIDE adequate ventilation in accordance with ASHRAE 15,
especially for enclosed and low overhead spaces. Inhalation of high
concentrations of vapor is harmful and may cause heart irregulari-
ties, unconsciousness, or death. Misuse can be fatal. Vapor is heavier
than air and reduces the amount of oxygen available for breathing.
Product causes eye and skin irritation. Decomposition products are
hazardous.
DO NOT USE OXYGEN to purge lines or to pressurize a machine
for any purpose. Oxygen gas reacts violently with oil, grease, and
other common substances.
NEVER EXCEED specified test pressures, VERIFY the allowable
test pressure by checking the instruction literature and the design
pressures on the equipment nameplate.
DO NOT USE air for leak testing. Use only tracer gases and dry
nitrogen.
DO NOT VALVE OFF any safety device.
BE SURE that all pressure relief devices are properly installed and
functioning before operating any machine.

DO NOT WELD OR FLAMECUT any refrigerant line or vessel
until all refrigerant (liquid and vapor) has been removed from chiller.
Traces of vapor should be displaced with dry air or nitrogen and
the work area should be well ventilated. Refrigerant in contact with
an open flame produces toxic gases.
DO NOT USE eyebolts or eyebolt holes to rig machine sections or
the entire assembly.
DO NOT work on high-voltage equipment unless you are a quali-
fied electrician.
DO NOT WORK ON electrical components, including control pan-
els, switches, starters, or oil heater until you are sure ALL POWER
IS OFF and no residual voltage can leak from capacitors or solid-
state components.
LOCK OPEN AND TAG electrical circuits during servicing. IF WORK
IS INTERRUPTED, confirm that all circuits are deenergized be-
fore resuming work.
DO NOT syphon refrigerant by mouth.
AVOID SPILLING liquid refrigerant on skin or getting it into the
eyes. USE SAFETY GOGGLES. Wash any spills from the skin

with soap and water. If any enters the eyes, IMMEDIATELY FLUSH
EYES with water and consult a physician.
NEVER APPLY an open flame or live steam to a refrigerant cyl-
inder. Dangerous overpressure can result. When necessary to heat
refrigerant, use only warm (110 F [43 C]) water.
DO NOT REUSE disposable (nonreturnable) cylinders or
attempt to refill them. It is DANGEROUS AND ILLEGAL. When
cylinder is emptied, evacuate remaining gas pressure, loosen
the collar and unscrew and discard the valve stem. DO NOT
INCINERATE.
CHECK THE REFRIGERANT TYPE before transferring refrig-
erant to the machine. The introduction of the wrong refrigerant can
cause damage or malfunction to this machine.

Operation of this equipment with refrigerants other than those

cited herein should comply with ASHRAE 15 (latest edition). Con-
tact Carrier for further information on use of this machine with other
refrigerants.
DO NOT ATTEMPT TO REMOVE fittings, covers, etc., while ma-
chine is under pressure or while machine is running. Be sure pres-
sure is at 0 psig (0 kPa) before breaking any refrigerant
connection.
CAREFULLY INSPECT all relief devices, rupture discs, and other
relief devices AT LEAST ONCE A YEAR. If machine operates in
a corrosive atmosphere, inspect the devices at more frequent
intervals.
DO NOT ATTEMPT TO REPAIR OR RECONDITION any relief
device when corrosion or build-up of foreign material (rust, dirt,
scale, etc.) is found within the valve body or mechanism. Replace
the device.
DO NOT install relief devices in series or backwards.
USE CARE when working near or in line with a compressed spring.
Sudden release of the spring can cause it and objects in its path to
act as projectiles.

DO NOT STEP on refrigerant lines. Broken lines can whip about
and cause personal injury and damage to the machine.
DO NOT climb over a machine. Use platform, catwalk, or staging.
Follow safe practices when using ladders.
USE MECHANICAL EQUIPMENT (crane, hoist, etc.) to lift or
move inspection covers or other heavy components. Even if com-
ponents are light, use such equipment when there is a risk of slip-
ping or losing your balance.
BE AWARE that certain automatic start arrangements CAN EN-
GAGE THE STARTER. Open the disconnect ahead of the starter
in addition to shutting off the machine or pump.
USE only repair or replacement parts that meet the code require-
ments of the original equipment.
DOUBLE-CHECK that coupling nut wrenches, dial indicators, or
other items have been removed before rotating any shafts.
DO NOT LOOSEN a packing gland nut before checking that the
nut has a positive thread engagement.
PERIODICALLY INSPECT all valves, fittings, and piping for cor-
rosion, rust, leaks, or damage.
DO NOT MIX REFRIGERANT from chillers that use different com-
pressor oils. Compressor damage can result.

19XB

Positive Pressure Storage System

50/60 Hz

Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.

Book 2
Tab

5a

PC 211

Catalog No. 531-927

Printed in U.S.A.

Form 19XB-1SI

Pg 1

6-96

Replaces: New

Содержание POSITIVE PRESSURE STORAGE SYSTEM 19XB

Страница 1: ...FLUSH EYES with water and consult a physician NEVER APPLY an open flame or live steam to a refrigerant cyl inder Dangerous overpressure can result When necessary to heat refrigerant use only warm 110...

Страница 2: ...a free standing unit that can be used with chillers that have an existing storage tank or with chillers that have isolation valves that permit built in refrigerant storage The 19XB PPS systems are fac...

Страница 3: ...u ft LEGEND LRA Locked Rotor Amps RLA Rated Load Amps NOTES 1 All storage vessels are 300 psig 2068 kPa designs per the ASME American Society of Mechanical Engineers Boiler Pressure Vessel Code Sectio...

Страница 4: ...CTIONS FIELD PIPING REFRIGERANT INLET VALVE VENT VALVE CONTROL BOX WIRING BY CONTRACTOR COMPRESSOR VALVES VALVES 19EA PUMPOUT UNIT 19EA CONTROL BOX INTERIOR 19EA PUMPOUT UNITS Fig 1 19XB Positive Pres...

Страница 5: ...lg 4 required Fig 2 19EA Pumpout Unit Typical Chiller Mount Fig 3 Pumpout Unit Contact Surfaces and Dimensions ELECTRICAL CONNECTION OPTION LIST TRADE SIZE QTY LOCATION 1 2 1 TOP 3 4 1 BOTTOM 1 1 MIDD...

Страница 6: ...udes the compressor condenser control box and the oil separator NOTES 1 The motor is hermetic with thermal protection 2 The control box is mounted and wired with a fuse on off switch according to NEMA...

Страница 7: ...e pumpout storage tank is factory equipped with relief de vices Refer to Fig 5 and Table 2 for size and location of the relief devices Vent the relief devices to the outdoors in ac cordance with ANSI...

Страница 8: ...R S T 0428 3175 2997 1448 730 365 945 1499 1121 1118 849 965 89 1442 505 491 1111 1530 0452 4553 4382 1546 826 413 1027 2191 1219 1216 948 1064 86 2172 528 497 1118 1537 NOTES 1 Denotes center of gra...

Страница 9: ...ng the reading adjusting and servicing of the equipment If the distance from the chiller to the pumpout unit is over 50 ft then 7 8 in OD tubing min must be used Provisions should be made for adjustme...

Страница 10: ...Overload Term Pumpdown Term Pumpdown Comp r Term Fig 7 19XB Pumpout System Wiring Schematic LEGEND C Contactor Fu Fuse 3 Amps HP High Pressure Cutout L Compressor Motor Voltage Line 3 phase LL Low Li...

Страница 11: ...t capacity refer to Table 2 OPERATION Overview Transferring refrigerant from one vessel to another is accomplished by using either gravity or pressure differential A difference in elevation between 2...

Страница 12: ...isolated chillers may place severe stress on external pip ing if springs on the chiller have not been blocked in both up and down directions 3 Open the refrigerant inlet valve Fig 9 on the pumpout com...

Страница 13: ...out condenser water i Run the pumpout compressor until the storage tank pres sure reaches 5 psig 34 kPa 18 in Hg 41 kPa absolute j Turn off the pumpout compressor k Close valves 1a 1b 2 5 and 6 VALVE...

Страница 14: ...tep 3e un til the chiller pressure is reduced to 18 in Hg 41 kPa absolute CHILLERS WITH ISOLATION VALVES The valves re ferred to in the following instructions are shown in Fig 9 and 11 Valve 7 remains...

Страница 15: ...e up 5 Leak test to ensure chiller vessel integrity 6 Open valve 5 fully VALVE 1a 1b 2 3 4 5 8 11 CONDITION C C C C 7 Close valves 1a 1b 3 and 5 8 Open chiller isolation valve 11 and any other isolati...

Страница 16: ...ine model number and serial number name quantity and part number of the part required delivery address and method of shipment TROUBLESHOOTING Information on troubleshooting for the PPS is included in...

Отзывы: