34
Right Hood
Side Panel
Hood Top Panel
Left Hood
Side Panel
Hood
Divider
A09700
Fig. 29 -- Hood Assembly
A09701
Fig. 30 -- Economizer Hood Installation
11. Open the filter clips on the inside of the hood top. Insert the
aluminum filter into the hood and close the clips to hold in
place. See Fig. 31.
12. To replace air filters, open filter access door remove old
filters and install new disposable filters in filter rack. See
Table 13 for filter part numbers.
IMPORTANT
: On the the bent coil (See Fig. 32 to determine coil
type) filter rack, the 18 x 24 x 1 (257.2mm x 609.6mm x25.4mm)
filter must be installed through the filter access door first then
install the 16 x 24 x 1 (406.4mm x 609.6mm x 25.4mm) filter.
NOTE
:
The economizer control settings and the filters are
accessible through the filter access door.
Table 13 – Filter Part Number
DESCRIPTION
PART NUMBER
Straight Indoor
Coil Air Filter
14 x 24 x 1
(355.6 x 609.6 x 25.4 mm)
KH01AA314
16 x 24 x 1
(406.4 x 609.6 x 25.4 mm)
KH01AA316
Bent Indoor
Coil Air Filter
16 x 24 x 1
(406.4 x 609.6 x 25.4 mm)
KH01AA316
18 x 24 x 1
(457.2 x 609.5 x 25.4 mm)
KH01AA318
13. Economizer controls are set to a standard factory setting.
Nevertheless, you can adjust these settings through the filter
access door. Review the settings in the Operation section:
(1.) The standard economizer controller has a factory
setting of “C” for the outdoor air temperature
changeover and 63
_
F (17
_
C) for the supply air
(mixed air) temperature sensor. The outdoor air
temperature changeover setting is adjusted on the
sensor by setting the dip switches on the sensor.
The ABCD potentiometer on the economizer
control should be set to the “D” position.
(2.) The low ambient compressor lockout switch setting
is fixed at 42
_
F (5.6
_
C).
(3.) The minimum position for the outdoor air damper
can be configured at the controller. When not using
a CO
2
sensor, the DCV Max potentiometer must be
completely closed (CCS) for the Minimum Posi-
tion potentiometer to function correctly.
(4.) Settings for the optional outdoor enthalpy sensor,
indoor enthalpy sensor, and CO
2
sensor can also be
configured at the controller.
14. Replace the filter access panel. Screw in place ensuring all
seams are air and watertight.
15. Install all economizer accessories then power HVAC unit
and test cycle economizer.
50V
L
--
A
Содержание Performance 50VL-A
Страница 3: ...3 A09462 Fig 2 50VL A24 36 Unit Dimensions 50VL A ...
Страница 4: ...4 A09463 Fig 3 50VL A42 60 Unit Dimensions 50VL A ...
Страница 18: ...18 A10202 Fig 13 Connection Wiring Diagram 208 230 3 60 50VL A ...
Страница 19: ...19 A10202 Fig 13 Cont Ladder Wiring Diagram 208 230 3 60 50VL A ...
Страница 22: ...22 A09089 Fig 15 Cooling Charging Chart 50VL A ...
Страница 40: ...40 A10201 Fig 41 Connection Wiring Diagram 230 3 50VL A ...
Страница 41: ...41 A10201 Fig 41 Cont Ladder Wiring Diagram 230 3 50VL A ...
Страница 42: ...42 A10203 Fig 42 Connection Wiring Diagram 460 3 50VL A ...
Страница 43: ...43 A10203 Fig 42 Cont Ladder Wiring Diagram 460 3 50VL A ...