background image

6

Accessory description and usage (Listed alphabetically) continued

6.

Evaporator Freeze Thermostat

An SPST temperature-actuated switch that stops unit operation when evaporator reaches freeze-up conditions.

Usage Guideline:

Required when low ambient kit has been added.

7.

Isolation Relay 

An SPDT relay which switches the low-ambient controller out of the outdoor fan motor circuit when the heat pump switches to heating mode.

Usage Guideline:

Required in all heat pumps where low ambient kit has been added.

8.

Liquid-Line Solenoid Valve (LLS) 

An electrically operated shutoff valve which stops and starts refrigerant liquid flow in response to compressor operation. It is to be installed at the outdoor unit
to control refrigerant off cycle migration in the heating mode. 

Usage Guideline:

An LLS is required in all long line heat pump applications to control refrigerant off cycle migration in the heating mode. See Long Line Ap-
plication Guideline.

9.

Low-Ambient Pressure Switch

A long life pressure switch which is mounted to outdoor unit service valve. It is designed to cycle the outdoor fan motor in order to maintain head pressure
within normal operating limits (approximately 200 psig to 365 psig). The control will maintain working head pressure at low-ambient temperatures down to 0°F
(–17.8°C) when properly installed.

Usage Guideline:

A Low-Ambient Pressure Switch or MotorMaster ®—Low-Ambient Controller must be used when cooling operation is used at outdoor tem-
peratures below 55°F (12.8°C). 

10.

MotorMaster®—Low-Ambient Controller

A fan-speed control device activated by a temperature sensor designed to control condenser fan motor speed in response to the saturated, condensing tem-
perature during operation in cooling mode only. For outdoor temperatures down to –20°F (–28.9°C), it maintains condensing temperature at 100°F ± 10°F
(37.8°C ± –12°C).

Usage Guideline:

A MotorMaster ®—Low-Ambient Controller or Low-Ambient Pressure Switch must be used when cooling operation is used at outdoor tem-
peratures below 55°F (12.8°C). 
Suggested for all commercial applications

11.

Outdoor Air Temperature Sensor

Designed for use with Carrier Thermostats listed in this publication. This device enables the thermostat to display the outdoor temperature. This device also is
required to enable special thermostat features such as auxiliary heat lock out.

Usage Guideline:

Suggested for all Carrier thermostats listed in this publication.

12.

Outdoor Thermostat 

An SPDT temperature-actuated switch which turns on supplemental electric heaters when outdoor air temperature drops below a user-selected set point.

Usage Guideline:

Electric supplemental heat applications in non-variable speed indoor units when electric heat staging is desired.

13.

Pressure Guard Kit

A pressure switch kit that cycles the outdoor fan to limit the heating head pressure below a pre-determined pressure setting.

Usage Guideline:

Some local codes may require limiting the heating head pressure in the vapor line in some applications.

14.

Secondary Outdoor Thermostat

An SPDT temperature-actuated switch which turns on third-stage of supplemental electric heaters when outdoor air temperature drops below the second-stage
set point.

Usage Guideline:

Outdoor thermostat applications where electric heater is capable of 3-stage operation.

15.

Snow Stand

Coated wire rack which supports unit 18 in. above mounting pad to allow for drainage from unit base.

Usage Guideline:

Suggested in the following applications:

Heat pump installations in heavy snowfall areas.
Heat pump installations in snowdrift locations.
Heat pump installations in areas of prolonged subfreezing temperatures.
All commercial installations.

16.

Sound Hood

Wraparound sound reducing cover for the compressor. Reduces the sound level by about 2 dBA.

Usage Guideline:

Suggested when unit is installed closer than 15 ft to quiet areas—bedrooms, etc.
Suggested when unit is installed between two houses less than 10 ft apart.

17.

Support Feet

Four stick-on plastic feet which raise the unit 4 in. above the mounting pad. This allows sand, dirt, and other debris to be flushed from the unit base; minimizes 
corrosion.

Usage Guideline:

Coastal installations.
Windy areas or where debris is normally circulating.
Rooftop installations.

18.

Thermostatic Expansion Valve (TXV) Bi-Flow

A modulating flow-control valve which meters refrigerant liquid flow rate into the evaporator in response to the superheat of the refrigerant gas leaving the
evaporator. 

Usage Guideline:

Required in all heat pump applications designed with Puron refrigerant. 

19.

Time-Delay Relay 

An SPST delay relay which briefly continues operation of indoor blower motor to provide additional cooling after the compressor cycles off.

Note:

 

Most indoor unit controls include this feature.  For those that do not, use the guideline below.

Usage Guideline:

For improved efficiency ratings for certain combinations of indoor and outdoor units. Refer to ARI Unitary Directory

.

Содержание Performance 12 38YZA

Страница 1: ...rformance advantage of Puron refrigerant the 38YZA is extremely efficient In fact the 38YZA features some of the lowest energy usages of single speed heat pumps available from Carrier Maximum performance and efficiency are made possible through the use of the FX4A and FV4A fan coils custom made for applications with Puron refrigerant Third the cost of service will potentially be reduced in the fut...

Страница 2: ...lay defrost relay defrost timer and low voltage terminal board The defrost control is a time temperature initiation termination control which includes 4 field selectable DIP switch time periods of 30 60 90 and 120 minutes This control also includes a field selectable DIP switch Quiet Shift defrost mode which if selected maintains extremely quiet operation during defrost Thermostatic Expansion Valv...

Страница 3: ...ube Aluminum Plate Fin Face Area Sq Ft 10 83 10 83 12 12 18 18 12 12 18 18 18 18 Fins per In 25 25 25 25 20 20 20 Rows 1 1 1 1 2 2 2 Circuits 2 2 2 4 3 4 5 VALVE CONNECTION In ID Sweat Vapor 5 8 5 8 3 4 3 4 7 8 7 8 7 8 Liquid 3 8 UNIT SIZE LIQUID TUBE DIAMETER IN VAPOR TUBE DIAMETER IN 0 to 50 Ft Tube Length 0 to 50 Ft Tube Length 0 to 50 Ft Alternate 018 3 8 5 8 5 8 024 3 8 5 8 3 4 030 036 3 8 3 ...

Страница 4: ...KHALS0401LLS Liquid Line Solenoid Valve All Sizes KSASF0101AAA Support Feet 4 in All Sizes KHASS0206MPK Snow Stand All Sizes KAACF0801MED Coastal Filter All Sizes Ball bearing motor must be used Must be applied on coils not equipped with Puron TXV When applied with Carrier s IdealHumidity series 58MVP 58CV A X and FE Indoor Models Must be installed in Dual Fuel Infinity system applications INFINIT...

Страница 5: ...APPLICATIONS BELOW 55 F REQUIRED FOR LONG LINE APPLICATIONS OVER 50 FT Crankcase Heater Yes Yes Evaporator Freeze Thermostat Yes No Compressor Start Assist Capacitor and Relay Yes Yes Puron Low Ambient Pressure Switch Yes No Wind Baffle See Low Ambient Pressure Switch Instructions No Support Feet Recommended No Puron Hard Shutoff TXV Yes Yes Puron Liquid Line Solenoid Valve for Heating No See Long...

Страница 6: ... all Carrier thermostats listed in this publication 12 Outdoor Thermostat An SPDT temperature actuated switch which turns on supplemental electric heaters when outdoor air temperature drops below a user selected set point Usage Guideline Electric supplemental heat applications in non variable speed indoor units when electric heat staging is desired 13 Pressure Guard Kit A pressure switch kit that ...

Страница 7: ... internal overload protection A weighted sound power dBA Note Tested in accordance with ARI Standard 270 95 Not listed with ARI UNIT SIZE SERIES V PH OPER VOLTS COMPR FAN FLA MCA MIN WIRE SIZE 60 C 75 C MAX LENGTH Ft 60 C 75 C MAX FUSE OR CKT BKR AMPS Max Min LRA RLA 018 31 32 208 230 1 253 197 51 0 10 3 0 5 13 4 14 14 59 56 20 024 31 32 61 0 13 5 0 8 17 7 14 14 44 42 25 030 31 32 72 5 14 7 1 1 19...

Страница 8: ...mum outdoor operating ambient in heating mode is 66 F 3 Series designation is the 13th position of the unit model number 4 Center of gravity 5 NOTES DIMENSIONS IN UNIT SIZE SERIES UNIT DIMENSIONS MINIMUM MOUNTING PAD DIMENSIONS A B C D E F G H J K L M Support Feet Snow Stand 018 024 1 2 33 13 16 22 1 2 27 1 2 2 13 16 6 15 16 21 1 2 27 7 8 5 8 8 3 16 12 13 3 4 12 20 x 27 24 x 28 030 1 2 27 13 16 30...

Страница 9: ...n U S A OUTDOOR TEMPERATURE F 10 0 10 20 30 40 50 60 70 80 70 60 50 40 30 20 10 KW BASED ON INDOOR ENT AIR AT 70 F AND AT RATED CFM 80 38YZA030 32 FX4A030 38YZA036 32 FX4A036 38YZA048 32 FX4A048 38YZA024 32 FX4A030 38YZA060 32 FX4A060 38YZA042 32 FX4A042 23 4 20 5 17 6 14 7 11 7 8 8 5 9 2 9 38YZA018 32 FX4A018 A03008 ...

Страница 10: ... SPEED FURNACE CC5A CD5AW024 17 200 TDR 13 00 11 15 16 400 3 22 9 900 2 16 7 5 CE3AA024 17 200 TDR 13 00 11 05 16 500 3 24 10 000 2 18 7 5 024 31 32 FX4BNF030 24 400 TDR TXV 12 00 10 30 24 600 3 28 15 500 2 24 7 4 CC5A CD5AA036 24 400 NONE 12 00 10 20 23 000 3 12 15 600 2 22 7 2 CC5A CD5AW036 24 400 NONE 12 00 10 20 23 000 3 12 15 500 2 22 7 2 CE3AA036 24 200 NONE 12 00 10 15 24 000 3 10 15 400 2 ...

Страница 11: ... 00 11 55 27 600 3 28 17 700 2 42 7 7 CK3BA036 27 800 TDR 13 00 11 80 27 600 3 42 17 700 2 48 8 0 CK5A CK5BA036 27 800 TDR 13 00 11 80 27 800 3 44 17 700 2 50 8 0 CK5A CK5BT036 27 000 TDR 13 00 11 80 27 800 3 44 17 800 2 48 8 0 CK5PA036 27 800 TDR TXV 13 00 11 80 27 800 3 42 17 800 2 48 8 0 CK5PT036 27 800 TDR TXV 13 00 11 80 27 600 3 42 17 800 2 50 8 0 COILS 58CV A X 090 16 VARIABLE SPEED FURNACE...

Страница 12: ...6 000 3 70 22 600 2 66 8 5 CK5A CK5BA042 34 200 TDR 13 00 11 40 36 000 3 62 22 200 2 60 8 3 CK5A CK5BA048 34 400 TDR 13 00 11 50 36 000 3 68 22 600 2 66 8 5 CK5A CK5BE042 34 400 TDR 13 00 11 45 36 200 3 68 22 800 2 66 8 5 CK5A CK5BT042 34 200 TDR 13 00 11 40 36 000 3 62 22 600 2 64 8 3 CK5A CK5BT048 34 400 TDR 13 00 11 50 36 000 3 70 22 600 2 66 8 5 CK5PA042 34 200 TDR TXV 13 00 11 40 36 000 3 62 ...

Страница 13: ...11 35 36 800 3 54 23 200 2 60 8 1 CK5A CK5BA048 34 000 TDR 13 20 11 75 36 000 3 52 22 600 2 62 8 1 CK5A CK5BE042 33 400 TDR 12 60 11 45 36 600 3 42 23 200 2 62 8 0 CK5PA042 34 200 TDR TXV 13 00 11 35 36 800 3 54 23 200 2 60 8 1 CK5PA048 34 000 TDR TXV 13 20 11 75 36 000 3 52 22 600 2 62 8 1 CK5PE042 33 400 TDR TXV 12 60 11 45 36 600 3 42 23 200 2 62 8 0 COILS 58MVP080 14 VARIABLE SPEED FURNACE CC5...

Страница 14: ...00 2 50 7 7 CK5PT048 40 000 TDR TXV 12 90 11 15 40 500 3 42 25 400 2 50 7 7 CK5PW048 40 000 TDR TXV 12 90 11 15 40 500 3 42 25 400 2 50 7 7 COILS 58CV A X 135 22 VARIABLE SPEED FURNACE CC5A CD5AW048 40 000 TDR 12 80 11 20 40 500 3 30 25 200 2 46 7 5 CD5AA048 40 000 TDR 12 80 11 20 40 500 3 32 25 200 2 46 7 5 CE3AA048 40 000 TDR 12 80 11 15 40 500 3 36 25 400 2 46 7 6 CK3BA048 40 000 TDR 12 90 11 2...

Страница 15: ... 110 22 VARIABLE SPEED FURNACE CD5PX060 45 000 TDR TXV 13 40 11 70 48 000 3 68 27 600 2 50 8 5 CE3AA060 45 000 TDR 13 20 11 60 47 500 3 42 27 800 2 40 8 1 CK3BA060 44 500 TDR 13 20 11 60 47 500 3 60 27 600 2 46 8 3 CK5A CK5BA060 44 500 TDR 13 20 11 60 47 000 3 48 27 400 2 42 8 1 CK5A CK5BT060 44 500 TDR 13 20 11 60 47 500 3 60 27 600 2 46 8 3 CK5A CK5BX060 45 500 TDR 13 50 11 85 47 500 3 60 27 600...

Страница 16: ...R 13 00 11 30 47 500 3 52 27 800 2 40 8 0 CC5A CD5AW060 45 000 TDR 13 00 11 70 48 000 3 54 27 800 2 42 8 2 CK3BA060 44 500 TDR 13 00 11 30 47 500 3 52 27 800 2 40 8 0 CK5A CK5BA060 44 500 TDR 13 00 11 30 47 500 3 52 27 800 2 40 8 0 CK5A CK5BX060 45 000 TDR 13 00 11 70 48 000 3 54 27 800 2 42 8 2 CK5PA060 44 500 TDR TXV 13 00 11 30 47 500 3 52 27 800 2 40 8 0 CK5PX060 45 000 TDR TXV 13 00 11 70 48 ...

Страница 17: ...1 2 12 13 1 13 1 2 36 57 17 3 17 3 1 34 16 6 16 6 1 5 15 8 15 8 1 69 15 15 1 89 14 1 14 1 2 12 13 1 13 1 2 36 675 72 20 9 11 2 1 39 19 9 10 9 1 56 18 8 10 5 1 74 17 6 10 1 1 95 16 3 9 68 2 17 14 9 9 21 2 41 67 19 1 14 7 1 38 18 2 14 4 1 55 17 2 14 1 73 16 1 13 5 1 93 15 13 1 2 15 13 7 12 6 2 4 63 17 8 14 2 1 37 17 13 9 1 53 16 13 5 1 72 15 13 1 92 13 9 12 6 2 14 12 7 12 2 38 62 17 8 17 8 1 37 17 1...

Страница 18: ...4 5 2 34 24 8 14 0 2 59 22 9 13 4 2 86 20 9 12 7 3 14 67 27 2 20 4 1 88 25 8 19 8 2 09 24 3 19 3 2 32 22 8 18 7 2 57 21 1 18 0 2 84 19 2 17 3 3 11 63 25 4 19 8 1 87 24 1 19 2 2 08 22 7 18 6 2 31 21 2 18 0 2 55 19 7 17 3 2 82 18 0 16 6 3 09 62 25 2 24 8 1 87 24 0 24 0 2 08 22 8 22 8 2 31 21 6 21 6 2 56 20 2 20 2 2 83 18 8 18 8 3 11 57 25 1 25 1 1 87 24 0 24 0 2 08 22 8 22 8 2 31 21 6 21 6 2 56 20 3...

Страница 19: ... 16 23 3 15 2 3 47 67 31 8 25 5 2 13 30 1 24 9 2 34 28 4 24 2 2 59 26 3 23 4 2 85 24 3 22 5 3 15 22 0 21 4 3 46 63 29 9 24 8 2 12 28 1 24 0 2 33 26 5 23 3 2 58 24 9 22 6 2 85 23 0 21 7 3 15 21 0 20 7 3 48 62 30 3 30 3 2 12 28 8 28 8 2 34 27 4 27 4 2 59 25 7 25 7 2 85 23 9 23 9 3 15 22 0 22 0 3 47 57 30 3 30 3 2 12 28 7 28 7 2 34 27 2 27 2 2 58 25 6 25 6 2 85 23 8 23 8 3 15 21 7 21 7 3 46 Indoor Se...

Страница 20: ... 1 4 40 62 36 0 36 0 2 72 34 4 34 4 3 01 32 7 32 7 3 33 30 9 30 9 3 67 28 9 28 9 4 03 26 7 26 7 4 42 57 36 0 36 0 2 72 34 4 34 4 3 01 32 7 32 7 3 33 30 9 30 9 3 67 28 9 28 9 4 03 26 7 26 7 4 42 Indoor Section Size Cooling Indoor Section Size Cooling Capacity Power Capacity Power CC5A CD5AA 042 1 00 1 00 COILS 58CV A X 090 16 VARIABLE SPEED FURNACE CC5A CD5AC 048 1 00 0 98 CE3AA 048 1 01 0 92 CC5A ...

Страница 21: ...27 6 25 3 4 02 25 2 24 1 4 40 62 36 0 36 0 2 72 34 4 34 4 3 01 32 7 32 7 3 33 30 9 30 9 3 67 28 9 28 9 4 03 26 7 26 7 4 42 57 36 0 36 0 2 72 34 4 34 4 3 01 32 7 32 7 3 33 30 9 30 9 3 67 28 9 28 9 4 03 26 7 26 7 4 42 Indoor Section Size Cooling Indoor Section Size Cooling Capacity Power Capacity Power CK5PA 042 1 01 0 91 CK5A CK5BA 042 1 01 0 92 048 1 01 0 91 048 1 00 0 89 CK5PT 042 1 01 0 91 CK5A ...

Страница 22: ... 22 40 9 40 9 3 57 39 1 39 1 3 98 37 1 37 1 4 41 34 8 34 8 4 89 32 3 32 3 5 40 57 43 0 43 0 3 22 41 0 41 0 3 58 39 2 39 2 3 98 37 1 37 1 4 42 34 9 34 9 4 90 32 4 32 4 5 41 Indoor Section Size Cooling Indoor Section Size Cooling Capacity Power Capacity Power CC5A CD5AC 048 0 98 0 99 CK5A CK5BW 048 0 99 0 91 CC5A CD5AW 048 0 99 0 99 CK5PA 048 0 99 0 91 CD5AA 048 0 99 0 99 CK5PT 048 0 99 0 91 CE3AA 0...

Страница 23: ...0 7 31 0 3 91 38 2 30 1 4 34 35 5 29 0 4 81 32 5 27 8 5 31 63 42 9 32 2 3 15 40 5 31 2 3 50 38 4 30 2 3 90 36 1 29 3 4 33 33 6 28 2 4 80 30 8 27 0 5 31 62 42 5 40 5 3 14 40 3 39 3 3 50 38 3 38 1 3 90 36 3 36 3 4 34 34 2 34 2 4 81 31 9 31 9 5 32 57 42 0 42 0 3 14 40 0 40 0 3 50 38 3 38 3 3 90 36 4 36 4 4 34 34 3 34 3 4 82 32 0 32 0 5 33 1575 72 49 3 26 0 3 26 46 5 25 0 3 61 43 9 24 1 4 01 41 2 23 1...

Страница 24: ... 47 7 47 7 3 88 45 6 45 6 4 29 43 5 43 5 4 75 40 9 40 9 5 24 38 4 38 4 5 79 Indoor Section Size Cooling Indoor Section Size Cooling Capacity Power Capacity Power CC5A CD5AA 060 0 99 1 00 CK5A CK5BT 060 0 99 0 92 CC5A CD5AW 060 0 99 0 98 CK5A CK5BX 060 1 01 0 93 CE3AA 060 1 01 1 01 CK5PA 060 0 99 0 92 CK3BA 060 1 00 1 00 CK5PT 060 0 99 0 92 CK5A CK5BA 060 1 00 1 00 CK5PX 060 1 01 0 93 CK5A CK5BX 06...

Страница 25: ... 6 5 68 55 7 41 4 6 29 52 2 40 0 6 95 48 4 38 5 7 68 63 61 1 44 2 4 60 58 0 42 8 5 08 55 5 41 7 5 65 52 5 40 4 6 26 49 3 39 0 6 93 45 6 37 4 7 66 62 60 3 55 1 4 59 57 3 53 6 5 07 54 6 52 3 5 62 51 7 50 8 6 23 48 8 48 8 6 90 45 8 45 8 7 64 57 58 7 58 7 4 57 56 2 56 2 5 06 54 0 54 0 5 61 51 5 51 5 6 23 48 9 48 9 6 91 45 9 45 9 7 65 2000 72 69 9 36 1 4 79 66 5 34 9 5 29 63 6 33 9 5 85 60 5 32 8 6 48 ...

Страница 26: ...42 10 5 9 58 1 45 12 5 11 1 1 47 14 8 13 4 1 51 17 4 17 4 1 56 20 3 20 3 1 63 23 7 23 7 1 73 75 525 6 35 5 84 1 45 8 24 7 57 1 51 10 2 9 26 1 56 12 1 10 8 1 61 14 3 13 0 1 66 16 8 16 8 1 73 19 6 19 6 1 81 22 9 22 9 1 93 600 6 48 5 96 1 46 8 38 7 70 1 50 10 3 9 36 1 55 12 3 10 9 1 59 14 5 13 2 1 63 17 0 17 0 1 69 19 8 19 8 1 76 23 2 23 2 1 87 675 6 60 6 07 1 47 8 50 7 81 1 51 10 4 9 47 1 55 12 4 11...

Страница 27: ... 1 18 3 2 19 23 2 23 2 2 26 26 9 26 9 2 36 30 9 30 9 2 46 825 10 4 9 58 2 04 12 8 11 8 2 07 15 2 13 9 2 10 17 6 15 7 2 12 20 4 18 6 2 16 23 6 23 6 2 22 27 4 27 4 2 31 31 0 31 0 2 36 950 10 6 9 78 2 06 13 1 12 0 2 08 15 4 14 1 2 10 17 9 15 9 2 12 20 7 18 8 2 15 24 0 24 0 2 21 27 7 27 7 2 27 31 1 31 1 2 32 Indoor Section Size Heating Indoor Section Size Heating Capacity Power Capacity Power CC5A CD5...

Страница 28: ...0 8 2 24 14 8 13 6 2 29 17 8 16 2 2 33 21 2 18 8 2 37 25 1 22 8 2 43 29 6 29 6 2 52 34 9 34 9 2 64 40 8 40 8 2 76 1200 12 0 11 0 2 28 15 0 13 8 2 32 18 0 16 4 2 35 21 5 19 1 2 39 25 4 23 1 2 44 30 0 30 0 2 52 35 4 35 4 2 63 41 1 41 1 2 74 Indoor Section Size Heating Indoor Section Size Heating Capacity Power Capacity Power CC5A CD5AA 036 1 00 1 02 CK5A CK5BT 036 0 96 0 95 CC5A CD5AW 036 1 00 1 02 ...

Страница 29: ... 31 8 28 9 3 12 37 1 37 1 3 29 43 4 43 4 3 50 50 7 50 7 3 79 Indoor Section Size Heating Indoor Section Size Heating Capacity Power Capacity Power CC5A CD5AA 042 0 99 1 01 CK3BA 042 0 97 0 94 CC5A CD5AC 048 0 98 1 02 048 0 97 0 92 CC5A CD5AW 042 0 99 1 01 CK5A CK5BA 042 0 97 0 94 048 0 98 0 98 048 0 97 0 92 CD5AA 048 0 99 0 99 CK5A CK5BE 042 0 98 0 93 CE3AA 042 0 99 0 98 CK5A CK5BT 042 0 97 0 94 0...

Страница 30: ... 42 6 3 51 49 8 49 8 3 81 1500 15 2 14 0 2 63 19 1 17 5 2 74 23 1 21 1 2 87 27 2 24 1 2 99 31 8 28 9 3 12 37 1 37 1 3 29 43 4 43 4 3 50 50 7 50 7 3 79 Indoor Section Size Heating Indoor Section Size Heating Capacity Power Capacity Power CK5PW 048 0 97 0 92 CK5A CK5BE 042 0 99 1 01 COILS 58CV A X 155 22 VARIABLE SPEED FURNACE CK5PA 042 0 99 0 98 CC5A CD5AW 042 0 96 0 95 048 0 97 0 96 048 0 95 0 91 ...

Страница 31: ...ion Size Heating Indoor Section Size Heating Capacity Power Capacity Power CC5A CD5AC 048 0 95 1 06 CK5PW 048 0 98 0 97 CC5A CD5AW 048 0 98 1 01 COILS 58CV A X 135 22 VARIABLE SPEED FURNACE CD5AA 048 0 98 1 01 CC5A CD5AW 048 0 98 1 01 CE3AA 048 1 00 1 02 CD5AA 048 0 98 1 00 CK3BA 048 1 00 1 02 CE3AA 048 0 98 0 99 CK5A CK5BA 048 1 00 1 02 CK3BA 048 0 98 0 97 CK5A CK5BE 042 0 99 1 07 CK5A CK5BA 048 ...

Страница 32: ... 55 7 55 7 3 74 70 1225 18 2 16 7 3 00 22 3 20 5 3 11 26 3 23 9 3 21 30 4 27 0 3 32 35 3 32 2 3 45 40 9 40 9 3 62 47 5 47 5 3 85 54 7 54 7 4 11 1400 18 6 17 1 3 04 22 6 20 8 3 13 26 6 24 3 3 22 30 8 27 4 3 31 35 8 32 6 3 43 41 5 41 5 3 58 48 2 48 2 3 79 55 3 55 3 4 02 1575 18 9 17 4 3 08 23 0 21 1 3 17 26 9 24 5 3 24 31 2 27 7 3 32 36 2 33 0 3 43 42 0 42 0 3 57 48 8 48 8 3 78 55 1 55 1 3 93 75 122...

Страница 33: ...ting Indoor Section Size Heating Capacity Power Capacity Power CC5A CD5AA 060 1 00 1 06 CK5A CK5BT 060 0 99 0 95 CC5A CD5AW 060 1 00 1 01 CK5A CK5BX 060 0 99 0 95 CE3AA 060 1 01 1 02 CK5PA 060 0 99 0 95 CK3BA 060 1 00 0 98 CK5PT 060 0 99 0 95 CK5A CK5BA 060 1 00 0 98 CK5PX 060 0 99 0 93 CK5A CK5BX 060 1 01 0 98 COILS 58CV A X 155 22 VARIABLE SPEED FURNACE CK5PA 060 1 00 0 98 CC5A CD5AW 060 0 98 1 ...

Страница 34: ...48 7 4 61 62 6 62 6 4 80 73 4 73 4 5 06 84 1 84 1 5 27 2250 27 3 25 1 4 17 33 5 30 8 4 29 39 6 36 1 4 39 46 3 41 1 4 49 54 2 49 3 4 62 63 3 63 3 4 80 74 4 74 4 5 02 84 0 84 0 5 20 70 1750 25 3 23 3 4 20 31 8 29 2 4 38 38 3 34 9 4 55 44 7 39 7 4 69 52 2 47 5 4 86 60 9 60 9 5 08 71 3 71 3 5 37 83 2 83 2 5 68 2000 25 9 23 8 4 26 32 4 29 8 4 43 38 8 35 4 4 57 45 3 40 2 4 69 52 9 48 2 4 84 61 7 61 7 5 ...

Страница 35: ...ms 8 and 9 following 8 For interconnecting refrigerant tube lengths greater than 50 ft and or elevation differences between indoor and outdoor units greater than 20 ft consult Application Guide line and Service Manual Air Conditioners and Heat Pumps Using Puron Refrigerant 9 If ANY refrigerant tubing is buried provide a minimum 6 in vertical rise to the valve connections at the unit Refrigerant tu...

Страница 36: ... be constructed of galvanized steel bonderized and coated with a powder coat paint Fans Condenser fan will be direct drive propeller type discharging air upward Air Cooled Split System Heat Pump 38YZA 1 1 2 to 5 Tons Nominal Condenser fan motors will be totally enclosed 1 phase type with class B insulation and permanently lubricated bearings Shafts will be corrosion resistant Fan blades will be st...

Отзывы: