30
Heat pump heating performance continued
Multipliers for Determining the Performance With Other Indoor Sections.
INDOOR
AIR
OUTDOOR COIL ENTERING AIR TEMPERATURES °F
–3
7
17
27
37
47
57
67
EDB CFM
Capacity
(MBtuh)
Total
Pow-
er
Capacity
(MBtuh)
Total
Pow-
er
Capacity
(MBtuh)
Total
Pow-
er
Capacity
(MBtuh)
Total
Pow-
er
Capacity
(MBtuh)
Total
Pow-
er
Capacity
(MBtuh)
Total
Pow-
er
Capacity
(MBtuh)
Total
Pow-
er
Capacity
(MBtuh)
Total
Pow-
er
Total Int*
kW† Total Int*
kW† Total Int*
kW† Total Int*
kW† Total Int*
kW† Total Int*
kW† Total Int*
kW† Total Int*
kW†
38YZA036-31, 32 Outdoor Section With FX4BNF036 Indoor Section continued
65
1050 15.3 14.1 2.31 19.0 17.5 2.43 22.8 20.8 2.55 26.9 23.9 2.68 31.5 28.6 2.84 36.8 36.8 3.02 43.0 43.0 3.25 50.3 50.3 3.55
1275 15.8 14.5 2.36 19.5 17.9 2.46 23.3 21.2 2.57 27.4 24.3 2.69 32.1 29.2 2.82 37.6 37.6 2.99 44.0 44.0 3.20 51.6 51.6 3.48
1500 16.2 14.9 2.42 19.9 18.3 2.51 23.7 21.6 2.61 27.8 24.7 2.72 32.6 29.7 2.84 38.2 38.2 3.00 44.8 44.8 3.20 52.4 52.4 3.47
70
1050 14.8 13.7 2.42 18.6 17.1 2.54 22.5 20.6 2.68 26.6 23.6 2.82 31.1 28.3 2.98 36.2 36.2 3.17 42.4 42.4 3.41 49.5 49.5 3.72
1275 15.3 14.1 2.47 19.1 17.5 2.57 23.0 21.0 2.70 27.1 24.0 2.82 31.7 28.8 2.96 37.0 37.0 3.13 43.3 43.3 3.35 50.7 50.7 3.64
1500 15.7 14.4 2.52 19.5 17.9 2.62 23.4 21.3 2.74 27.5 24.4 2.85 32.2 29.3 2.98 37.6 37.6 3.14 44.1 44.1 3.35 51.6 51.6 3.62
75
1050 14.4 13.2 2.53 18.1 16.7 2.66 22.2 20.2 2.81 26.2 23.3 2.96 30.7 27.9 3.13 35.7 35.7 3.33 41.7 41.7 3.58 48.7 48.7 3.90
1275 14.8 13.6 2.58 18.7 17.1 2.69 22.7 20.7 2.83 26.7 23.7 2.96 31.3 28.5 3.11 36.5 36.5 3.28 42.6 42.6 3.51 49.8 49.8 3.81
1500 15.2 14.0 2.63 19.1 17.5 2.74 23.1 21.1 2.87 27.2 24.1 2.99 31.8 28.9 3.12 37.1 37.1 3.29 43.4 43.4 3.50 50.7 50.7 3.79
Indoor
Section
Size
Heating
Indoor
Section
Size
Heating
Capacity
Power
Capacity
Power
CK5PW
048
0.97
0.92
CK5A/CK5BE
042
0.99
1.01
COILS + 58CV(A,X)155-22 VARIABLE SPEED FURNACE
CK5PA
042
0.99
0.98
CC5A/CD5AW
042
0.96
0.95
048
0.97
0.96
048
0.95
0.91
CK5PE
042
0.99
1.01
CD5AA
048
0.95
0.90
COILS + 58MVP080-14 VARIABLE SPEED FURNACE
CE3AA
048
0.97
0.93
CC5A/CD5AA
042
0.99
0.97
CK3BA
042
0.97
0.93
CK5A/CK5BA
042
0.99
0.97
048
0.97
0.91
048
0.97
0.96
CK5A/CK5BA
042
0.97
0.93
CK5PA
042
0.99
0.97
048
0.97
0.91
048
0.97
0.96
CK5A/CK5BT
042
0.97
0.93
COILS + 58MVP080-20 VARIABLE SPEED FURNACE
048
0.97
0.91
CC5A/CD5AA
042
0.99
0.98
CK5A/CK5BW
048
0.97
0.91
CD5AA
048
1.00
0.97
CK5PA
042
0.97
0.93
CK5A/CK5BA
042
0.99
0.98
048
0.97
0.91
048
0.97
0.96
CK5PT
042
0.97
0.92
CK5PA
042
0.99
0.98
048
0.97
0.91
048
0.97
0.96
CK5PW
048
0.97
0.91
COILS + 58MVP100-20 VARIABLE SPEED FURNACE
COILS + 58MVP040-14 VARIABLE SPEED FURNACE
CC5A/CD5AA
042
0.98
0.95
CC5A/CD5AA
042
0.97
0.97
CK5A/CK5BA
042
0.98
0.95
CD5AA
048
0.97
0.96
CK5A/CK5BE
042
0.96
0.99
CK5A/CK5BA
042
0.97
0.97
CK5PA
042
0.98
0.95
048
0.97
0.96
CK5PE
042
0.96
0.99
CK5A/CK5BE
042
0.96
1.00
COILS + 58MVP120-20 VARIABLE SPEED FURNACE
CK5A/CK5BW
048
0.99
0.96
CC5A/CD5AA
042
0.96
0.95
CK5PA
042
0.97
0.97
CD5AA
048
0.97
0.94
048
0.97
0.96
CK5A/CK5BA
042
0.96
0.95
CK5PE
042
0.96
1.00
048
0.97
0.94
CK5PW
048
0.99
0.96
CK5A/CK5BE
042
0.96
0.99
COILS + 58MVP060-14 VARIABLE SPEED FURNACE
CK5A/CK5BW
048
0.99
0.93
CC5A/CD5AA
042
0.99
0.98
CK5PA
042
0.96
0.95
CD5AA
048
0.97
0.96
048
0.97
0.94
CK5A/CK5BA
042
0.99
0.98
CK5PE
042
0.96
0.99
048
0.97
0.96
CK5PW
048
0.99
0.93
See notes on pg. 34.