spare protective limits input channel in place of the factory-installed jumper. (Wire multiple
inputs in series.) The opening of any contact will result in a safety shutdown and LID display.
Refer to the certified drawings for safety contact ratings.
Analog temperature sensors may also be added to the options modules, if installed. These
may be programmed to cause an alert on the CCN network, but will not shut the machine down.
Spare Alarm Contacts
Two spare sets of alarm contacts are provided within the starter. The contact ratings are
provided in the certified drawings. The contacts are located on terminal strip TB6, terminals 5A
and 5B, and terminals 5C and 5D.
Condenser Pump Control
The machine will monitor the
CONDENSER PRESSURE
and may turn on this pump if the
pressure becomes too high whenever the compressor is shut down.
CONDENSER
PRESSURE OVERRIDE
is used to determine this pressure point. This value is found on the
Equipment Service1 LID table and has a default value (
Table 4
). If the
CONDENSER
PRESSURE
is greater than or equal to the
CONDENSER PRESSURE OVERRIDE
, and the
ENTERING CONDENSER WATER TEMP
(
Temperature
) is less than 115 F (46 C), then the
condenser pump will energize to try to decrease the pressure. The pump will turn off when the
condenser pressure is less than the pressure override less 5 psi (34 kPa), or the
CONDENSER
REFRIG (Refrigerant) TEMP
is within 3° F (2° C) of the
ENTERING CONDENSER WATER
temperature.
Содержание PC211
Страница 317: ...Figure 1 19XL Identification ...
Страница 318: ...Figure 2A Front View Typical 19XL Components Design I See next page for Rear View ...
Страница 319: ...Figure 2A Rear View Typical 19XL Components Design I ...
Страница 320: ...Figure 2B Front View Typical 19XL Components Design II See next page for Rear View ...
Страница 321: ...Figure 2B Rear View Typical 19XL Components Design II ...
Страница 322: ...Figure 3 Refrigerant Motor Cooling and Oil Cooling Cycles ...
Страница 323: ...Figure 4 Lubrication System ...
Страница 324: ...Figure 5 Cutler Hammer Solid State Starter Internal View ...
Страница 325: ...Figure 6 Benshaw Inc Solid State Starter Internal View ...
Страница 326: ...Figure 7 Typical Starter Front View Solid State Starter Shown ...
Страница 327: ...Figure 8 19XL Controls and Sensor Locations ...
Страница 328: ...Figure 9 Control Sensors Temperature ...
Страница 329: ...Figure 10 Control Sensors Pressure Transducer Typical ...
Страница 330: ...Figure 11 Control Panel Front View with Options Module ...
Страница 331: ...Figure 12 Power Panel with Options ...
Страница 332: ...Figure 13 LID Default Screen ...
Страница 333: ...Figure 14 LID Service Screen ...
Страница 334: ...Figure 15 Example of Point Status Screen Status01 ...
Страница 335: ...Figure 16 19XL Menu Structure ...
Страница 336: ...Figure 17 19XL Service Menu Structure ...
Страница 337: ...Figure 18 Example of Time Schedule Operation Screen ...
Страница 338: ...Figure 19 Example of Set Point Screen ...
Страница 339: ...Figure 20 19XL Hot Gas Bypass Surge Prevention ...
Страница 340: ...Figure 21 19XL with Default Metric Settings ...
Страница 341: ...Figure 22 Example of Attach to Network Device Screen ...
Страница 342: ...Figure 23 Example of Holiday Period Screen ...
Страница 344: ...Figure 25 Typical Wet Bulb Type Vacuum Indicator ...
Страница 345: ...Figure 26 19XL Leak Test Procedures ...
Страница 346: ...Figure 27 Typical Optional Pumpout System Piping Schematic with Storage Tank ...
Страница 347: ...Figure 28 Typical Optional Pumpout System Piping Schematic without Storage Tank ...
Страница 348: ...Figure 29 Dehydration Cold Trap ...
Страница 349: ...Figure 30 Benshaw Inc Solid State Starter Power Stack ...
Страница 350: ...Figure 31 Ramp Up and Starting Torque Potentiometers ...
Страница 351: ...Figure 32 Typical Potentiometer Adjustment ...
Страница 352: ...Figure 33 Typical Cutler Hammer Solid State Starter ...
Страница 353: ...Figure 34 Correct Motor Rotation ...
Страница 356: ...Figure 37 Optional Pumpout System ...
Страница 357: ...Figure 38 Guide Vane Actuator Linkage ...
Страница 358: ...Figure 39 19XL Float Valve Designs ...
Страница 359: ...Figure 40 Optional Pumpout System Controls ...
Страница 360: ...Figure 41 PSIO Module Address Selector Switch Locations and LED Locations ...
Страница 361: ...Figure 42 LID Module Rear View and LED Locations ...
Страница 362: ...Figure 43 Processor PSIO Module ...
Страница 363: ...Figure 44 Starter Management Module SSM ...
Страница 364: ...Switch Setting Option Module 1 Option Module 2 S1 S2 6 4 7 2 Figure 45 Options Module ...
Страница 365: ...Figure 46 Typical Benshaw Inc Solid State Starter Internal View ...
Страница 366: ...Figure 47 Resistance Check ...
Страница 367: ...Figure 48 SCR and Power Poles ...
Страница 368: ...Figure 49 Typical Cutler Hammer Solid State Starter Internal View ...
Страница 369: ...Figure 50 Cutler Hammer Terminal Functions ...
Страница 370: ...Figure 51 Solid State Starter General Operation Troubleshooting Guide Typical ...
Страница 371: ...Figure 52 Solid State Starter Starter Fault Motor Will Not Start Troubleshooting Guide Typical ...
Страница 373: ...Figure 54 Compressor Fits and Clearances Continued ...
Страница 374: ...Figure 55 Compressor Fits and Clearances Continued ...