Table 47A — Set Point Ranges and Defaults (English Units)
LEGEND
*These items are found under the Service function, and can only be accessed
using either the ComfortWORKS® software or Service Tool.
†These items are found under the Service function.
**Occupied space.
††Sizes 088-104 only.
¶Supply duct.
NOTE: For VAV applications, the OHSP provides the morning warm-up set
point.
Table 47B — Set Point Ranges and Defaults (SI Units)
LEGEND
*These items are found under the Service function, and can only be accessed
using either the ComfortWORKS software or Service Tool.
†These items are found under the Service function.
**Occupied space.
††Sizes 088-104 only.
||HSIO display reads in units of CFM. Service tool will read in units of cubic
meters/minute; default is 0.03 m
3
/m with range of 0 to 1416 m
3
/m.
¶Supply duct.
NOTE: For VAV applications, the OHSP provides the morning warm-up set
point.
DISPLAY
SET POINT DESCRIPTION
DEFAULT VALUE
ALLOWABLE RANGE
BPSP
Building pressure set point
0.05 in. wg
0 to .50 in. wg
ECSO*
Economizer set point offset
3 F
1 to 10 F
HHL†
High humidity override (percent)
99%
0 to 100%
HTMP
High temperature minimum position
35%
0 to 100%
HUSP
Humidity set point (percent)**
40%
0 to 100%
IAQS†
IAQ set point
650 ppm
0 to 5000 ppm
LIMT†
Reset limit (F)
10 F
0 to 20 F
LSP
Loadshed set point (percent)
50%
0 to 100%
LTMP
Low temperature minimum position
10%
0 to 100%
MDP†
Minimum damper position (percent)
20%
0 to 100%
NTLO†
NTFC lockout temperature (F)
50 F
40 to 70 F
OACS† (OCS††)
Outdoor-air cfm set point
1 cfm
0 to 50,000 cfm
OCSP
Occupied cool set point (F)**
78 F
55 to 80 F
OHSP
Occupied heat set point (F)**
68 F
55 to 80 F
PES1† (PES††)
Power exhaust on-set point 1 (percent)
90%
30 to 100%
PES2†
Power exhaust on-set point 2 (percent)
90%
30 to 100%
RTIO†
Reset ratio
3
0 to 10
SASP
Supply air set point (F)
55 F
45 to 70 F
SPSP
Static pressure set point¶
1.5 in. wg
0 to 5.0 in. wg
UCDB*
Unoccupied cooling deadband
1 F
0 to 10 F
UCSP
Unoccupied cool set point (F)**
90 F
75 to 95 F
UHDB*
Unoccupied heating deadband
1 F
0 to 10 F
UHSP
Unoccupied heat set point (F)**
55 F
40 to 80 F
IAQ
—
Indoor-Air Quality
NFTC
—
Nighttime Free Cooling
ppm
—
Parts Per Million
VAV
—
Variable Air Volume
DISPLAY
SET POINT DESCRIPTION
DEFAULT VALUE
ALLOWABLE RANGE
BPSP
Building pressure set point
12.44 Pa
0 to 125 Pa
ECSO*
Economizer set point offset
1.7 C
0.6 to 5.6 C
HHL†
High humidity override (percent)
99%
0 to 100%
HTMP
High temperature minimum position
35%
0 to 100%
HUSP
Humidity set point (percent)**
40%**
0 to 100%
IAQS†
IAQ set point
650 ppm
0 to 5000 ppm
LIMT†
Reset limit (F)
5.6 C
0 to 11.1 C
LSP
Loadshed set point (percent)
50%
0 to 100%
LTMP
Low temperature minimum position
10%
0 to 100%
MDP†
Minimum damper position (percent)
20%
0 to 100%
NTLO†
NTFC lockout temperature (F)
10.0 C
4.4 to 21.0 C
OACS† (OCS††)
Outdoor-air cfm set point
1 cfm||
0 to 50,000 cfm||
OCSP
Occupied cool set point (F)**
25.6 C**
13 to 27 C
OHSP
Occupied heat set point (F)**
20 C**
13 to 27 C
PES1† (PES††)
Power exhaust on-set point 1 (percent)
90%
30 to 100%
PES2†
Power exhaust on-set point 2 (percent)
90%
30 to 100%
RTIO†
Reset ratio
3
0 to 10
SASP
Supply air set point (F)
12.8 C
7.2 to 21 C
SPSP
Static pressure set point¶
373 Pa¶
0 to 1246 Pa
UCDB*
Unoccupied cooling deadband
0.6 C
0 to 5.6 C
UCSP
Unoccupied cool set point (F)**
32.2 C**
24 to 35 C
UHDB*
Unoccupied heating deadband
0.6 C
0 to 5.6 C
UHSP
Unoccupied heat set point (F)**
12.8 C**
4.4 to 27 C
IAQ
—
Indoor-Air Quality
NFTC
—
Nighttime Free Cooling
ppm
—
Parts Per Million
VAV
—
Variable Air Volume