111
APPENDIX E — Carrier Default Program Parameter Values
*These settings differ from the VFD manufacturer defaults and are required for Carrier applications.
NOTE: To restore original factory settings, change tYP to 6 in Setup mode (SetP). This restores
the VFD original factory settings.
PARAMETER GROUP
PARAMETER
DEFAULT VALUE
SEtP
(Setup)
ACC1
60.0 Sec
DEC1
60.0 Sec
UL
60.0 Hz
LL
10.0 Hz*
Luln
1
P3
20%
F-P3
0.0 Hz
P4
100%
F-P4
60 Hz
tHr1
See Table 66
StC1
0
StL1
110%
OLN
1
tYP
5*
Gr.F
(Fundamental)
FH
60 Hz
Pt
2
Gr.Fb
(Feedback)
FbP1
1*
Fbln
2
GP
.30
Gl
2 sec
GA
0
GFS
80
P1LL
10
PuL
1
PuUl
10
PuLL
10
Gr.SF
(Frequency Settings)
Fsor
60 Hz
Sr.n
1* (054-104 only)
SrN1
0* (054-104 only)
Gr.Pn
(Panel Control)
Fr
0*
Gr.St
(Terminal Selection)
1t
1
1t0
0
1t1
56
1t2
13
1t3
3
1t4
10
Gr.Pr
(Protection)
UuC
1*
UuCt
2
ArSt
3
Gr.Ut
(Utility)
Cnod
1*
bLSF
1* (054-104 only)
Fnod
2*
bLPn
1*