Table 14 — Sensor Set Point Alert Limits, Ranges, and Default Values
LEGEND
ppm — parts per million
*Once the unit changes from Unoccupied to Occupied mode, a programmed delay of 30 minutes
takes place before any alert will be generated.
Table 15 — Alert Criteria Reset Value for Return to Normal
NOTE: Alert will automatically reset when the actual value equals
the Alert High Limit minus the Reset Value or the actual value
equals the Alert Low Limit plus the reset value.
NAME
DESCRIPTION
SUBFUNCTION
OCCUPIED
SPACE
STATUS
ALERT
DEFAULT
(LOW)
ALERT
DEFAULT
(HIGH)
LOW
LIMIT
HIGH
LIMIT
BP
Building
pressure
Pressure
Occupied
–0.25 in.wg
0.25 in.wg
–0.5 in.wg
0.5 in.wg
IAQ
Indoor-Air
Quality
Inputs
Occupied
0 ppm
800 ppm
0 ppm
5000 ppm
OAC
Outdoor-Air
Cfm
Inputs
Occupied
0 cfm
50,000 cfm
0 cfm
50,000 cfm
OARH
Outdoor-Air
Relative
Humidity
Inputs
Occupied/
Unoccupied
0%
100%
0%
100%
OAT
Outdoor-Air
Temp
Temps
Occupied/
Unoccupied
–40 F
125 F
–40 F
245 F
RAT*
Return-Air
Temp
Temps
Occupied
60 F
90 F
–40 F
245 F
Unoccupied
35 F
120 F
–40 F
245 F
RH*
Relative
Humidity
Inputs
Occupied/
Unoccupied
0%
100%
0%
100%
SAT*
Supply-Air
Temp
Temps
Occupied
45 F
180 F
–40 F
245 F
Unoccupied
35 F
180 F
–40 F
245 F
SP*
Static
Pressure
Pressure
Occupied/
Unoccupied
0.0 in. wg
2.0 in. wg
0.0 in. wg
5.0 in. wg
SPT*
Space
Temperature
Temps
Occupied
65 F
80 F
–10 F
245 F
Unoccupied
45 F
100 F
–10 F
245 F
NAME
DESCRIPTION
RESET VALUE
BP
Actual Space Pressure
None
IAQ
Indoor-Air Quality
None
OAC
Constant Outdoor-Air Cfm
None
OARH
Outdoor-Air Relative Humidity
2%
OAT
Outdoor-Air Temperature
1 F
RAT
Return-Air Temperature
1 F
RH
Space Relative Humidity
2%
SAT
Supply-Air Temperature
2 F
SP
Static Pressure
0.2 in. wg
SPT
Space Temperature
1 F