17
O/W2
W/W1
Y1/W2
G
R
W2
W1
THERMIDISTAT
CONTROL
MODEL RH
FK4, FV4
FAN COIL
TWO-STAGE
AIR CONDITIONER
Y1
G
C
Y2
R
Y1
C
DHUM
HUM
B
S1
S2
Y/Y2
R
O
C
DH
HEAT STAGE 2
HEAT STAGE 1
COOL STAGE 1
COOL STAGE 2
FAN
24 VAC HOT
24 VAC COMM
DEHUMIDIFY
HUMIDIFY
N/A
OUTDOOR
SENSOR
CONNECTION
Y/Y2
HUMIDIFIER
(24 VAC)
OUTDOOR
SENSOR
REMOVE J2 JUMPER
FOR HEAT STAGING
REMOVE
J1 JUMPER
O/W2
W/W1
Y1/W2
G
R
THERMIDISTAT
CONTROL
MODEL RH
FURNACE
BOARD
AFS
BOARD
TWO-STAGE
AIR CONDITIONER
VARIABLE SPEED
80% NON-CONDENSING FURNACE
W/W1
G
Y/Y2
C
Y2
Y1
C
DHUM
HUM
B
S1
S2
R
W2
O
Y1
R
COM
HUM
PL9-10
DEHUM
HEAT STAGE 1
COOL STAGE 2
COOL STAGE 1
HEAT STAGE 2
FAN
24 VAC HOT
24 VAC COM
DEHUMIDIFY
HUMIDIFY
N/A
OUTDOOR
SENSOR
CONNECTIONS
Y/Y2
HUMIDIFIER
(24 VAC)
OUTDOOR
SENSOR
O/W2
W/W1
Y1/W2
G
R
THERMIDISTAT
CONTROL
MODEL RH
VARIABLE-SPEED
CONDENSING
FURNACE
TWO-STAGE
AIR CONDITIONER
W/W1
G
Y/Y2
C
Y2
R
Y1
C
DHUM
HUM
B
S1
S2
W2
R
C
HEAT STAGE 1
COOL STAGE 1
COOL STAGE 2
HEAT STAGE 2
FAN
24 VAC HOT
24 VAC COMM
DEHUMIDIFY
HUMIDIFY
N/A
OUTDOOR
SENSOR
CONNECTION
Y/Y2
HUMIDIFIER
(24 VAC)
OUTDOOR
SENSOR
HUM
DEHUM
DE
JUMPER
LEGEND
24 VOLT FACTORY WIRING
24 VOLT FIELD WIRING
FIELD SPLICE CONNECTION
RELAY SPDT, PILOT DUTY
24-V COIL (HN61KK324)
OR EQUIVALENT
HUMIDISTAT, OPENS ON
HUMIDITY RISE (HL38MG026)
AIRFLOW SELECTOR
R1
H
AFS
A02005
Fig. 13
---
Infinity Wiring with 2--Stage Puron refrigerant Air Conditioner
Applies to 24ANA7 Models Only
WIRING DIAGRAM NOTES:
1. WIRING MUST CONFORM TO NEC OR LOCAL CODES.
2. UNDERLINED LETTER ON THERMOSTAT TERMINAL INDICATES USAGE. FOR EXAMPLE: O/W2 MEANS O IS ENERGIZED IN COOLING MODE.
3. REFER TO INDOOR UNIT INSTALLATION INSTRUCTIONS FOR ANY ADDITIONAL FEATURES AND WIRING INFORMATION.
4. NON---PROGRAMMABLE MODEL 2S01 B, WHEN USED IN AIR CONDITIONING INSTALLATION THE R19 JUMPER MUST BE CUT AND REMOVED.
5. PROGRAMMABLE MODEL 2S01 B MUST HAVE DIP SWITCH C ON WHEN USED IN AIR CONDITIONER APPLICATIONS.
6. THERMIDISTAT DIP SWITCH NO. 1 SHOULD BE SET IN OFF POSITION FOR AIR CONDITIONER APPLICATIONS (FACTORY DEFAULT).
7. AS AN OPTION O/W2CAN CONTROL SECOND---STAGE HEAT.
8. THERMIDISTAT DIP SWITCH NO. 2 SHOULD BE SET IN THE ON POSITION FOR DUAL CAPACITY COMPRESSOR OPERATION.
9. TO ACTIVATE DEHUMIDIFY FUNCTION ON FK4 OR FV4, REMOVE J1 JUMPER AT FAN COIL CONTROL BOARD.
10. AS AN OPTION, LOCK FURNACE INTO LOW---FIRE OPERATION AND LET O/W2 CONTROL HIGH FIRE OPERATION. REFER TO FURNACE INSTALLATION
INSTRUCTIONS FOR PROPER SETUP.
11. TO ACTIVATE DEHUMIDIFY FEATURE ON CURRENT STYLE, VARIABLE---SPEED, 80 PERCENT NON---CONDENSING, FURNACE DISCONNECT GREEN
(DEHUM) WIRE FROM G ON FURNACE CONTROL BOARD AND CONNECT TO DEHUMIDIFY TERMINAL DHUM ON THERMIDISTAT.
12. THE DE JUMPERS MUST BE REMOVED TO ENABLE THE DEHUMIDIFICATION FEATURE ON FURNACE.
24AN
A