NOTE

:

24ANA7 series only, using non--communicating

(non--Infinity) Carrier electronic thermostats are equipped with a
15--minute staging timer. This timer prevents the two--stage
system from at high stage until unit has been operating in low
stage for 15 minutes unless there is at least a 5

_

F difference

between room temperature and thermostat set point. To force high
stage (after a minimum of 2 minutes in low stage), adjust the set
point at least 5

_

below room ambient.

6. Set room thermostat to COOL and fan control to AUTO

or ON as desired. Wait for appropriate time delay(s).
Operate unit for 15 minutes. Check refrigerant charge.

STEP 12

SYSTEM FUNCTIONS AND SEQUENCE OF

OPERATION

The outdoor unit control system has special functions. The

following is an overview of the two--stage control functions:

COOLING OPERATION

The 24ANA7 models utilize either a 2--stage cooling indoor
thermostat or an Infinity communicating User Interface. The

24ANA1 models utilize an Infinity communicating User Interface

only. With a call for first stage cooling, the outdoor fan and
low--stage compressor are energized. If low--stage cannot satisfy

cooling demand, high--stage is energized by the second stage of
indoor thermostat or User Interface. After second stage is

satisfied, the unit returns to low--stage operation until first stage is

satisfied or until second stage is required again. When both first
stage and second stage cooling are satisfied, the compressor will

shut off.

NOTE

: On 24ANA7 models, if unit has not operated within the

past 12 hrs, or following a unit power--up, upon the next
thermostat high-- or low--stage demand, unit operates for a
minimum of 5 minutes in high--stage.

NOTE

:

On 24ANA7 models with non--communicating

(non--Infinity) systems, with first stage of cooling, (Y1) is
powered on; and with second stage of cooling, (Y1 and Y2) are
on.

NOTE

: When two--stage unit is operating at low--stage, system

vapor (suction) pressure will be higher than a standard
single--stage system or high--stage operation.

NOTE

: Outdoor fan motor will continue to operate for one

minute after compressor shuts off, when outdoor ambient is
greater than or equal to 100

_

F.

COMMUNICATION AND STATUS FUNCTION LIGHTS
For Infinity Control Only, Green communications (COMM)

Light

A green LED

(COMM light)

on the outdoor board (see Fig. 10)

indicates successful communication with the other system
products. The green LED will remain OFF until communications

is established. Once a valid command is received, the green LED

will turn ON continuously. If no communication is received
within 2 minutes, the LED will be turned OFF until the next valid

communication.

Amber Status Light

An amber colored

STATUS light

is used to display the operation

mode and fault codes as specified in the troubleshooting section.
See Table 5 for codes and definitions.

NOTE

: Only one code will be displayed on the outdoor unit

control board (the most recent, with the highest priority).

UTILITY INTERFACE
With Infinity Control

The utility curtailment relay should be wired between R and Y2

connections on the control board for Infinity Communicating
Systems only (see Fig. 10.) This input allows a power utility

device to interrupt compressor operation during peak load

periods. When the utility sends a signal to shut the system down,
the User Interface will display, “Curtailment Active”.

ONE MINUTE STAGE CHANGE TIME DELAY ON
24ANA7 MODELS

When compressor changes stages from high to low or low to
high, there is a 1--minute time delay before compressor restarts.

The outdoor fan motor remains running.

COMPRESSOR OPERATION ON 24ANA7 MODELS

When the compressor operates in high stage operation, the motor
rotates clockwise. Both the lower and upper pistons are eccentric

with the rotating crankshaft and both compress refrigerant.
When the compressor operates in low stage operation the motor

reverses direction (rotates counterclockwise). The lower piston

becomes idle and the upper piston compresses refrigerant.

The

start and run windings are reversed.
COMPRESSOR OPERATION ON 24ANA1 MODELS

When the compressor is operating in low stage, the modulating

ring is de--activated, allowing two internal bypass ports to close
off 33% of the scroll compression area so the system operates at

part load capacity. The 24--volt solenoid coil is de--energized in
low stage operation.
When the compressor is operating at high stage, the modulating

ring is activated, sealing the bypass ports, which allows the
compressor to operate at full load capacity. The 24--volt solenoid

coil is energized in high stage operation. The 24ANA1 unit
contains a 230v to 24vac transformer to supply power to the

solenoid when it is energized. The compressor solenoid load

should not be included in the system (furnace or fan coil) control
power transformer sizing.

CRANKCASE HEATER OPERATION

The crankcase heater is energized during unit off cycle regardless
of OAT temperature on 24ANA7 models.
The crankcase heater is energized during off cycle below 65

_

F on

24ANA1 models.

OUTDOOR FAN MOTOR OPERATION

The outdoor unit control energizes the outdoor fan any time the
compressor is operating. The outdoor fan remains energized if a

pressure switch or compressor overload should open. Outdoor fan

motor will continue to operate for one minute after the
compressor shuts off when the outdoor ambient is greater than or

equal to 100

_

F.

On 24ANA7 models, the outdoor fan remains energized during

the 1--minute compressor staging time delay.

24AN

A

Содержание INFINITY 24ANA

Страница 1: ... series will also be identified TABLE OF CONTENTS PAGE SAFETY CONSIDERATIONS 2 INSTALLATION RECOMMENDATIONS 2 INSTALLATION 3 11 Step 1 Check Equipment Jobsite 3 Step 2 Install on Solid Pad 3 Step 3 Clearance Requirements 3 Step 4 Operating Ambient 3 Step 5 Install TXV 3 4 Step 6 Make Piping Connections 5 8 Step 7 Make Electrical Connections 8 9 Step 8 Compressor Crankcase Heater 9 Step 9 Install A...

Страница 2: ...D SAFETY HAZARD Failure to follow this warning could result in personal injury or equipment damage Puron refrigerant systems operate at higher pressures than standard R 22 systems Do not use R 22 service equipment or components on Puron equipment INSTALLATION RECOMMENDATIONS NOTE In some cases noise in the living area has been traced to gas pulsations from improper installation of equipment 1 Loca...

Страница 3: ...ng rooftop applications Roof mounted units exposed to winds above 5 mph may require wind baffles Consult the Application Guideline and Service Manual Residential Split System Air Conditioners and Heat Pumps Using Puron Refrigerant for wind baffle construction UNIT BASE PAN DIMENSIONS TIEDOWN KNOCKOUT LOCATIONS A B C 36 1 2 x 40 11 5 8 6 13 16 28 3 4 29 1 2 X 33 10 1 16 5 5 8 23 3 4 A05177 Fig 3 Cl...

Страница 4: ...pe See Fig 4 for correct positioning of sensing bulb 9 Proceed with remainder of unit installation 2 O CLOCK 10 O CLOCK SENSING BULB STRAP SUCTION TUBE 8 O CLOCK 4 O CLOCK IN OD SMALLER LARGER THAN 7 8 IN OD 7 8 A81032 Fig 4 Position of Sensing Bulb REPLACING TXV ON R 22 INDOOR COIL 1 Pump system down to 2 psig and recover refrigerant 2 Remove coil access panel and fitting panel from front of cabi...

Страница 5: ...e or improper operation To prevent damage to unit or service valves observe the following S Use a brazing shield S Wrap service valves with wet cloth or use a heat sink material Outdoor units may be connected to indoor section using accessory tubing package or field supplied refrigerant grade tubing of correct size and condition For tubing requirements beyond 80 ft substantial capacity and perform...

Страница 6: ...d with Infinity Control Low Ambient not allowed with non communicating Thermostat No No Winter Start Control Standard with Infinity Control Low Ambient not allowed with Non Communicating Thermostat No No Accumulator No No No Compressor Start Assist Capacitor and Relay Standard on 24ANA7 models Not required on 24ANA1 models since compressor always starts un loaded Standard on 24ANA7 models Not requ...

Страница 7: ...refrigerant grade tubing Service valves are closed from factory and ready for brazing After wrapping service valve with a wet cloth braze sweat connections using industry accepted methods and materials Consult local code requirements Refrigerant tubing and indoor coil are now ready for leak testing This check should include all field and factory joints EVACUATE REFRIGERANT TUBING AND INDOOR COIL C...

Страница 8: ...t with compressor terminal box cover removed Be sure field wiring complies with local and national fire safety and electrical codes and voltage to system is within limits shown on unit rating plate Contact local power company for correction of improper voltage See unit rating plate for recommended circuit protection device NOTE Operation of unit on improper line voltage constitutes abuse and could...

Страница 9: ...he positions of SW1 5 AIRFLOW SELECTION FOR FK4 FV4 FAN COILS FOR 24ANA7 MODELS ONLY USING NON COMMUNICAT ING NON INFINITY THERMOSTATS The FK4 and FV4 provide high and low stage blower operation to match the capacities of compressor at high and low stage To select recommended airflow refer to the FK4 and FV4 Installation Instructions The FK4 and FV4 utilize an Easy Select control board that allows...

Страница 10: ...mber Status Light An amber colored STATUS light is used to display the operation mode and fault codes as specified in the troubleshooting section See Table 5 for codes and definitions NOTE Only one code will be displayed on the outdoor unit control board the most recent with the highest priority UTILITY INTERFACE With Infinity Control The utility curtailment relay should be wired between R and Y2 ...

Страница 11: ...d low ambient operation The Infinity Control provides an automatic evaporator coil freeze protection algorithm that eliminates the need for an evaporator freeze thermostat Low ambient cooling must be enabled in the User Interface set up Fan may not begin to cycle until about 40_F OAT Fan will cycle based on coil and outdoor air temperature Infinity controlled low ambient mode operates as follows S...

Страница 12: ...trol senses the opening of a high or low pressure switch it will respond as follows 1 De energize the appropriate compressor contactor 2 Keep the outdoor fan operating for 15 minutes 3 Display the appropriate fault code See Table 5 4 After a 15 minute delay if there is still a call for cooling and the LPS or HPS is reset the appropriate compressor contactor is energized 5 If LPS or HPS has not clo...

Страница 13: ...art voltage at VS terminal is not achieved the start relay is de energized after 1 second and the control will flash the appropriate fault code If the specified start voltage is not achieved for 3 consecutive low stage starts low stage operation is locked out for 30 minutes If the specified start voltage is not achieved for 3 consecutive high stage starts high stage operation is locked out for 30 ...

Страница 14: ... If the outdoor air sensor indicates 10_F warmer thanthe coil sensor or the outdoor air sensor indicates 20_F cooler than the coil sensor the sensors are out of range If the sensors are out of range the control will flash the appropriate fault code as shown in Table 5 The thermistor comparison is not performed during low ambient cooling or defrost operation FAILED THERMISTOR DEFAULT OPERATION Fact...

Страница 15: ...2 74 1 98 1 55 0 74 Run R C 0 80 0 75 0 48 0 36 Winding 24ANA1024 24ANA1036 24ANA1048 24ANA1060 Start S C 1 40 1 29 1 52 0 60 Run R C 1 32 0 89 0 64 0 49 Table 4 Required Liquid Line Temperature F LIQUID PRESSURE AT SER VICE VALVE PSIG REQUIRED SUBCOOLING TEMPERATURE F 8 10 12 14 16 18 189 58 56 54 52 50 48 195 60 58 56 54 52 50 202 62 60 58 56 54 52 208 64 62 60 58 56 54 215 66 64 62 60 58 56 222...

Страница 16: ...or not reading or out of range Ohm out sensor and check wiring Thermistors out of range 56 Improper relationship between coil sensor and outdoor air sensor Ohm out sensors and check wiring Low Stage Ther mal Cutout 71 No voltage phase difference is detected on 24ANA7 models or compres sor voltage sensed then disappears on 24ANA1 models while cooling or heating demand exists Possible causes are int...

Страница 17: ...TY RISE HL38MG026 AIRFLOW SELECTOR R1 H AFS A02005 Fig 13 Infinity Wiring with 2 Stage Puron refrigerant Air Conditioner Applies to 24ANA7 Models Only WIRING DIAGRAM NOTES 1 WIRING MUST CONFORM TO NEC OR LOCAL CODES 2 UNDERLINED LETTER ON THERMOSTAT TERMINAL INDICATES USAGE FOR EXAMPLE O W2 MEANS O IS ENERGIZED IN COOLING MODE 3 REFER TO INDOOR UNIT INSTALLATION INSTRUCTIONS FOR ANY ADDITIONAL FEA...

Страница 18: ...h rated working pressures less than 600 psig S Do not leave Puron suction line filter driers in line longer than 72 hours S Do not install a suction line filter drier in liquid line S POE oils absorb moisture rapidly Do not expose oil to atmosphere S POE oils may cause damage to certain plastics and roofing materials S Wrap all filter driers and service valves with wet cloth when brazing S A facto...

Отзывы: