background image

Configuring i-Vu Open Link Driver Properties 

 

 

18 

i-Vu Open Link 

 

After you discover the i-Vu Open Link, you may want to customize the i-Vu Open Link's settings for your 

applications. Change settings on the 

Driver Properties 

page.  

Start i-Vu/Field Assistant. 

Right-click the i-Vu Open Link in the navigation tree (

Installer

 view) and select 

Driver Properties

Select from the menu and adjust properties.  

  
 

 

Device 

On the 

Device 

page, you can change the following properties: 

 

BACnet device object properties for the i-Vu Open Link 

 

i-Vu Open Link communication 

 

Configuration

 

NOTE  

The three APDU fields refer to all networks over which the i-

Vu Open Link communicates. 

Max Masters

 - defines the highest MS/TP Master MAC address on 

the MS/TP network.  

Max Masters and Max Info 

Frames

 

For example, if there are 3 master nodes on an MS/TP network, 

and their MAC addresses are 1, 8, and 16, then Max Masters 

would be set to 16 (since this is the highest MS/TP MAC address 

on the network).  
This property optimizes MS/TP network communications by 

preventing token passes and “poll for master” requests to non—

existent Master nodes.  
In the above example, MAC address 16 would know to pass the 

token back to MAC address 1 instead of counting up to MAC 

address 127). Each MS/TP master node on the network must have 

their Max Masters set to this same value. The default is 127. 

Max Info Frames 

- defines the maximum number of responses that 

will be sent when the i-Vu Open Link receives the token.  

Any positive integer is a valid number. The default is 10 and 

should be ideal for the majority of applications. In cases where the 

i-Vu Open Link is the target of many requests, this number could 

be increased as high as 100 or 200.  

  

 

Notification Class #1 

i-Vu/Field Assistant alarms use Notification Class #1. A BACnet alarm's Notification Class defines:  

 

Alarm priority for Alarm, Fault, and Return to Normal states 

 

Options for BACnet alarm acknowledgement 

 

Where alarms should be sent (recipients) 

  

Configuring i-Vu Open Link Driver Properties 

Содержание i-Vu Open Link

Страница 1: ...in nk k I In ns st ta al ll la at ti io on n a an nd d S St ta ar rt t u up p G Gu ui id de e CARRIER CORPORATION 2010 A member of the United Technologies Corporation family Stock symbol UTX Catalog...

Страница 2: ......

Страница 3: ...se an IP addressing scheme 9 To obtain an IP address using DHCP 9 To assign a custom IP address 9 Configuring BACnet device instance and network number 12 Driver 13 To set up BACnet Broadcast Manageme...

Страница 4: ......

Страница 5: ...nected via a common BACnet IP backbone The i Vu Open Link can also integrate third party equipment supporting BACnet MS TP BACnet IP Modbus RTU Modbus IP and LON FT 10 protocols The i Vu Open Link has...

Страница 6: ...5 may need to be installed on Port S1 if the i Vu Open Link is at the beginning or end of a network segment The BT485 adds bias and terminates a network segment Port S2 Configurable EIA 485 EIA 232 po...

Страница 7: ...d brownout 0 to 140 F 18 to 60 C 0 to 90 relative humidity non condensing Storage temperature range 24 to 140 F 30 to 60 C 0 to 90 relative humidity non condensing Physical Rugged aluminum cover remov...

Страница 8: ...te the printed circuit board with fingerprints moisture or any foreign material Do not touch components or leads Handle the board by its edges Isolate from high voltage or electrostatic discharge Ensu...

Страница 9: ...the i Vu Open Link s power 9 Verify that the Run LED a dot in the lower right corner of the Module Status LED begins blinking The Module Status LED will display 8 for about 5 seconds and then reverts...

Страница 10: ...orts and grounds 3 Verify that the Port S1 jumpers are set to 485 2w 4 Set the MS TP baud rate DIP switches 1 and 2 to match the baud rate of the Open network The default is 76 8k 5 Connect the i Vu O...

Страница 11: ...able or disable with a jumper Make sure that only devices at the end of a network have termination enabled EXAMPLE If an EIA 485 2 wire network s characteristic impedance is 120 Ohms terminate one pai...

Страница 12: ...8x where x router address subnet mask 255 255 255 0 default gateway 192 168 168 254 To set the i Vu Open Link address on the Open network CAUTION The router address must be unique on the IP and Open n...

Страница 13: ...r assigned IP addressing The default IP address settings are as follows IP address 192 168 168 x where x i Vu Open Link address rotary switch settings Subnet Mask 255 255 255 0 Default Gateway 192 168...

Страница 14: ...ng Standard desktop select Start right click on My Computer and select Manage b In the Computer Management window select Device Manager and expand Ports COM LPT 4 Ensure that i Vu Open Link s Router C...

Страница 15: ...ault Gateway Click Enter 16 Type in the new Default Gateway Click Enter This Default Gateway will now show up on the Router Configuration screen 17 After entering your settings type 1 to reset and cli...

Страница 16: ...n 5 Ground pin 5 4 Follow steps 4 19 above to launch a terminal program and access the Router Configuration screen to set the IP parameters 5 Reset the Port S2 jumper to the EIA 485 position 6 Cycle t...

Страница 17: ...Router Configuration screen 2 Cycle power to the router for the new settings to effect NOTE If the BACnet MS TP network number of the router is assigned and not auto generated and the Open controllers...

Страница 18: ...program uses when controller s real time clock is invalid Clock Fail Date and Time TIP Use an occupied date and time such as a Tuesday at 10 a m so the equipment does not operate in unoccupied mode i...

Страница 19: ...ollers on one subnet to communicate with controllers on other subnets Enable i Vu to see upload or configure controllers on different subnets NOTE In this document the term router refers to the i Vu O...

Страница 20: ...the BBMD BACnet Broadcast Management Device for its subnet 8 To check if the router has an existing BBMD table click Broadcast Distribution Table Read button 9 If the Broadcast Distribution Table con...

Страница 21: ...Using the next IP address in the bdt file repeat steps 7 through 14 until every file has been updated NOTE To clear the BBMD entries from a router follow the steps above using an empty blank bdt file...

Страница 22: ...set to 16 since this is the highest MS TP MAC address on the network This property optimizes MS TP network communications by preventing token passes and poll for master requests to non existent Master...

Страница 23: ...turn to normal message stored in the i Vu Field Assistant database change the acknowledgement settings on i Vu Field Assistant s Alarm Enable Disable tab for an alarm source or an alarm category Recip...

Страница 24: ...ctions in i Vu Help Controller generated Alarm Short message shown on i Vu s Alarm page or in an alarm action when this type of alarm is generated Description Events Clear these checkboxes to disable...

Страница 25: ...oller alarms After this period minutes seconds of non response from an Open controller the router sends an alarm to the server Dead Module Timeout Alarm Store Forward On the Alarm Store and Forward pa...

Страница 26: ...look for error conditions If you cannot determine the error from the Modstat send a screenshot of the Modstat to Carrier Technical Support To obtain a Modstat Go to the the Enhanced Access menu Select...

Страница 27: ...he i Vu Open Link s 10 year Lithium CR123A battery provides a maximum of 720 hours data retention during power outages To conserve battery life battery backup turns off after a specified number of day...

Страница 28: ...Vu Open Link Serial number If you need the i Vu Open Link s serial number when troubleshooting the number is on a sticker on the back of the main controller board a Module Status report modstat from...

Страница 29: ...harmful interference in which case the user will be required to correct the interference at his own expense CAUTION Changes or modifications not expressly approved by the responsible party for compli...

Страница 30: ...e Statement 26 i Vu Open Link The PIC statements are updated regularly Please refer to the BACnet website http www bacnetinternational net catalog index php m 28 for the latest information Appendix A...

Страница 31: ......

Страница 32: ...CARRIER CORPORATION 2010 A member of the United Technologies Corporation family Stock symbol UTX Catalog No 11 808 462 01 11 19 2010...

Отзывы: