Perform a Control Test —
Check the safety controls
status by performing an automated control test. Access the
CONTROL TEST table and select a test to be performed
function (Table 6).
The Automated Control Test checks all outputs and inputs
for function. The compressor must be in the OFF mode to
operate the controls test. The compressor can be put in OFF
mode by pressing the STOP push-button on the CVC. Each
test asks the operator to confirm the operation is occurring
and whether or not to continue. If an error occurs, the op-
erator can try to address the problem as the test is being done
or note the problem and proceed to the next test.
NOTE: Enter guide vane calibration to calibrate guide
input on CCM (Plug J4 upper terminal 9 and 10).
NOTE: If during the control test the guide vanes do not open,
verify the low pressure alarm is not active. (An active low
pressure alarm causes the guide vanes to close.)
NOTE: The oil pump test will not energize the oil pump if
cooler pressure is below –5 psig (–35 kPa).
When the control test is finished or the EXIT softkey is
pressed, the test stops, and the CONTROL TEST menu dis-
plays. If a specific automated test procedure is not com-
pleted, access the particular control test to test the function
when ready. The CONTROL TEST menu is described in the
table below.
CCM Pressure Thermistors
Check of all thermistors.
CCM Pressure Transducers Check of all transducers.
Pump
Checks operation of pump out-
puts; pumps are activated. Also
tests associated inputs such as
flow or pressure.
Discrete ouputs
Activation of all on/off outputs
individually.
Guide Vane
Check of the guide vane
operation.
Diffuser Actuator*
Check of the diffuser actuator.
Pumpdown/Lockout
Pumpdown prevents the low re-
frigerant alarm during evacuation
so refrigerant can be removed
form the unit. Also locks the
compressor off and starts the
water pumps.
Terminate Lockout
To charge refrigerant and enable
the chiller to run after pumpdown
lockout.
Guide Vane Calibration
Calibrates guide vane input on
CCM.
*Diffuser tests function only on size 5 compressor with diffuser con-
trol enabled.
NOTE: During any of the tests, an out-of-range reading will have an
asterisk (*) next to the reading and a message will be displayed.
Check Optional Pumpout System Controls and
Compressor —
Controls include an on/off switch, a 3-amp
fuse, the compressor overloads, an internal thermostat, a com-
pressor contactor, and a refrigerant high pressure cutout.
The high pressure cutout is factory set to open at 161 psig
(1110 kPa) and reset at 130 psig (896 kPa). Ensure the water-
cooled
condenser
has
been
connected.
Loosen
the
compressor holddown bolts to allow free spring travel. Open
the compressor suction and discharge the service valves. En-
sure oil is visible in the compressor sight glass. Add oil if
necessary.
See the Pumpout and Refrigerant Transfer Procedures and
Optional Pumpout System Maintenance sections, pages 62
and 68, for details on the transfer of refrigerant, oil speci-
fications, etc.
Table 6 — Control Test Menu Functions
TESTS TO BE
PERFORMED
DEVICES TESTED
1. CCM Thermistors
Entering Chilled Water
Leaving Chilled Water
Entering Condenser Water
Leaving Condenser Water
Remote Reset Sensor
Comp Discharge Temp
Comp Thrust Bearing Temp
Oil Sump Temp
Comp Motor Winding Temp
Spare Temperature 1
Space Temperature 2
2. CCM Pressure
Transducers
Evaporator Pressure
Condenser Pressure
Oil Pump Delta P
Spare Pressure Delta P
Condenser Water Delta P
Transducer Voltage Ref
3. Pumps
Oil Pump — Confirm pressure
Chilled Water — Confirm Delta P
Condenser Water — Confirm
Delta P
4. Discrete Outputs
Oil Heater Relay
Hot Gas Bypass Relay
Tower Fan Relay Low
Tower Fan Relay High
Alarm Relay
Shunt Trip Relay
5. Guide Vane Actuator
Open/Close
6. Diffuser Actuator
Open/Close
7. Pumpdown/Lockout
When using pumpdown/lockout,
observe freeze up precautions when
removing charge:
Instructs operator which valves to
close and when.
Starts chilled water and condenser
water pumps and confirms flows.
Monitors
Evaporator pressure
Condenser pressure
Evaporator temperature during
pumpout procedures
Turns pumps off after pumpdown.
Locks out compressor.
8. Terminate Lockout
Starts pumps and monitors flows.
Instructs operator which valves to
open and when.
Monitors
Evaporator pressure
Condenser pressure
Evaporator temperature during
charging process
Terminates compressor lockout.
High Altitude Locations —
Because the chiller is ini-
tially calibrated at sea level, it is necessary to recalibrate
the pressure transducers if the chiller has been moved to a
high altitude location. See the calibration procedure in the
Troubleshooting Guide section.
Charge Refrigerant into Chiller
The transfer, addition, or removal of refrigerant in spring
isolated chillers may place severe stress on external pip-
ing if springs have not been blocked in both up and down
directions.