Table 2 — CVC Display Data (cont)
EXAMPLE 20 — RAMP_DEM DISPLAY SCREEN
To access this display from the CVC default screen:
1. Press
MENU
.
2. Press SERVICE .
3. Scroll down to highlight EQUIPMENT SERVICE .
4. Press SELECT .
5. Scroll down to highlight RAMP_DEM .
DESCRIPTION
STATUS
UNITS
POINT
DEFAULT
Pulldown Ramp Type:
0/1
ramp
opt
1
Select: Temp=0, Load=1
Demand Limit + kW Ramp
Demand Limit Source
0/1
dem
src
0
Select: Amps=0, kW=1
Motor Load Ramp %/Min
5-20
kw
ramp
10
Demand Limit Prop Band
3-15
%
dem
prop
10
Demand Limit At 20 mA
40-100
%
dem
20ma
40
20mA Demand Limit Opt
0/1
DS/ENABLE
dem
sel
DSABLE
Motor Rated Kilowatts
50-9999
kW
motor
kw
145
Demand Watts Interval
5-60
MIN
dw
int
15
NOTE: No variables are available for CCN read or write operation.
EXAMPLE 20 — TEMP_CTL DISPLAY SCREEN
To access this display from the CVC default screen:
1. Press
MENU
.
2. Press SERVICE .
3. Scroll down to highlight EQUIPMENT SERVICE .
4. Press SELECT .
5. Scroll down to highlight TEMP_CTL .
DESCRIPTION
STATUS
UNITS
POINT
DEFAULT
Control Point
EWB Control Option
0/1
DSABLE/ENABLE
ecw
opt
DSABLE
Temp Pulldown Deg/Min
2-10
^F
tmp
ramp
3
Temperature Reset
RESET TYPE 1
Degrees REset At 20 mA
−30- 30
^F
deg
20ma
10
RESET TYPE 2
Remote Temp (No Reset)
−40-245
DEG F
res
rt1
85
Remote Temp (Full Reset)
_40-245
DEG F
res
rt2
65
Degrees Reset
−30-30
^F
deg
rt
10
RESET TYPE 3
CHW Delta T (No Reset)
0-15
^F
restd
1
10
CHW Delta T (Full Reset)
0-15
^F
restd
2
0
Degrees Reset
−30-30
^F
deg
chw
5
Select/Enable Reset Type
0-3
res
sel
0
31