Table 2 — CVC Display Data (cont)
EXAMPLE 14 — NET
OPT DISPLAY SCREEN
To access this display from the CVC default screen:
1. Press
MENU
.
2. Press SERVICE .
3. Scroll down to highlight EQUIPMENT CONFIGURATION .
4. Press SELECT .
5. Scroll down to highlight NET
OPT .
DESCRIPTION
STATUS
UNITS
POINT
DEFAULT
Loadshed Function
Group Number
0-99
ldsgrp
0
Demand Limit Decrease
0-60
%
ldsdelta
20
Maximum Loadshed Time
0-120
MIN
maxldstm
60
CCN Occupancy Config:
Schedule Number
3-99
occpcxxe
3
Broadcast Option
0-1
DSABLE/ENABLE
occbrcst
DSABLE
Alarm Configuration
Re-alarm Time
0-1440
MIN
30
Alarm Routing
0-1
10000000
NOTE: No variables are available for CCN read or write operation.
EXAMPLE 15 — ISM
CONF DISPLAY SCREEN
To access this display from the CVC default screen:
1. Press
MENU
.
2. Press SERVICE .
3. Scroll down to highlight ISM (STARTER) CONFIG DATA .
4. Press SELECT .
5. Scroll down to highlight ISM
CONF .
DESCRIPTION
STATUS
UNITS
POINT
DEFAULT
Starter Type
0-2
starter
1
(0 = Full, 1 = Red, 2 = SS/VFD)
Motor Rated Line Voltage
200-13200
VOLTS
v
fs
460
Volt Transformer Ratio:1
1-33
vt
rat
1
Overvoltage Threshold
105-115
%
overvolt
115
Undervoltage Threshold
85-95
%
undvolt
85
Over/Under Volt Time
1-10
SEC
uvuntime
5
Voltage % Imbalance
1-10
%
v
unbal
5
Voltage Imbalance Time
1-10
SEC
v
time
5
Motor Rated Load Amps
10-5000
AMPS
a
fs
200
Motor Locked Rotor Trip
100-60000
AMPS
motor
lr
1000
Locked Rotor Start Delay
1-10
cycles
lrdelay
5
Starter LRA Rating
100-60000
AMPS
start
lr
2000
Motor Current CT Ratio:1
10-1000
ct
turns
100
Current % Imbalance
5-40
%
c
unbal
15
Current Imbalance Time
1-10
SEC
c
time
5
3 Grnd Fault CT’s? (1 = No)
0-1
NO/YES
gf
phase
YES
Ground Fault CT Ratio:1
150
gf
ctr
150
Ground Fault Current
1-20
AMPS
gf
amps
15
Ground Fault Start Delay
1-20
cycles
gf
delay
10
Ground Fault Persistence
1-10
cycles
gf
pers
5
Single Cycle Dropout
0/1
DSABLE/ENABLE
cycdrop
DSABLE
Frequency = 60 Hz? (No = 50)
0/1
NO/YES
freq
YES
Line Frequency Faulting
0/1
DSABLE/ENABLE
freq
en
DSABLE
28