background image

GH7T: Installation Instructions

Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.

2

Installation

Check Equipment and Job Site

IMPORTANT: 

All  split  system  and  packaged  heat  pumps  must  be

installed pursuant to applicable regional efficiency standards issued by

the Department of Energy.

Unpack Unit

Move to final location. Remove carton taking care not to damage unit. 

Inspect Equipment

File  claim  with  shipping  company  prior  to  installation  if  shipment  is

damaged or incomplete. Locate unit rating plate on unit corner panel. It

contains information needed to properly install unit. Check rating plate

to be sure unit matches job specifications.

Install on a Solid, Level Mounting Pad

If conditions or local codes require the unit be attached to pad, tie down

bolts should be used and fastened through  knockouts  provided in unit

base pan. Refer to unit mounting pattern in 

Fig. 2

 to determine base pan

size and knockout hole location.
For  hurricane  tie  downs,  contact  distributor  for  details  and  PE

Certification (Professional Engineer), if required.
On rooftop applications, mount on level platform or frame. Place unit

above a load-bearing wall and isolate unit and tubing set from structure.

Arrange supporting members to adequately support unit and minimize

transmission  of  vibration  to  building.  Consult  local  codes  governing

rooftop applications. 
Roof mounted  units exposed  to winds  above  5  mph (8.05  km/h)  may

require  wind  baffles.  Consult  the  Service  Manual  -  Residential  Split

System Air Conditioners and Heat Pumps for wind baffle construction.

NOTE: 

Unit  must be level  to within  ±2°(±3/8 in./ft,±9.5 mm/m.) per

compressor manufacturer specifications.

Clearance Requirements

When  installing,  allow  sufficient  space  for  airflow  clearance,  wiring,

refrigerant  piping,  and  service. Allow  24  in.  (609.6  mm)  clearance  to

service  end  of  unit  and  48  in.  (1219.2  mm)  (above  unit.  For  proper

airflow, a 6-in. (152.4 mm) clearance on 1 side of unit and 12-in. (304.8

mm) on all remaining sides must be maintained. Maintain a distance of

24 in. (609.6 mm) between units.  Position so water, snow, or ice from

roof or eaves cannot fall directly on unit. 
On rooftop applications, locate unit at least 6 in. (152.4 mm)  above roof

surface.

A05177

Fig. 2 – Tiedown Knockout Locations

Check Defrost Thermostat

Check defrost  thermostat to  ensure  it  is properly located  and securely

attached.  There  is  a  liquid  header  with  a  distributor  and  feeder  tube

going into outdoor coil. At the end of the one of the feeder tubes, there is

a  3/8  in.  O.D.  stub  tube  approximately  2  in.  long.  (See 

Fig. 3

.)  The

defrost thermostat should be located on stub tube. Note that there is only

one stub tube used with liquid header, and on most units it is the bottom

circuit. 

A97517

Fig. 3 – Defrost Thermostat Location

Elevate Unit

Elevate  unit  per  local  climate  and  code  requirements  to  provide

clearance above estimated snowfall level and ensure adequate drainage

of unit. 

CAUTION

!

CUT HAZARD

Failure to follow this caution may result in personal injury.
Sheet metal parts may have sharp edges or burrs. Use care and wear

appropriate protective clothing and gloves when handling parts.

CAUTION

!

UNIT OPERATION HAZARD

Failure  to  follow  this  caution  may  result  in  equipment  damage  or

improper operation.
Locate  the  unit  in  such  a  way  that  it  is  stable  in  all  circumstances

including adverse weather conditions. 

UNIT BASE PAN

Dimension in. 

(mm)

TIEDOWN KNOCKOUT LOCATIONS in. (mm)

A

B

C

35 X 35

(889 X 889)

9–1/8 (231.8)

6–9/16 (166.7) 28–7/16 (722.3)

CAUTION

!

UNIT OPERATION HAZARD

Failure  to  follow  this  caution  may  result  in  equipment  damage  or

improper operation.
Do not allow water and/or ice to build up in base pan.

FEEDER TUBE

DEFROST
THERMOSTAT

A97517

STUB TUBE

COIL

Содержание GH7T

Страница 1: ...propriate for unit capacity 3 Run refrigerant tubes as directly as possible by avoiding unnecessary turns and bends 4 Leave some slack between structure and unit to absorb vibration 5 When passing refrigerant tubes through the wall seal opening with RTV or other pliable silicon based caulk See Fig 1 6 Avoid direct tubing contact with water pipes duct work floor joists wall studs floors and walls 7...

Страница 2: ...space for airflow clearance wiring refrigerant piping and service Allow 24 in 609 6 mm clearance to service end of unit and 48 in 1219 2 mm above unit For proper airflow a 6 in 152 4 mm clearance on 1 side of unit and 12 in 304 8 mm on all remaining sides must be maintained Maintain a distance of 24 in 609 6 mm between units Position so water snow or ice from roof or eaves cannot fall directly on ...

Страница 3: ...iston body of the liquid service valve temporarily held in place with a plastic cap Do not remove the plastic cap until line set tubing is ready to be installed Refer to Fig 4 and follow these steps for piston installation 1 Remove plastic cap holding piston in piston body of liquid service valve 2 Check that piston size stamped on side of piston matches with number listed on unit rating plate Ret...

Страница 4: ...th a heat sinking material such as a wet cloth Braze joints using a Sil Fos or Phos copper alloy Install Liquid Line Filter Drier Indoor Refer to Fig 6 and install filter drier as follows 1 Braze 5 in 127 mm liquid tube to the indoor coil 2 Wrap filter drier with damp cloth 3 Braze filter drier to 5 in 127 mm long liquid tube from step 1 4 Connect and braze liquid refrigerant tube to the filter dr...

Страница 5: ...d readily accessible from unit per Section 440 14 of NEC Route Ground and Power Wires Remove access panel to gain access to unit wiring Extend wires from disconnect through power wiring hole provided and into unit control box Connect Ground and Power Wires Connect ground wire to ground connection in control box for safety Connect power wiring to contactor as shown in Fig 8 A94025 Fig 8 Line Connec...

Страница 6: ...at the Y2 signal is communicated via the cool tap to the desired speed tap 2 The Y1 call for low stage cooling energizes the Fan tap on the control board The red wire from the fan tap is connected to tap 1 on the motor Refer to the furnace Product Data to find the corresponding airflow If the airflow setting for low cooling needs to be switched from tap 1 to a different tap jumper a connection fro...

Страница 7: ... 5 minute time guard begins counting Compressor will not come on until this delay expires In the event of a power interruption the time guard will not allow another cycle for 5 minutes Compressor Operation The basic scroll design has been modified with the addition of an internal unloading mechanism that opens a by pass port in the first compression pocket effectively reducing the displacement of ...

Страница 8: ...oor temperature is between 70 F and 80 F 21 11 C and 26 67 C Follow the procedure below Unit is factory charged for 15ft 4 57 m of lineset Adjust charge by adding or removing 0 6 oz ft 018 kg m of 3 8 liquid line above or below 15ft 4 57 m respectively For standard refrigerant line lengths 80 ft 24 38 m or less allow system to operate in cooling mode at least 15 minutes If conditions are favorable...

Страница 9: ...unit before adding panels and covers Securely fasten all panels and covers 3 Tighten service valve stem caps to 1 12 turn past finger tight 4 Leave Owner s Manual with owner Explain system operation and periodic maintenance requirements outlined in manual 5 Fill out Dealer Installation Checklist and place in customer file Troubleshooting If the compressor fails to operate with a cooling call the t...

Страница 10: ...erved A Carrier Company Edition Date 03 22 Catalog No GH7T 01SI Replaces New GH7T Installation Instructions Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations 10 ...

Отзывы: