background image

GH7T: Installation Instructions

Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.

4

Brazing Connections

Connect vapor tube to fitting on outdoor unit vapor service valves (see

Table 2

). Connect liquid tubing to adapter tube on liquid service valve.

Use refrigerant grade tubing.

Notes

:

1.Do not apply capillary tube indoor coils to these units.

2.For Tubing Set lengths between 80 and 200 ft. (24.38 and 60.96 m) horizontal or 

20 ft. (6.1 m) vertical differential, refer to the Residential Piping and Longline

Guideline.

Apply heat absorbing paste or heat sink product between service valve

and joint. Wrap service valves with a heat sinking material such as a wet

cloth.

After wrapping service valve with a wet cloth, tubing set can be brazed

to service valve using either silver bearing or non–silver bearing brazing

material.  Do  not  use  soft  solder  (materials  which  melt  below

800°F/427°C). Consult local code requirements. 

NOTE: 

Some  outdoor  units contain  a  mechanical  fitting at  the  liquid

distributor.  This connection is not field serviceable and should not be

disturbed.

NOTE: 

For  Liquid  Service  Valve  -  Braze  lineset  to  adapter  tube

BEFORE bolting adapter to valve.  This helps prevent overheating and

damage to plastic washer or o-ring.

For  Vapor  Service  Valve  -  remove  valve  core  from  schrader  port  on

Service Valve  BEFORE  brazing.    This  helps  prevent  overheating  and

damage to valve seals (refer to 

Fig. 5

). Replace valve core when brazing

is completed.

A14236

Fig. 5 – Vapor Service Valve

Clean line set tube ends with emery cloth or steel brush. Remove any grit

or debris.
Insert line set tube ends into service valve tube stubs.
Apply heat absorbing paste or heat sink product between service valve

and joint. Wrap service valves with a heat sinking material such as a wet

cloth.
Braze joints using a Sil-Fos or Phos-copper alloy.

Install Liquid Line Filter Drier Indoor

Refer to 

Fig. 6

 and install filter drier as follows:

1. Braze 5 in. (127 mm) liquid tube to the indoor coil.
2. Wrap filter drier with damp cloth.
3. Braze filter drier to 5 in. (127 mm) long liquid tube from step 1. 
4. Connect and braze liquid refrigerant tube to the filter drier. 

A05227

Fig. 6 – Liquid Line Filter Drier

Refrigerant tubing and indoor coil are now ready for leak testing. This

check should include all field and factory joints. 

WARNING

!

FIRE HAZARD

Failure to following this warning could result in personal injury, death

and/or property damage.

Refrigerant  and  oil  mixture  could  ignite  and  burn  as  it  escapes  and

contacts  brazing  torch.   Make sure the  refrigerant  charge is  properly

removed from both the high and low sides of the system before brazing

any component or lines.

Table 2 – Refrigerant Connections and Recommended Liquid and 

Vapor Tube Diameters (In.)

UNIT SIZE

LIQUID

RATED VAPOR

*

*. Units are rated with 25 ft. (7.6 m) of lineset. See Product Data sheet for performance 

data when using different size and length linesets.

Connection 

Diameter

Tube 

Diameter

Connection 

Diameter

Tube 

Diameter

024

3/8

3/8

3/4

3/4

036

3/8

3/8

7/8

7/8

048, 060

3/8

3/8

7/8

1-1/8

CAUTION

!

UNIT DAMAGE HAZARD

Failure  to  follow  this  caution  may  result  in  equipment  damage  or

improper operation.
Service valves must be wrapped in a heat–sinking material such as a

wet cloth while brazing.

CAUTION

!

BURN HAZARD

Failure to follow this Caution may result in personal injury.
Components  will  be  HOT  after  brazing.    Wear  appropriate  personal

protective  equipment  and  allow  to  cool  before  handling  parts  and

equipment

CAUTION

!

UNIT DAMAGE HAZARD

Failure  to  follow  this  caution  may  result  in  equipment  damage  or

improper operation.

1. Installation of  filter  drier  in liquid line is  required.
2. Filter drier must be wrapped in a heat-sinking material such as a

wet cloth while brazing.

Содержание GH7T

Страница 1: ...propriate for unit capacity 3 Run refrigerant tubes as directly as possible by avoiding unnecessary turns and bends 4 Leave some slack between structure and unit to absorb vibration 5 When passing refrigerant tubes through the wall seal opening with RTV or other pliable silicon based caulk See Fig 1 6 Avoid direct tubing contact with water pipes duct work floor joists wall studs floors and walls 7...

Страница 2: ...space for airflow clearance wiring refrigerant piping and service Allow 24 in 609 6 mm clearance to service end of unit and 48 in 1219 2 mm above unit For proper airflow a 6 in 152 4 mm clearance on 1 side of unit and 12 in 304 8 mm on all remaining sides must be maintained Maintain a distance of 24 in 609 6 mm between units Position so water snow or ice from roof or eaves cannot fall directly on ...

Страница 3: ...iston body of the liquid service valve temporarily held in place with a plastic cap Do not remove the plastic cap until line set tubing is ready to be installed Refer to Fig 4 and follow these steps for piston installation 1 Remove plastic cap holding piston in piston body of liquid service valve 2 Check that piston size stamped on side of piston matches with number listed on unit rating plate Ret...

Страница 4: ...th a heat sinking material such as a wet cloth Braze joints using a Sil Fos or Phos copper alloy Install Liquid Line Filter Drier Indoor Refer to Fig 6 and install filter drier as follows 1 Braze 5 in 127 mm liquid tube to the indoor coil 2 Wrap filter drier with damp cloth 3 Braze filter drier to 5 in 127 mm long liquid tube from step 1 4 Connect and braze liquid refrigerant tube to the filter dr...

Страница 5: ...d readily accessible from unit per Section 440 14 of NEC Route Ground and Power Wires Remove access panel to gain access to unit wiring Extend wires from disconnect through power wiring hole provided and into unit control box Connect Ground and Power Wires Connect ground wire to ground connection in control box for safety Connect power wiring to contactor as shown in Fig 8 A94025 Fig 8 Line Connec...

Страница 6: ...at the Y2 signal is communicated via the cool tap to the desired speed tap 2 The Y1 call for low stage cooling energizes the Fan tap on the control board The red wire from the fan tap is connected to tap 1 on the motor Refer to the furnace Product Data to find the corresponding airflow If the airflow setting for low cooling needs to be switched from tap 1 to a different tap jumper a connection fro...

Страница 7: ... 5 minute time guard begins counting Compressor will not come on until this delay expires In the event of a power interruption the time guard will not allow another cycle for 5 minutes Compressor Operation The basic scroll design has been modified with the addition of an internal unloading mechanism that opens a by pass port in the first compression pocket effectively reducing the displacement of ...

Страница 8: ...oor temperature is between 70 F and 80 F 21 11 C and 26 67 C Follow the procedure below Unit is factory charged for 15ft 4 57 m of lineset Adjust charge by adding or removing 0 6 oz ft 018 kg m of 3 8 liquid line above or below 15ft 4 57 m respectively For standard refrigerant line lengths 80 ft 24 38 m or less allow system to operate in cooling mode at least 15 minutes If conditions are favorable...

Страница 9: ...unit before adding panels and covers Securely fasten all panels and covers 3 Tighten service valve stem caps to 1 12 turn past finger tight 4 Leave Owner s Manual with owner Explain system operation and periodic maintenance requirements outlined in manual 5 Fill out Dealer Installation Checklist and place in customer file Troubleshooting If the compressor fails to operate with a cooling call the t...

Страница 10: ...erved A Carrier Company Edition Date 03 22 Catalog No GH7T 01SI Replaces New GH7T Installation Instructions Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations 10 ...

Отзывы: