PMSTR-4000                         

Quick Start Tips 

September 15, 2021 

 

 

 

Page 6 

 

 

HOT STANDBY 

If sequencing is used, sensor 2 on the unit can be connected to a shell temperature 
sensor to enable the hot standby feature. Setpoint 2 on the unit is configured to the 
standby setpoint and whenever the sequenced slave disable command is sent, the 
control will override this to maintain the standby water temperature. 

 

Message

 

when

 

sequenced

 

slave

 

is

 

disabled

 

but

 

hot

 

standby

 

is

 

active

 

To enable hot standby: 

SENSOR SETUP 

 SENSOR 2 

 TYPE 

 STANDBY  

SENSOR SETUP 

 SENSOR 2 

 RANGE 

 (choose sensor range) 

SETPOINT SETUP 

 SETPOINT 2 SETUP 

 SENSOR USED 

 2  

Enter the desired setpoint, cut-in, cut-out and PID settings as desired. Note that setpoint 
1 and setpoint 2 each have individual settings. 

 

 