HOT STANDBY
If sequencing is used, sensor 2 on the unit can be connected to a shell temperature
sensor to enable the hot standby feature. Setpoint 2 on the unit is configured to the
standby setpoint and whenever the sequenced slave disable command is sent, the
control will override this to maintain the standby water temperature.
Message
when
sequenced
slave
is
disabled
but
hot
standby
is
active
To enable hot standby:
SENSOR SETUP
SENSOR 2
TYPE
STANDBY
SENSOR SETUP
SENSOR 2
RANGE
(choose sensor range)
SETPOINT SETUP
SETPOINT 2 SETUP
SENSOR USED
2
Enter the desired setpoint, cut-in, cut-out and PID settings as desired. Note that setpoint
1 and setpoint 2 each have individual settings.