background image

 

PMSTR-4000                         

Quick Start Tips 

September 15, 2021 

 

 

 

Page 3 

 

 

USING MODBUS MONITOR TO VERIFY COMMUNICATION STATUS 

A Modbus monitoring program such as ModScan or Shortbus Modbus Scanner can be 
used to check if communication is active. Connect the Ethernet port of the PMSTR-4000 
to a PC and set up a static IP address to match that of the PMSTR-4000. By default, the 
IP address of the PMSTR-4000 is 192.168.0.11, but this can be immediately changed 
from option groups 13 through 15. Set up the PC address to have a different last octet 
from the PMSTR-4000 – an example would be to set the PC static IP address to 
192.168.0.19. 

Use the Modbus monitoring program to read registers 00020 through 00027. These 
indicate the following: 

  00020 – status of unit 1 (0 = no communication, 1 = communication active) 

  00021 – status of unit 2 (0 = no communication, 1 = communication active) 

  00022 – status of unit 3 (0 = no communication, 1 = communication active) 

  00023 – status of unit 4 (0 = no communication, 1 = communication active) 

  00024 – status of unit 5 (0 = no communication, 1 = communication active) 

  00025 – status of unit 6 (0 = no communication, 1 = communication active) 

  00026 – status of unit 7 (0 = no communication, 1 = communication active) 

  00027 – status of unit 8 (0 = no communication, 1 = communication active) 

SENSOR ISSUES 

If the process control sensor (steam or hot water) does not have a valid reading, the 
PMSTR-4000 will override the virtual HAND-OFF-AUTO position of each unit and force 
each into HAND. The PMSTR-4000 does this since it is not possible to control the load 
without a sensor connected. Placing each unit back into HAND allows them to control to 
their local sensor and maintain an output. Since the units will all be in HAND, it will not 
be possible for the units to be ONLINE when there is a sensor issue.

 

 

 

Отзывы: