F96CTN and G96CTN (Series A): Installation, Start-up, Operating, Service and Maintenance Instructions
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
17
A10491
Fig. 25 – Installation on Combustible Flooring
Downflow Installation
NOTE:
The furnace must be pitched as shown in
for proper
condensate drainage.
Supply Air Connections
NOTE:
For downflow applications, this furnace is approved for use on
combustible flooring when any one of the following accessories are
used:
• Special Base, NAHA01101SB
• Cased Coil Assembly Part No. EAM4X, END4X, ENW4X, EAD4X
• Coil Casing model number NAEA
1. Determine application being installed from
.
2. Construct hole in floor per
3. Construct plenum to dimensions specified in
.
4. Install special base coil assembly or coil box as shown in
.
NOTE:
It is recommended that the perforated supply-air duct flanges be
completely removed from furnace when installing the furnace on a
factory-supplied cased coil or coil box. To remove the supply-air duct
flange, use wide duct pliers or hand seamers to bend flange back and
forth until it breaks off. Be careful of sharp edges. See
.
Connect supply-air duct to supply-air outlet on furnace. Bend flange
inward past 90° with wide duct pliers. See
. The supply-air duct
must be connected to ONLY the furnace supply outlet or air conditioning
coil casing (when used). When installed on combustible material,
supply-air duct must be connected to ONLY the factory-approved
accessory subbase, or a factory-approved air conditioning coil casing.
DO NOT cut main furnace casing to attach supply side air duct,
humidifier, or other accessories. All supply-side accessories MUST be
connected to duct external to furnace casing.
Return Air Connections
The return-air duct must be connected to return-air opening (bottom
inlet). DO NOT cut into casing sides (left or right). Bypass humidifier
connections should be made at ductwork or coil casing sides exterior to
furnace. See
Bottom Return Air Inlet
These furnaces are shipped with bottom closure panel installed in bottom
return-air opening. Remove and discard this panel when bottom return
air is used. To remove bottom closure panel, see
Horizontal Installation
NOTE:
The furnace must be pitched forward as shown in
for
proper condensate drainage.
The furnace can be installed horizontally in an attic or crawlspace on
either the left-hand (LH) or right-hand (RH) side. The furnace can be
hung from floor joists, rafters or trusses or installed on a
non-combustible platform, blocks, bricks or pad.
PLENUM
OPENING
C
A
B
D
FLOOR
OPENING
DOWNFLOW
SUBBASE
SHEET METAL
PLENUM
FLOOR
OPENING
FURNACE
(OR COIL CASING
WHEN USED)
COMBUSTIBLE
FLOORING
APPROVED
COIL ASSEMBLY
OR
COIL BOX
FURNACE
SHEET METAL
PLENUM
FLOOR
OPENING
COMBUSTIBLE
FLOORING
CAUTION
!
CUT HAZARD
Failure to follow this caution may result in personal injury.
Sheet metal parts may have sharp edges or burrs. Use care and wear
appropriate protective clothing, safety glasses and gloves when
handling parts, and servicing furnaces.
WARNING
!
FIRE HAZARD
A failure to follow this warning could cause personal injury, death
and/or property damage.
Never connect return-air ducts to the back of the furnace. Follow
instructions below.
WARNING
!
FIRE, EXPLOSION, AND CARBON MONOXIDE
POISONING HAZARD
Failure to follow this warning could result in personal injury, death, or
property damage.
Do not install the furnace on its back or hang furnace with control
compartment facing downward. Safety control operation will be
adversely affected. Never connect return-air ducts to the back of the
furnace.
CAUTION
!
MINOR PROPERTY HAZARD
Failure to follow this caution may result in minor property damage.
Local codes may require a drain pan under entire furnace and
condensate trap when a condensing furnace is used in an attic
application or over a finished ceiling.