4

Fig. 7 — Equipment Control Module Mounting

Fig. 8 — Standoff Installed on Equipment Control 

Module

16. Match and connect equipment wires to proper terminals

of each connector block, being careful not to over tighten

the screws. Correct polarity must be observed when con-

necting the two wires from the equipment control module

to the display module

 

mounting base. If wires are con-

nected incorrectly, the display module will not operate.

See Fig. 9.

17. Snap cover over top of equipment control module. See

Fig. 10.

18. Turn on power to equipment. On power up, all display

segments will light for 5 seconds. For the next 5 seconds,

a 2-digit code will appear on the center of the large dis-

play which identifies the equipment configuration:

AC — Two-stage heat / Two-stage cool
HP — Three-stage heat / Two-stage cool

Fig. 10 — Cover Installed on Equipment Control 

Module

Fig. 9 — Control Module Connector Block Terminals

a33-9169

RELAY

S

OAT

RR

S

S

RTN

HUM

D1
D2
V+

Vg

Rc

Rh
W1

G

Y2

C

O/W2/B

Y1

CONNECT 

TO U

S

ER 

INTERFACE

DRY

CONTACT 

OAT/RR

S

RETURN

JW6

TWI

S

T

OFF

S

EPARATE

RC/RH BY 

BLACK

BREAKING
JW6 ON 
CONTROL 
MODULE
BOARD.

RED

                                 LEGEND

OAT

Outdoor Air Temperature Sensor

RAS

Remote Room Temperature Sensor

a33-9170

a33-9168

a33-9171

Содержание EDGE PRO 33CS2PP2S-01

Страница 1: ...fies the most serious hazards which will result in severe personal injury or death WARNING signifies a haz ard which could result in personal injury or death CAUTION is used to identify unsafe practices which would result in minor personal injury or property damage GENERAL Carrier s 7 day 5 2 day or 1 day programmable commer cial thermostat control is a wall mounted low voltage control which provi...

Страница 2: ... in a frequently used room preferably on an inside wall on a section of wall without pipes or ductwork where temperature operating limits are within 67 to 257 F 55 to 125 C where humidity operating range is within 0 to 95 rela tive humidity non condensing The thermostat should NOT be mounted close to a window on an outside wall or next to a door leading to the outside where exposed to direct light...

Страница 3: ...ole in wall to prevent air leaks Leaks can af fect operation and cause incorrect temperature and or hu midity measurement 11 Attach 2 wire pigtail to display module Pigtail is packed loose in the box from the factory Pigtail is attached to the back of the display module via 2 pin keyed connector 12 Reattach display module body to mounting base by first setting the module on at top of mounting base...

Страница 4: ...ig 10 18 Turn on power to equipment On power up all display segments will light for 5 seconds For the next 5 seconds a 2 digit code will appear on the center of the large dis play which identifies the equipment configuration AC Two stage heat Two stage cool HP Three stage heat Two stage cool Fig 10 Cover Installed on Equipment Control Module Fig 9 Control Module Connector Block Terminals a33 9169 ...

Страница 5: ...r to be connected to it for proper operation The thermostat will not operate without these connections The Rh and Rc terminals are connected via the PCB breakout jumper For applications using a single 24 VAC transformer for power the breakout jumper should remain in tact For applications using two 24 VAC transformers the breakout jumper must be broken because possible voltage dif ferences between ...

Страница 6: ... default is OF off OPTION 08 AUXILIARY HEAT LOCKOUT TEM PERATURE SETTING This selection is available on heat pump systems with a valid outdoor temperature sensor con nected Available settings are Off 5 10 15 20 25 30 35 40 45 50 and 55 When set to OF off the function is disabled Auxiliary heat is allowed to operate whenever sufficient demand for heat is available When set to 5 through 55 F this is...

Страница 7: ...ttons to change to the desired value When set to 2 the dry contact will operate as a DEHUM re lay This option is only available on the 33CS2PPRH 01 mod el There is a 1 4 hysteresis around the dehumidification set point to prevent rapid on off cycling of the DEHUM output When configured for dehumidification the Rc terminal must be connected to one of the dry contact terminals This provides power to...

Страница 8: ...ed the installer will then choose the end date for daylight savings time Fall which will be a month range of 7 to 12 To activate the function the installer changes the 2 by pressing the up button and On is displayed The setting should be left On to enable the Daylight Savings Time func tion Default is On OPTION 32 UNUSED OPTION 33 SINGLE OR TWO PIECE INSTALLA TION This configuration allows the the...

Страница 9: ...te use MODE button to select between HEAT COOL AUTO or EM HEAT to provide desired operation Default Schedule If the programmed schedule is to be used make sure the triangle icon next to the FOLLOW SCHEDULE icon is turned on The default schedule is shown in Table 2 Pressing the Schedule button will cycle the triangle icon through the FOLLOW SCHEDULE HOLD and HOLI DAY selections If fixed temperature...

Страница 10: ...Press the softkey below the dehumidification icon button to bring up dehumidification se lections Dehumidification options are only available when in Cooling mode When system is in AUTO mode dehumidifica tion options are available if the last system operation was a call for cooling If FAN is set for continuous operation Fan On icon dis played then the G output is turned off for 30 seconds at the e...

Страница 11: ...ion func tion For dehumidification control 24 volts is applied from Rc to the dehumidifier through relay contacts D1 and D2 A sepa rate jumper wire is needed between Rc and one dry contact ter minal such as D1 If timed control of the system fan is required the dry con tact can be used for this function For fan control 24 volts is applied from Rh to G through relay contacts D1 and D2 A sep arate ju...

Страница 12: ...X COMMERCIAL THERMOSTAT CONNECTION BOARD TB2 Humidi MiZer FIOP Connection not required TB2 for 48 50HJ015 028 and 48 50TJ TM016 028 units Connection Board for all other units LEGEND FIOP Factory Installed Option FU Fuse LTLO Low Temperature Lockout a33 9174 Rc Rh W W1 G Y Y2 C O W2 B Y1 OAT RRS SRTN HUM D1 D2 V Vg R Y1 Y2 W1 W2 G C X COMMERCIAL THERMOSTAT BASE UNIT CONNECTION BOARD HM OC W2 W1 W2 ...

Страница 13: ...2 V Vg R Y1 Y2 W1 W2 G C X COMMERCIAL THERMOSTAT TB1 TB2 1 2 HUMIDISTAT Humidi MiZer FIOP Connection not required TB1 for 48 50PG03 16 units and TB2 for 48 50PG PM20 28 units and 48 50HG014 028 units a33 9176 Rc Rh W1 G Y2 C O W2 B Y1 OAT RRS SRTN HUM D1 D2 V Vg X C G W2 W1 Y2 Y1 R COMMERCIAL THERMOSTAT COMMAND CENTER Connection not required a33 9177 ...

Страница 14: ...Q024 028 Heat Pump Units Rc Rh W1 G Y2 C O W2 B Y1 OAT RRS SRTN HUM D1 D2 V Vg RC RH W1 W2 Y1 Y2 G C X 11 TB2 COMMERCIAL THERMOSTAT R R ISOLATION RELAY Connection not required a33 9178 Rc Rh W1 G Y2 C O W2 B Y1 OAT RRS SRTN HUM D1 D2 V Vg R W1 W2 C Y1 Y2 G COMMERCIAL THERMOSTAT TB3 a33 9179 ...

Страница 15: ...R Y1 Y2 W1 W2 G C X 8 38ARD012 LLSV 1 IFC COMMERCIAL THERMOSTAT CONNECTION BOARD TB LLSV 2 1 2 3 W1 W2 4 9 5 38ARD014 024 TB2 Connection not required LEGEND IFC Indoor Fan Contactor LLSV Liquid Line Solenoid Valve a33 9180 Rc Rh W1 G Y2 C O W2 B Y1 OAT RRS SRTN HUM D1 D2 V Vg COMMERCIAL THERMOSTAT FAN COIL 40 SERIES CONDENSING UNIT 38 SERIES R G C R C INDOOR UNIT OUTDOOR UNIT a33 9181 ...

Страница 16: ...C PEC PS PSW PT RHC RHE RHR RHS RTG RVC RVE RVR RVS RWS VQL Water Source Heat Pump Units with Deluxe D Controls Rc Rh W1 G Y2 C O W2 B Y1 OAT RRS SRTN HUM D1 D2 V Vg COMMERCIAL THERMOSTAT COMPLETE C P1 Y W O G R C AL1 COMPLETE C P1 SECOND COMPRESSOR Y FIRST COMPRESSOR a33 9182 Rc Rh W1 G Y2 C O W2 B Y1 OAT RRS SRTN HUM D1 D2 V Vg COMMERCIAL THERMOSTAT DELUXE D P1 Y1 R O W2 G W1 C AL1 Y2 a33 9183 ...

Страница 17: ...g 24 Thermostat Wiring Outdoor Air Temperature and Remote Room Temperature Sensors Rc Rh W1 G Y2 C O W2 B Y1 OAT RRS SRTN HUM D1 D2 V Vg COMMERCIAL THERMOSTAT TERMINAL BOARD Y Y2 C O W2 W W1 G R Y1 W2 DELUXE D P2 R H a33 9184 Rc Rh W1 G Y2 C O W2 B Y1 OAT RRS SRTN HUM D1 D2 V Vg OAT SENSOR REMOTE ROOM COMMERCIAL THERMOSTAT SENSOR a33 9185 ...

Страница 18: ...T SENSOR 4 SENSOR 1 SENSOR 1 SENSOR 1 SENSOR 8 SENSOR 7 SENSOR 5 SENSOR 9 SENSOR 6 SENSOR 1 SENSOR 2 SENSOR 3 SPACE TEMPERATURE AVERAGING 9 SENSOR APPLICATION RRS STRN SPACE TEMPERATURE AVERAGING 4 SENSOR APPLICATION SENSOR 1 SENSOR 2 SENSOR 3 SENSOR 4 COMMERCIAL THERMOSTAT RRS STRN a33 9190 ...

Страница 19: ...ol 24 V is provided from the HUM terminal to operate the equipment 4 For dehumidifer control 24 V is applied from Rc to the dehumidifier through relay contacts D1 and D2 a33 9186 Rc Rh W1 G Y2 C O W2 B Y1 OAT RRS SRTN HUM D1 D2 V Vg COMMERCIAL THERMOSTAT HUMIDIFIER NOTES 1 D1 and D2 can be used independently for equipment requiring a dry contact 2 If humidifier has its own low voltage power supply...

Страница 20: ...ht to discontinue or change at any time specifications or designs without notice and without incurring obligations Catalog No 04 53330010 01 Printed in U S A Form 33CS 65SI Pg 20 8 08 Replaces New Copyright 2008 Carrier Corporation ...

Страница 21: ......

Страница 22: ......

Страница 23: ......

Страница 24: ...ter Reminder Option 03 _____ Fahrenheit Centigrade Selection Option 04 _____ Fan G on with W W1 Selection Option 05 _____ Space Temperature Sensing Option 06 _____ Cooling Lockout Option 07 _____ Equipment DDC Controller Option 08 _____ Auxiliary Heat Lockout Temperature Setting only available when heat pump is used and when outdoor air temperature sensor is present Option 09 Unused Option 10 ____...

Отзывы: