Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
PC 903
Catalog No. 533-00053
Printed in U.S.A.
Form 30GXN,GXR-3SI
Pg 1
6-03
Replaces: 30GXN,GXR-2SI
Book 2
Tab
5c
Installation Instructions
CONTENTS
Page
SAFETY CONSIDERATIONS
. . . . . . . . . . . . . . . . . . . . . . 1
INTRODUCTION
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
INSTALLATION
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-72
Step 1 — Inspect Shipment
. . . . . . . . . . . . . . . . . . . . . . 1
Step 2 — Rig and Place Unit
. . . . . . . . . . . . . . . . . . . . . 1
Step 3 — Piping Connections
. . . . . . . . . . . . . . . . . . . 44
• GENERAL
• DUPLEX UNIT PIPING CONNECTIONS
• COOLER FLUID, VENT, AND DRAIN
• BRINE UNITS
• WATER TREATMENT
• PREPARATION FOR YEAR-ROUND OPERATION
• WINTER SHUTDOWN PREPARATION
Step 4 — Make Electrical Connections
. . . . . . . . . . 50
• FIELD POWER CONNECTIONS
• FIELD CONTROL POWER CONNECTIONS
• DUPLEX UNIT POWER CONNECTIONS
• COMFORTLINK™ COMMUNICATION
WIRING
Duplex Chiller Control Configuration
. . . . . . . . . . . . 53
Step 5 — Install Accessories
. . . . . . . . . . . . . . . . . . . . 72
• ELECTRICAL
• LOW-AMBIENT OPERATION
• MINIMUM LOAD ACCESSORY
• MISCELLANEOUS ACCESSORIES
Step 6 — Leak Test Unit
. . . . . . . . . . . . . . . . . . . . . . . . . 72
Step 7 — Refrigerant Charge
. . . . . . . . . . . . . . . . . . . . 72
SAFETY CONSIDERATIONS
Installing, starting up, and servicing this equipment can
be hazardous due to system pressures, electrical components,
and equipment location. Only trained, qualified installers and
service mechanics should install, start up, and service this
equipment.
When working on the equipment, observe precautions in the
literature, and on tags, stickers, and labels attached to the
equipment.
• Follow all safety codes.
• Wear safety glasses and work gloves.
• Use care in handling, rigging, and setting bulky equipment.
INTRODUCTION
These instructions cover installation of 30GXN,R080-528
liquid chillers with electronic controls and units with
factory-installed options (FIOPs).
INSTALLATION
Step 1 — Inspect Shipment —
Inspect unit for dam-
age upon arrival. If damage is found, immediately file a claim
with the shipping company. When considering location for the
unit, be sure to consult NEC (National Electrical Code, U.S.A.)
and/or local code requirements. Allow sufficient space for air-
flow, wiring, piping, and service as follows.
Front and Rear . . . 6 ft (1829 mm); from outer most edge*
Top . . . . . . . . . . . . . . . . . . . . . . . Do not restrict in any way
Ends . . . . . . . . . . . . 5 ft (1524 mm); from outer most edge*
*Outer most edge may include sound enclosure or hail
guard.
See Fig. 1-25 for unit dimensions and Table 1 for duplex
unit combinations. Ensure surface beneath unit is level and
capable of supporting the operating weight of the unit. See
Fig. 26-28 and Tables 2A-2D for unit mounting and operating
weights. Unit operating ranges are listed in Tables 3A and 3B.
Step 2 — Rig and Place Unit —
These units are de-
signed for overhead rigging and it is important that this method
be used. See Fig. 28 or rigging label on unit. Holes are provid-
ed in frame baserails; field-supplied 2-in. Schedule 40 pipes
pass through these holes, extending beyond frame far enough
to attach cables or chains on both sides.
As shown in Fig. 28, use the recommended length of chain
or cable to facilitate lifting of the unit. Two options have been
provided for the rigging of these units.
Rigging option 1 uses a central rigging point. The lifting
point must be a minimum of 13 ft (3.9 m) above the top of the
unit. For a more level lift, the chains or cables of the cooler/
compressor side must be shortened by about 20 in. (508 mm).
Use spreader bars to keep cables or chains clear of unit sides.
As further protection for the coil faces, leave plywood sheets
supplied for shipping in place against sides of unit, behind
cables or chains. Option 1 must be used for 30GXN,R204-350,
and applicable modular units.
ELECTRIC SHOCK HAZARD
To avoid the possibility of electrical shock,
open and tag all disconnects before install-
ing this equipment.
IMPORTANT: This equipment generates, uses, and can
radiate radio frequency energy. If not installed and used
in accordance with these instructions, this equipment
may cause radio interference. The equipment has been test-
ed and found to comply with the limits of a Class A
computing device as defined by the FCC (Federal Commu-
nications Commission, U.S.A.) Regulations, Subpart J of
Part 15, which are designed to provide reasonable protec-
tion against such interference when operated in a commer-
cial environment.
IMPORTANT: Rigging option 1 must be used for
30GXN,R204-350 and associated modular units. Sizes
080-178 and associated modular units may use either rig-
ging option 1 or 2.
30GXN,R080-528
ECOLOGIC™ Air-Cooled Chillers
60 Hz
Содержание ECOLOGIC 30GXN
Страница 3: ...3 Fig 1 Dimensions 30GXN R080 090 Cast iron Steel ...
Страница 4: ...4 Fig 2 Dimensions 30GXN R083 093 106 108 114 125 135 Cast iron Steel ...
Страница 5: ...5 Fig 3 Dimensions 30GXN R118 128 138 150 160 Cast iron Steel ...
Страница 6: ...6 Fig 4 Dimensions 30GXN R153 174 Cast iron Steel ...
Страница 7: ...7 Fig 5 Dimensions 30GXN R163 178 Cast iron Steel ...
Страница 8: ...8 Fig 6 Dimensions 30GXN R204 225 Cast iron Steel ...
Страница 9: ...9 Fig 7 Dimensions 30GXN R208 228 Cast iron Steel ...
Страница 10: ...10 Fig 8 Dimensions 30GXN R249 264 Cast iron Steel ...
Страница 11: ...11 Fig 9 Dimensions 30GXN R253 268 Cast iron Steel ...
Страница 12: ...12 Fig 10 Dimensions 30GXN R281 301 325 350 Cast iron Steel ...
Страница 13: ...13 Fig 11 Dimensions 30GXN R283 ...
Страница 14: ...14 Fig 12 Dimensions 30GXN R303 ...
Страница 15: ...15 Fig 13 Dimensions 30GXN R328 ...
Страница 16: ...16 Fig 14 Dimensions 30GXN R353 ...
Страница 17: ...17 Fig 15 Dimensions 30GXN R370 ...
Страница 18: ...18 Fig 16 Dimensions 30GXN R373 ...
Страница 19: ...19 Fig 17 Dimensions 30GXN R390 ...
Страница 20: ...20 Fig 18 Dimensions 30GXN R393 418 ...
Страница 21: ...21 Fig 19 Dimensions 30GXN R415 ...
Страница 22: ...22 Fig 20 Dimensions 30GXN R450 ...
Страница 23: ...23 Fig 21 Dimensions 30GXN R453 ...
Страница 24: ...24 Fig 22 Dimensions 30GXN R475 ...
Страница 25: ...25 Fig 23 Dimensions 30GXN R478 ...
Страница 26: ...26 Fig 24 Dimensions 30GXN R500 525 ...
Страница 27: ...27 Fig 25 Dimensions 30GXN R503 528 ...
Страница 73: ......