45
Table 5 — Flexible Coupling Alignment
BRINE UNITS — Special factory modifications to the units
are required to allow them to operate at fluid temperatures less
than 34 F (1.1 C). Be sure that the fluid has sufficient inhibited
glycol or other suitable corrosion-resistant antifreeze solution
to prevent cooler freeze-up.
WATER TREATMENT — Fill the fluid loop with water (or
brine) and a corrosion-resistant inhibitor suitable for the water
of the area. Consult the local water treatment specialist for
characteristics of system water and a recommended inhibitor
for the cooler fluid loop. It is recommended that once the
cooler water lines have been installed and leak checked that the
cooler heads be insulated with a suitable thickness of closed-
cell insulation. This will minimize the amount of condensation
that will form on the cooler heads.
PREPARATION FOR YEAR-ROUND OPERATION — In
areas where the piping or unit is exposed to 32 F (0
°
C) or low-
er ambient temperatures, freeze-up protection is required using
inhibited glycol or other suitable corrosion-resistant antifreeze
solution and electric heater tapes. Heater tapes on piping
should have a rating for area ambient temperatures and be cov-
ered with a suitable thickness of closed-cell insulation. Route
power for the heater tapes from a separately fused disconnect.
Mount the disconnect within sight from the unit per local or
NEC codes. Identify disconnect as heater tape power source
with warning that power must not be turned off except when
servicing unit.
A drain connection is located at the bottom of the cooler
head. See Fig. 1-25 and 34 for connection location. Install shut-
off valves to the drain line before filling the system with fluid.
WINTER SHUTDOWN PREPARATION — At the end of
each cooling season the fluid should be drained from the sys-
tem. However, due to the cooler circuiting, some fluid will re-
main in the cooler after draining. To prevent freeze-up damage
to the cooler tubes perform the following procedure.
1. If factory-installed cooler heaters have been installed,
deenergize the heaters to prevent damage and possible
safety hazards when draining, or when there is no liquid
in the system. Remove Fuse 1 to deenergize heaters.
Drain the fluid from the system.
2. Isolate the cooler from the rest of the system with
water shut-off valves.
3. Completely fill the cooler with an appropriate amount
of inhibited glycol solution (or other suitable
corrosion-inhibitive antifreeze) for 15
°
F (8.3
°
C)
below the expected low ambient conditions, 5 gallons
(19 L) minimum.
4. Leave the cooler filled with the antifreeze solution for
the winter, or drain if desired. Be sure to deenergize
heaters (if installed) as explained in Step 1 to prevent
damage. Use an approved method of disposal when
removing antifreeze solution.
MODEL
PIPE SIZE
in. (mm)
LENGTH
in. (mm)
MAX. PARALLEL
OFFSET
in. (mm)
MAX.
ELONGATION
in. (mm)
MAX.
COMPRESSION
in. (mm)
CONNECTION
STYLE
MAX. WORKING
PRESSURE
PSI
Flex-Hose SVG8
8 (219)
16 (406)
0.5 (13)
0
0
Victaulic/Varies
155
Unaflex Style 1000
8 (219)
6 (152)
1 (25)
0.75 (19)
1.75 (44)
Flange
150
IMPORTANT: Adding antifreeze solution is the only cer-
tain means of protecting the unit from freeze-up if heater
fails or electrical power is interrupted or lost while tempera-
tures are below 32 F (0° C).
IMPORTANT: Before starting the unit, be sure all of the air
has been purged from the system.
COUPLING
NOZZLE CONNECTIONS
Fig. 29 — Victaulic Flange
Fig. 30 — Flow Sensor Coupling, Victaulic Flange
Fig. 31 — Victaulic Flange Connection Locations
Содержание ECOLOGIC 30GXN
Страница 3: ...3 Fig 1 Dimensions 30GXN R080 090 Cast iron Steel ...
Страница 4: ...4 Fig 2 Dimensions 30GXN R083 093 106 108 114 125 135 Cast iron Steel ...
Страница 5: ...5 Fig 3 Dimensions 30GXN R118 128 138 150 160 Cast iron Steel ...
Страница 6: ...6 Fig 4 Dimensions 30GXN R153 174 Cast iron Steel ...
Страница 7: ...7 Fig 5 Dimensions 30GXN R163 178 Cast iron Steel ...
Страница 8: ...8 Fig 6 Dimensions 30GXN R204 225 Cast iron Steel ...
Страница 9: ...9 Fig 7 Dimensions 30GXN R208 228 Cast iron Steel ...
Страница 10: ...10 Fig 8 Dimensions 30GXN R249 264 Cast iron Steel ...
Страница 11: ...11 Fig 9 Dimensions 30GXN R253 268 Cast iron Steel ...
Страница 12: ...12 Fig 10 Dimensions 30GXN R281 301 325 350 Cast iron Steel ...
Страница 13: ...13 Fig 11 Dimensions 30GXN R283 ...
Страница 14: ...14 Fig 12 Dimensions 30GXN R303 ...
Страница 15: ...15 Fig 13 Dimensions 30GXN R328 ...
Страница 16: ...16 Fig 14 Dimensions 30GXN R353 ...
Страница 17: ...17 Fig 15 Dimensions 30GXN R370 ...
Страница 18: ...18 Fig 16 Dimensions 30GXN R373 ...
Страница 19: ...19 Fig 17 Dimensions 30GXN R390 ...
Страница 20: ...20 Fig 18 Dimensions 30GXN R393 418 ...
Страница 21: ...21 Fig 19 Dimensions 30GXN R415 ...
Страница 22: ...22 Fig 20 Dimensions 30GXN R450 ...
Страница 23: ...23 Fig 21 Dimensions 30GXN R453 ...
Страница 24: ...24 Fig 22 Dimensions 30GXN R475 ...
Страница 25: ...25 Fig 23 Dimensions 30GXN R478 ...
Страница 26: ...26 Fig 24 Dimensions 30GXN R500 525 ...
Страница 27: ...27 Fig 25 Dimensions 30GXN R503 528 ...
Страница 73: ......