Table 3B — Duplex Unit Operating Range
Step 3 — Piping Connections —
See Fig. 29-35 for
piping applications.
GENERAL — The factory-installed victaulic connections al-
low clamp-on connection of water lines to the coolers in all
30GXN,R units. See Tables 4 and 5 for proper piping align-
ment with the victaulic flanges. Each unit is shipped with
2 flange assemblies (Fig. 29) with integral nozzles, 2 gaskets
(located in control box) and one flow sensor. See Fig. 30. The
flow sensor is factory-installed in the side of the entering fluid
nozzle.
DUPLEX UNIT PIPING CONNECTIONS — The 30GXN,R
duplex units require a field piping connection between the two
modules. All duplex 30GXN,R chillers have standard 8 in.
(219.1 mm) diameter pipe connections. Victaulic style grooved
pipe fittings are recommended for the interconnecting piping to
ensure no weld slag enters the cooler. A flexible coupling
(Braided Stainless Flex Hose SVG8 or Butyl Rubber Unaflex
Style 1000 or similar) is required between the two modules.
See Fig. 11-25. Tables 4 and 5 provide alignment criteria for
the Victaulic and Flex-Hose couplings. Piping details for use
with the Duplex Trim Kit are shown on the Typical Duplex
Connection Piping diagram in Fig. 32B and 33.
COOLER FLUID, VENT, AND DRAIN — The inlet (re-
turn) fluid connection is always the lower of the 2 cooler con-
nections. See Fig. 1-25 for locations. A screen strainer with a
minimum size of 20 mesh must be installed ahead of the cooler
inlet to prevent debris from damaging internal tubes of the
cooler. Outlet (supply) fluid connection is the upper connection
of the 2 cooler connections.
The cooler has victaulic connections to connect the field-
supplied piping. Plan the piping arrangement in accordance
with good piping practices and so that the piping does not cross
in front of the cooler head. Use flexible connections on cooler
piping to reduce vibration transmission. Offset the piping to
permit removal of the cooler head for maintenance. Install
pipe hangers where needed. Make sure no weight or stress is
placed on the water nozzle.
Standard piping alignment criteria is shown in Tables 4
and 5.
Provide openings in fluid piping for pressure gages and
thermometers (if used). These openings should be 5 to 10 pipe
diameters from the unit leaving water nozzle. For thorough
mixing and temperature stabilization, wells in the leaving fluid
pipe should extend at least 2 in. (50 mm) into the pipe.
Although cooler has an air vent, it is recommended that a
field-supplied air vent be installed in the system to facilitate
servicing. Field-supplied shut-off and balancing valves should
also be installed to facilitate servicing and flow balancing. Lo-
cate valves in return and supply fluid lines as close to the chill-
er as possible. Locate air vent at highest point of the cooler
fluid system. See Fig. 32A and 32B.
Provide drain connections at all low points to permit com-
plete drainage of the system.
A thermal flow sensor is factory installed in the entering
fluid nozzle. The sensor is factory wired. If a cooler pump in-
terlock is used, connect the interlock to terminals TB5-1, 2.
The factory-installed flow sensor and cooler interlock must be
wired in series.
Table 4 — Victaulic Connection Alignment
30GXN,R
COOLER
NO. OF
PASSES
MAX. COOLER TEMPERATURE
DIFFERENCE
REFERENCE
MIN FLOW RATE
NOMINAL
FLOW RATE
F
C
Gpm
L/s
Gpm
L/s
283
STD
1
20
11.1
329
20.8
658
41.5
303
STD
1
20
11.1
347
21.9
694
43.8
328
STD
1
20
11.1
382
24.1
764
48.2
353
STD
1
20
11.1
420
26.5
839
53.0
370
STD
1
20
11.1
502
31.7
879
55.5
373
STD
1
20
11.1
444
28.0
889
56.1
390
STD
1
20
11.1
588
37.1
909
57.3
393
STD
1
20
11.1
461
29.1
921
58.1
415
STD
1
20
11.1
588
37.1
974
61.4
418
STD
1
20
11.1
475
30.0
950
59.9
450
STD
1
20
11.1
502
31.7
1031
65.0
453
STD
1
20
11.1
512
32.3
1025
64.7
475
STD
1
20
11.1
542
34.2
1085
68.4
478
STD
1
20
11.1
546
34.4
1091
68.8
500
STD
1
20
11.1
571
36.0
1141
72.0
503
STD
1
20
11.1
579
36.5
1158
73.0
525
STD
1
20
11.1
601
37.9
1202
75.8
528
STD
1
20
11.1
607
38.3
1214
76.6
Remove chilled water flow switch, entering and leaving
water thermistors before welding connecting piping. Rein-
stall flow switch and thermistors after welding is complete.
Failure to remove these devices may cause unit damage.
IMPORTANT: Installation of a cooler pump interlock is
recommended to aid in preventing potential system dam-
age due to loss of fluid flow. Install on TB5-1 to TB5-2 and
connect pump interlock. See Field Control Power Connec-
tions section.
PIPE SIZE NOM. in.
(ACTUAL mm)
PIPE END SEPARATION
in. (mm)
PIPE ALIGNMENT
in./Ft (mm/m)
8 (219.1)
0-0.13 (0-3.2)
0.27 (21)
Содержание ECOLOGIC 30GXN
Страница 3: ...3 Fig 1 Dimensions 30GXN R080 090 Cast iron Steel ...
Страница 4: ...4 Fig 2 Dimensions 30GXN R083 093 106 108 114 125 135 Cast iron Steel ...
Страница 5: ...5 Fig 3 Dimensions 30GXN R118 128 138 150 160 Cast iron Steel ...
Страница 6: ...6 Fig 4 Dimensions 30GXN R153 174 Cast iron Steel ...
Страница 7: ...7 Fig 5 Dimensions 30GXN R163 178 Cast iron Steel ...
Страница 8: ...8 Fig 6 Dimensions 30GXN R204 225 Cast iron Steel ...
Страница 9: ...9 Fig 7 Dimensions 30GXN R208 228 Cast iron Steel ...
Страница 10: ...10 Fig 8 Dimensions 30GXN R249 264 Cast iron Steel ...
Страница 11: ...11 Fig 9 Dimensions 30GXN R253 268 Cast iron Steel ...
Страница 12: ...12 Fig 10 Dimensions 30GXN R281 301 325 350 Cast iron Steel ...
Страница 13: ...13 Fig 11 Dimensions 30GXN R283 ...
Страница 14: ...14 Fig 12 Dimensions 30GXN R303 ...
Страница 15: ...15 Fig 13 Dimensions 30GXN R328 ...
Страница 16: ...16 Fig 14 Dimensions 30GXN R353 ...
Страница 17: ...17 Fig 15 Dimensions 30GXN R370 ...
Страница 18: ...18 Fig 16 Dimensions 30GXN R373 ...
Страница 19: ...19 Fig 17 Dimensions 30GXN R390 ...
Страница 20: ...20 Fig 18 Dimensions 30GXN R393 418 ...
Страница 21: ...21 Fig 19 Dimensions 30GXN R415 ...
Страница 22: ...22 Fig 20 Dimensions 30GXN R450 ...
Страница 23: ...23 Fig 21 Dimensions 30GXN R453 ...
Страница 24: ...24 Fig 22 Dimensions 30GXN R475 ...
Страница 25: ...25 Fig 23 Dimensions 30GXN R478 ...
Страница 26: ...26 Fig 24 Dimensions 30GXN R500 525 ...
Страница 27: ...27 Fig 25 Dimensions 30GXN R503 528 ...
Страница 73: ......