Step 4 — Make Electrical Connections —
The
electrical characteristics of the available power supply must
agree with the unit nameplate rating. Supply voltage must be
within the limits shown. Refer to Tables 6-9 for electrical and
configuration data.
FIELD POWER CONNECTIONS (See Fig. 35 and 37) — All
power wiring must comply with applicable local and national
codes. Install field-supplied, branch circuit fused disconnect(s)
of a type that can be locked off or open. Disconnect(s) must be
located within sight and readily accessible from the unit in com-
pliance with NEC Article 440-14 (U.S.A.). See Tables 7A-7E
for unit electrical data. See Tables 8A and 8B for compressor
electrical data. See Table 9 for Condenser Fan Electrical data.
Maximum wire size that the unit terminal block or non-
fused disconnect will accept is 500 kcmil.
The 30GXN,R units require 1 or 2 power supplies, depend-
ing on the unit and circuit voltage. See Tables 7A and 7E for
the number of power supplies and conductors required for each
unit.
National Electric Code requires all conduits from the condi-
tioned space to the control box to be sealed to prevent the flow
of air and moisture into the control box.
FIELD CONTROL POWER CONNECTIONS (See Fig. 38)
— Units with a power supply of 208/230-, 460-, and 575-3-60
require 115-1-60 control circuit power. Units with a 380-3-60
power supply require 230-1-60 control circuit power.
For units with 380-3-60 power: Control voltage is tapped
from line to neutral. No additional power supply is required. If
a separate power source is required, disconnect the wires be-
tween the control and power terminal blocks.
Terminals TB5-1 and TB5-2 are provided for field installa-
tion of a chilled water (fluid) pump interlock (CWPI). Chilled
water (fluid) flow sensor (CWFS) is factory installed. These
devices are to be installed in series. Contacts must be capable
of handling a 24-vac at 50 mA load.
Accessory remote on-off switch can be wired into TB5-13
and TB5-14. To use this feature, remove the factory-installed
jumper and install the device in series. See Fig. 38. Contacts
must be capable of handling a 24-vac at 50 mA.
Terminals TB5-10 and TB5-12 are provided for a field-
supplied chilled water (fluid) pump relay (CWP). A field-
supplied control relay of appropriate voltage must be provided.
Maximum load allowed is 75 va at either 115 or 230 v control
power. See Fig. 38.
IMPORTANT: The 30GXN,R units have a factory-installed
option available for a non-fused disconnect for unit power
supply. If the unit is equipped with this option, all field
power wiring should be made to the non-fused disconnect
since no terminal blocks are supplied.
Do not use interlocks or other safety device contacts con-
nected between TB5-13 and TB5-14 as remote on-off. Con-
nection of safeties or other interlocks between these 2
terminals will result in an electrical bypass if the ENABLE-
OFF-REMOTE contact switch is in the ENABLE position.
If remote on-off unit control is required, a field-supplied
relay must be installed in the unit control box and wired as
shown in Fig. 38. Failure to wire the remote on-off as rec-
ommended will result in tube freeze damage.
Fig. 36 — Field Power Wiring — 30GXN,R080-178 and Associated Modular Sizes
Содержание ECOLOGIC 30GXN
Страница 3: ...3 Fig 1 Dimensions 30GXN R080 090 Cast iron Steel ...
Страница 4: ...4 Fig 2 Dimensions 30GXN R083 093 106 108 114 125 135 Cast iron Steel ...
Страница 5: ...5 Fig 3 Dimensions 30GXN R118 128 138 150 160 Cast iron Steel ...
Страница 6: ...6 Fig 4 Dimensions 30GXN R153 174 Cast iron Steel ...
Страница 7: ...7 Fig 5 Dimensions 30GXN R163 178 Cast iron Steel ...
Страница 8: ...8 Fig 6 Dimensions 30GXN R204 225 Cast iron Steel ...
Страница 9: ...9 Fig 7 Dimensions 30GXN R208 228 Cast iron Steel ...
Страница 10: ...10 Fig 8 Dimensions 30GXN R249 264 Cast iron Steel ...
Страница 11: ...11 Fig 9 Dimensions 30GXN R253 268 Cast iron Steel ...
Страница 12: ...12 Fig 10 Dimensions 30GXN R281 301 325 350 Cast iron Steel ...
Страница 13: ...13 Fig 11 Dimensions 30GXN R283 ...
Страница 14: ...14 Fig 12 Dimensions 30GXN R303 ...
Страница 15: ...15 Fig 13 Dimensions 30GXN R328 ...
Страница 16: ...16 Fig 14 Dimensions 30GXN R353 ...
Страница 17: ...17 Fig 15 Dimensions 30GXN R370 ...
Страница 18: ...18 Fig 16 Dimensions 30GXN R373 ...
Страница 19: ...19 Fig 17 Dimensions 30GXN R390 ...
Страница 20: ...20 Fig 18 Dimensions 30GXN R393 418 ...
Страница 21: ...21 Fig 19 Dimensions 30GXN R415 ...
Страница 22: ...22 Fig 20 Dimensions 30GXN R450 ...
Страница 23: ...23 Fig 21 Dimensions 30GXN R453 ...
Страница 24: ...24 Fig 22 Dimensions 30GXN R475 ...
Страница 25: ...25 Fig 23 Dimensions 30GXN R478 ...
Страница 26: ...26 Fig 24 Dimensions 30GXN R500 525 ...
Страница 27: ...27 Fig 25 Dimensions 30GXN R503 528 ...
Страница 73: ......