19
SELECT LOCATION FOR AIR CLEANER
UNIT DIMENSIONS.
DIRECTION OF AIR FLOW THROUGH THE AIR CLEANER
Remember to select a location that is readily accessible for periodic
inspection and cleaning of this air cleaner. Allow a minimum of 24"
clearance in front and 12" clearance above the air cleaner for component
removal and service space. For complete dimensions required refer to the
section entitled
This air cleaner is set up for left to right air flow when you are facing the
access door.
For right to left air flow, follow these directions:
1. Remove the prefilter(s) and cells from the
cabinet. A plastic positioning spacer is
located inside the bottom of the cabinet.
This spacer is secured to the cabinet using
a #6-32 round head Phillips drive thread
cutting screw to assure installation of the
cells in the proper position with respect
to air flow (Figure 6).
2. Remove the screw and reposition the
spacer in the alternate hole at the bottom of
the cabinet.
3. Replace the screw to insure the plastic spacer is not accidentally
knocked out of place during normal maintenance. It must be installed in
the hole provided closest to the air leaving side of the cabinet. Seal the
unused hole with duct tape.
4. Remove the cell handle and reattach to the opposite end of the cell. Turn
cells around, replace in cabinet and replace prefilters on the air
entering side. The directional arrows on the cell end plates must point in
the direction of air flow.