Accessory usage guideline

 

* For tubing line sets between 50 and 175 ft and/or 20 ft elevation difference between indoor and outdoor units, refer to the Application Guideline and Service Man-

ual—Air Conditioners and Heat Pumps Using Puron® Refrigerant.

† Required for all applications.

 

Accessory description and usage (Listed alphabetically)

 

1. Coastal Filter

 

A mesh screen inserted under the top cover and inside the base pan to protect the condenser coil from salt damage without restricting airflow.

SUGGESTED USE: In geographic areas where salt damage could occur.

 

2. Compressor Start Assist — Capacitor and Relay

 

Start capacitor and start relay gives hard boost to compressor motor at each start-up.

SUGGESTED USE: Installations where interconnecting tube length exceeds 50 ft.

Installations where outdoor design temperature exceeds 105°F (40.6°C).
Units installed with Low-Ambient Pressure Switch.

 

3. Compressor Start Assist — PTC Type

 

Solid state electrical device which gives a soft boost to the reciprocating compressor at each start-up.

SUGGESTED USE: Installations with marginal power supply.

 

4. Crankcase Heater

 

An electric resistance heater which mounts to the base of the compressor to keep the lubricant warm during off cycles. Improves compressor lubrication on restart and minimizes chance 
of refrigerant slugging. May or may not include a thermostat control.

SUGGESTED USE: When interconnecting tube length exceeds 50 ft.

When unit will be operated below 55°F (12.8°C) outdoor air temperature. (Use with Low-Ambient Pressure Switch.)
All commercial installations.

 

5. Evaporator Freeze Thermostat

 

An SPST temperature actuated switch which stops unit operation when evaporator reaches freeze-up conditions.

SUGGESTED USE: All units to which Low-Ambient Pressure Switch has been added.

 

6. Filter Drier— Suction Line

 

A device for removing contaminants from refrigerant circulating in a heat pump system; 2-direction flow for heat pumps.

SUGGESTED USE: Split-system heat pumps.

 

7. Isolation Relay

 

An SPDT relay which switches the Low-Ambient Controller out of the outdoor fan motor circuit when the heat pump switches to heating mode.

SUGGESTED USE: All heat pumps where Low-Ambient Pressure Switch has been added.

 

8. Liquid-Line Solenoid Valve (LSV)

 

An electrically operated shutoff valve to be installed at the outdoor unit and which stops and starts refrigerant liquid flow in response to compressor operation. Maintains a column of 
refrigerant liquid ready for action at next compressor operation cycle.

SUGGESTED USE: In long-line applications. (Refer to the Residential Split-System Long-Line Application Guideline and Service Manual.)

 

9. Low-Ambient Pressure Switch

 

A long life pressure switch which is mounted to outdoor unit service valve. It is designed to cycle the outdoor fan motor in order to maintain head pressure within normal operating 
limits (approximately 200 psig to 365 psig). The control will maintain working head pressure at low-ambient temperatures down to 0°F (–17.8°C) when properly installed.

SUGGESTED USE: Cooling operation at outdoor temperatures below 55°F (12.8°C).

 

10. Outdoor Air Temperature Sensor

 

A device that allows the temperature at a remote location (outdoors) to be displayed at the thermostat.

SUGGESTED USE: All Carrier programmable thermostats.

 

11. Outdoor Thermostat

 

An SPDT temperature actuated switch which turns on supplemental electric heaters when outdoor air temperature drops below set point.

SUGGESTED USE: Heat pump installations with multiple-stage supplemental heaters.

 

12. Pressure Guard™ Kit

 

A pressure-switch kit that cycles the outdoor fan to limit the heating head pressure below a pre-determined pressure setting.

SUGGESTED USE: Some local codes may require limiting the heating head pressure in the vapor line in some applications.

 

13. Secondary Outdoor Thermostat

 

An SPDT temperature actuated switch which turns on third stage of supplemental electric heaters when outdoor air temperature drops below the second-stage set point.

SUGGESTED USE: Some local codes may require limiting the heating head pressure in the vapor line in some applications.

 

14. Snow Stand

 

Coated wire rack which supports unit 18 in. above mounting pad to allow for drainage from unit base.

SUGGESTED USE: Heat pump installations in heavy snowfall areas.

Heat pump installations in snowdrift locations.
Heat pump installations in areas of prolonged subfreezing temperatures.
All commercial installations.

 

ACCESSORY

REQUIRED FOR LOW-AMBIENT

APPLICATIONS

(BELOW 55°F)

REQUIRED FOR LONG-LINE

APPLICATIONS*

(OVER 50 FT)

Crankcase Heater

 

Yes

Yes

 

Evaporator Freeze Thermostat

 

Yes

No

 

Compressor Start Assist — Capacitor and Relay

 

Yes

Yes

 

Puron Low Ambient Pressure Switch

 

Yes

No

 

Wind Baffle

 

See Low-Ambient

Pressure Switch Instructions

No

 

Support Feet

 

Recommended

No

 

Puron Hard Shutoff TXV

 

Yes†

Yes†

 

Puron Liquid-Line Solenoid Valve for Heating

 

No

See Long-Line

Application Guideline

Содержание Deluxe 38YZA

Страница 1: ...ential Second thanks to the performance advantage of Puron refrigerant the 38YZA is extremely efficient In fact the 38YZA features some of the lowest energy usages of single speed heat pumps available from Carrier Maximum performance and efficiency are made possible through the use of the FX4A and FV4A fan coils Custom Made for applications with Puron refrigerant Third the cost of service will pot...

Страница 2: ...tch Quiet Shift defrost mode which if selected maintains extremely quiet operation during defrost Thermostatic Expansion Valve TXV This unit must be installed with a Puron refrigerant TXV on the indoor coil The FX4 and FV4 indoor fan coils come factory equipped with a bi flow Puron refrigerant TXV When installed in this application no further change is required If any other indoor fan coil or furn...

Страница 3: ...2 18 18 12 12 18 18 18 18 Fins per In 25 25 25 25 20 20 20 Rows 1 1 1 1 2 2 2 Circuits 2 2 2 4 3 4 5 VALVE CONNECTION In ID Sweat Vapor 5 8 5 8 3 4 3 4 7 8 7 8 7 8 Liquid 3 8 UNIT SIZE LIQUID TUBE DIAMETER IN VAPOR TUBE DIAMETER IN 0 to 50 Ft Tube Length Alternate 0 to 50 Ft Tube Length Alternate 018 3 8 3 8 5 8 5 8 024 3 8 3 8 5 8 3 4 030 036 3 8 3 8 3 4 5 8 7 8 042 048 3 8 3 8 7 8 3 4 060 3 8 3 ...

Страница 4: ...8 030 KSATX0301PUR Bi Flow TXV Hard Shutoff Sizes 036 042 KSATX0401PUR Bi Flow TXV Hard Shutoff Size 048 KSATX0501PUR Bi Flow TXV Hard Shutoff Size 060 KHAPG0101PGS Pressure Guard Kit Sizes 018 024 042 and 048 KHAPG0201PGS Pressure Guard Kit Sizes 030 036 and 060 KH45LG140 RCD Filter Drier Suction Line Sizes 018 036 KH45LG141 RCD Filter Drier Suction Line Sizes 042 060 KHALS0401LLS Liquid Line Sol...

Страница 5: ... refrigerant liquid flow in response to compressor operation Maintains a column of refrigerant liquid ready for action at next compressor operation cycle SUGGESTED USE In long line applications Refer to the Residential Split System Long Line Application Guideline and Service Manual 9 Low Ambient Pressure Switch A long life pressure switch which is mounted to outdoor unit service valve It is design...

Страница 6: ... NEC ANSI NFPA 70 The ampacity of nonmetallic sheathed cable NM trade name ROMEX shall be that of 60 C 140 F conductors per the NEC ANSI NFPA 70 Article 336 26 If other than uncoated non plated 60 or 75 C 140 or 167 F insulation copper wire solid wire for 10 AWG and smaller stranded wire for larger than 10 AWG is used consult applicable tables of the NEC ANSI NFPA 70 NOTE Control circuit is 24v on...

Страница 7: ...mum outdoor operating ambient in heating mode is 66 F 3 Series designation is the 13th position of the unit model number 4 Center of gravity 5 NOTES DIMENSIONS IN UNIT SIZE SERIES UNIT DIMENSIONS MINIMUM MOUNTING PAD DIMENSIONS A B C D E F G H J K L M Support Feet Snow Stand 018 024 1 2 33 13 16 22 1 2 27 1 2 2 13 16 6 15 16 21 1 2 27 7 8 5 8 8 3 16 12 13 3 4 12 20 x 27 24 x 28 030 1 2 27 13 16 30...

Страница 8: ...inted in U S A OUTDOOR TEMPERATURE F 10 0 10 20 30 40 50 60 70 80 70 60 50 40 30 20 10 KW BASED ON INDOOR ENT AIR AT 70 F AND AT RATED CFM 80 38YZA030 32 FX4A030 38YZA036 32 FX4A036 38YZA048 32 FX4A048 38YZA024 32 FX4A030 38YZA060 32 FX4A060 38YZA042 32 FX4A042 23 4 20 5 17 6 14 7 11 7 8 8 5 9 2 9 38YZA018 32 FX4A018 ...

Страница 9: ...DR 12 00 10 30 24 600 3 28 15 500 2 24 7 40 CC5A CD5AA036 825 24 400 NONE 12 00 10 20 23 000 3 12 15 600 2 22 7 20 CD5AW036 825 24 400 NONE 12 00 10 20 23 000 3 12 15 500 2 22 7 20 CE3AA036 750 24 200 NONE 12 00 10 15 24 000 3 10 15 400 2 16 7 00 CF5AA036 825 24 200 NONE 11 70 10 20 23 200 3 14 15 500 2 20 7 20 CK3BA036 825 24 400 NONE 12 00 10 25 24 000 3 26 15 600 2 24 7 40 CK5A CK5BA036 825 24 ...

Страница 10: ...80 11 25 28 600 3 52 18 100 2 48 8 00 CK5A CK5BA036 1000 27 400 TDR 13 00 11 25 28 600 3 52 18 100 2 48 8 00 COILS 58MVP080 14 VARIABLE SPEED FURNACE CC5A CD5AA036 1000 27 400 TDR 12 80 11 40 28 600 3 54 18 000 2 50 8 00 CK5A CK5BA036 1000 27 200 TDR 13 00 11 40 28 600 3 54 18 000 2 50 8 00 COILS 58MVP080 20 VARIABLE SPEED FURNACE CD5AW036 1000 27 400 TDR 12 50 11 25 28 600 3 52 18 100 2 48 8 00 C...

Страница 11: ...50 34 200 TDR 13 11 45 36 000 3 64 22 200 2 6 8 3 CK5A CK5BA048 1050 34 400 TDR 13 1 11 55 36 000 3 7 22 600 2 68 8 5 CK5A CK5BT042 1050 34 200 TDR 13 11 45 35 800 3 64 22 200 2 6 8 3 CK5A CK5BT048 1050 34 400 TDR 13 1 11 55 36 000 3 7 22 600 2 68 8 5 CK5A CK5BW048 1050 34 400 TDR 13 1 11 55 36 000 3 7 22 600 2 68 8 5 CK5PA042 1050 34 200 TDR TXV 13 11 45 35 800 3 64 22 200 2 6 8 3 CK5PA048 1050 3...

Страница 12: ...URNACE CE3AA048 1225 40 000 TDR 12 7 11 41 000 3 34 25 600 2 46 7 5 CK3BA048 1225 40 000 TDR 12 8 11 05 41 000 3 38 25 600 2 46 7 6 CK5A CK5BA048 1225 40 000 TDR 12 8 11 05 41 000 3 38 25 400 2 48 7 6 CK5A CK5BT048 1225 40 000 TDR 12 8 11 05 41 000 3 38 25 400 2 48 7 6 CK5PA048 1225 40 000 TDR TXV 12 8 11 05 41 000 3 38 25 400 2 48 7 6 CK5PT048 1225 40 000 TDR TXV 12 8 11 05 41 000 3 38 25 400 2 4...

Страница 13: ...8 10 40FK A B FK4 C D NB006 1400 46 500 TDR 13 50 12 05 48 000 3 76 27 600 2 54 8 30 40FK A B FK4 C D NF005 1400 45 500 TDR 13 00 11 60 47 500 3 58 27 800 2 46 8 20 COILS 58CV A X 090 16 VARIABLE SPEED FURNACE CE3AA060 1400 44 500 TDR 12 9 11 4 47 500 3 64 27 400 2 5 8 5 COILS 58CV A X 110 22 VARIABLE SPEED FURNACE CD5PX060 1400 45 000 TDR TXV 13 4 11 7 48 000 3 68 27 600 2 5 8 5 CE3AA060 1400 45 ...

Страница 14: ... 1400 45 000 TDR 13 00 11 45 48 000 3 54 27 800 2 44 8 20 CK3BA060 1400 44 500 TDR 13 00 11 25 47 500 3 50 27 800 2 40 8 00 CK5A CK5BA060 1400 44 500 TDR 13 00 11 25 47 500 3 50 27 800 2 40 8 00 CK5A CK5BX060 1400 45 000 TDR 13 00 11 45 48 000 3 54 27 800 2 44 8 20 COILS 58MVP120 20 VARIABLE SPEED FURNACE CC5A CD5AA060 1400 44 500 TDR 13 00 11 30 47 500 3 52 27 800 2 40 8 00 CC5A CD5AW060 1400 45 ...

Страница 15: ...16 4 1 51 15 8 15 8 1 69 15 15 1 89 14 1 14 1 2 12 13 1 13 1 2 36 57 17 3 17 3 1 34 16 6 16 6 1 5 15 8 15 8 1 69 15 15 1 89 14 1 14 1 2 12 13 1 13 1 2 36 675 72 20 9 11 2 1 39 19 9 10 9 1 56 18 8 10 5 1 74 17 6 10 1 1 95 16 3 9 68 2 17 14 9 9 21 2 41 67 19 1 14 7 1 38 18 2 14 4 1 55 17 2 14 1 73 16 1 13 5 1 93 15 13 1 2 15 13 7 12 6 2 4 63 17 8 14 2 1 37 17 13 9 1 53 16 13 5 1 72 15 13 1 92 13 9 1...

Страница 16: ...3 23 1 23 1 2 04 22 1 22 1 2 26 20 9 20 9 2 51 19 6 19 6 2 78 18 2 18 2 3 06 950 72 29 7 15 6 1 89 28 2 15 1 2 10 26 5 14 5 2 34 24 8 14 0 2 59 22 9 13 4 2 86 20 9 12 7 3 14 67 27 2 20 4 1 88 25 8 19 8 2 09 24 3 19 3 2 32 22 8 18 7 2 57 21 1 18 0 2 84 19 2 17 3 3 11 63 25 4 19 8 1 87 24 1 19 2 2 08 22 7 18 6 2 31 21 2 18 0 2 55 19 7 17 3 2 82 18 0 16 6 3 09 62 25 2 24 8 1 87 24 0 24 0 2 08 22 8 22...

Страница 17: ... 1200 72 33 8 18 8 2 13 32 0 18 1 2 35 30 1 17 5 2 60 28 1 16 8 2 86 25 8 16 0 3 16 23 3 15 2 3 47 67 31 8 25 5 2 13 30 1 24 9 2 34 28 4 24 2 2 59 26 3 23 4 2 85 24 3 22 5 3 15 22 0 21 4 3 46 63 29 9 24 8 2 12 28 1 24 0 2 33 26 5 23 3 2 58 24 9 22 6 2 85 23 0 21 7 3 15 21 0 20 7 3 48 62 30 3 30 3 2 12 28 8 28 8 2 34 27 4 27 4 2 59 25 7 25 7 2 85 23 9 23 9 3 15 22 0 22 0 3 47 57 30 3 30 3 2 12 28 7...

Страница 18: ... 7 32 7 3 33 30 9 30 9 3 67 28 9 28 9 4 03 26 7 26 7 4 42 57 36 0 36 0 2 72 34 4 34 4 3 01 32 7 32 7 3 33 30 9 30 9 3 67 28 9 28 9 4 03 26 7 26 7 4 42 Indoor Section Size Cooling Indoor Section Size Cooling Capacity Power Capacity Power CC5A CD5AA 042 1 00 1 00 COILS 58CV A X 110 22 VARIABLE SPEED FURNACE CC5A CD5AC 048 1 00 0 98 CD5AA 048 1 01 0 91 CC5A CD5AW 042 1 00 0 98 CE3AA 048 1 01 0 91 048...

Страница 19: ...34 8 34 8 2 63 33 3 33 3 2 92 31 7 31 7 3 23 30 0 30 0 3 57 28 1 28 1 3 94 26 0 26 0 4 32 1500 72 41 4 22 2 2 73 39 3 21 5 3 02 37 1 20 7 3 34 34 6 19 8 3 70 32 1 18 9 4 06 29 2 18 0 4 45 67 38 4 29 9 2 72 36 5 29 1 3 01 34 4 28 3 3 33 32 1 27 4 3 68 29 7 26 4 4 04 27 1 25 2 4 42 63 35 8 28 9 2 72 34 0 28 1 3 01 32 0 27 2 3 32 29 9 26 3 3 66 27 6 25 3 4 02 25 2 24 1 4 40 62 36 0 36 0 2 72 34 4 34 ...

Страница 20: ...58 39 2 39 2 3 98 37 1 37 1 4 42 34 9 34 9 4 90 32 4 32 4 5 41 Indoor Section Size Cooling Indoor Section Size Cooling Capacity Power Capacity Power CC5A CD5AC 048 0 98 1 07 CK3BA 048 0 99 0 97 CC5A CD5AW 048 0 99 1 08 CK5A CK5BA 048 0 99 0 97 CD5AA 048 0 99 1 08 CK5A CK5BT 048 0 99 0 97 CE3AA 048 1 00 1 08 CK5A CK5BW 048 0 99 0 97 CK3BA 048 0 99 1 08 CK5PA 048 0 99 0 97 CK5A CK5BA 048 0 99 1 08 C...

Страница 21: ... 49 4 3 51 47 6 47 6 3 87 45 5 45 5 4 28 43 3 43 3 4 74 41 2 41 2 5 26 38 5 38 5 5 81 57 49 8 49 8 3 51 47 7 47 7 3 88 45 6 45 6 4 29 43 5 43 5 4 75 40 9 40 9 5 24 38 4 38 4 5 79 Indoor Section Size Cooling Indoor Section Size Cooling Capacity Power Capacity Power CC5A CD5AA 060 0 98 1 06 CK5A CK5BT 060 0 98 0 98 CC5A CD5AW 060 0 98 1 06 CK5A CK5BX 060 1 00 0 99 CE3AA 060 1 00 1 06 CK5PA 060 0 98 ...

Страница 22: ...0 1 7 04 52 3 28 6 7 77 67 64 9 45 1 4 63 61 9 43 9 5 13 58 8 42 6 5 68 55 7 41 4 6 29 52 2 40 0 6 95 48 4 38 5 7 68 63 61 1 44 2 4 60 58 0 42 8 5 08 55 5 41 7 5 65 52 5 40 4 6 26 49 3 39 0 6 93 45 6 37 4 7 66 62 60 3 55 1 4 59 57 3 53 6 5 07 54 6 52 3 5 62 51 7 50 8 6 23 48 8 48 8 6 90 45 8 45 8 7 64 57 58 7 58 7 4 57 56 2 56 2 5 06 54 0 54 0 5 61 51 5 51 5 6 23 48 9 48 9 6 91 45 9 45 9 7 65 2000...

Страница 23: ...3 5 1 76 675 6 83 6 28 1 38 8 68 7 97 1 42 10 5 9 58 1 45 12 5 11 1 1 47 14 8 13 4 1 51 17 4 17 4 1 56 20 3 20 3 1 63 23 7 23 7 1 73 75 525 6 35 5 84 1 45 8 24 7 57 1 51 10 2 9 26 1 56 12 1 10 8 1 61 14 3 13 0 1 66 16 8 16 8 1 73 19 6 19 6 1 81 22 9 22 9 1 93 600 6 48 5 96 1 46 8 38 7 70 1 50 10 3 9 36 1 55 12 3 10 9 1 59 14 5 13 2 1 63 17 0 17 0 1 69 19 8 19 8 1 76 23 2 23 2 1 87 675 6 60 6 07 1 ...

Страница 24: ... 19 1 2 06 24 3 24 3 2 11 28 0 28 0 2 16 31 1 31 1 2 20 75 700 10 2 9 37 2 02 12 6 11 6 2 06 15 0 13 7 2 11 17 4 15 4 2 14 20 1 18 3 2 19 23 2 23 2 2 26 26 9 26 9 2 36 30 9 30 9 2 46 825 10 4 9 58 2 04 12 8 11 8 2 07 15 2 13 9 2 10 17 6 15 7 2 12 20 4 18 6 2 16 23 6 23 6 2 22 27 4 27 4 2 31 31 0 31 0 2 36 950 10 6 9 78 2 06 13 1 12 0 2 08 15 4 14 1 2 10 17 9 15 9 2 12 20 7 18 8 2 15 24 0 24 0 2 21...

Страница 25: ...6 0 2 32 20 9 18 5 2 37 24 7 22 5 2 44 29 2 29 2 2 54 34 3 34 3 2 66 40 3 40 3 2 81 1050 11 8 10 8 2 24 14 8 13 6 2 29 17 8 16 2 2 33 21 2 18 8 2 37 25 1 22 8 2 43 29 6 29 6 2 52 34 9 34 9 2 64 40 8 40 8 2 76 1200 12 0 11 0 2 28 15 0 13 8 2 32 18 0 16 4 2 35 21 5 19 1 2 39 25 4 23 1 2 44 30 0 30 0 2 52 35 4 35 4 2 63 41 1 41 1 2 74 Indoor Section Size Heating Indoor Section Size Heating Capacity P...

Страница 26: ...ection Size Heating Capacity Power Capacity Power CC5A CD5AA 042 0 99 1 01 CK5A CK5BA 042 0 97 0 92 CC5A CD5AC 048 0 98 1 02 048 0 97 0 91 CC5A CD5AW 042 0 98 1 01 CK5A CK5BT 042 0 97 0 92 048 0 98 0 98 048 0 97 0 91 CD5AA 048 0 99 0 99 CK5A CK5BW 048 0 97 0 91 CE3AA 042 0 99 0 98 CK5PA 042 0 97 0 92 048 0 99 0 97 048 0 97 0 91 CF3AA 036 0 98 1 00 CK5PT 042 0 97 0 92 CF5AA 048 0 97 0 97 048 0 97 0...

Страница 27: ...7 0 3 13 43 3 43 3 3 35 50 7 50 7 3 64 1500 15 7 14 4 2 52 19 5 17 9 2 62 23 4 21 3 2 74 27 5 24 4 2 85 32 2 29 3 2 98 37 6 37 6 3 14 44 1 44 1 3 35 51 6 51 6 3 62 75 1050 14 4 13 2 2 53 18 1 16 7 2 66 22 2 20 2 2 81 26 2 23 3 2 96 30 7 27 9 3 13 35 7 35 7 3 33 41 7 41 7 3 58 48 7 48 7 3 90 1275 14 8 13 6 2 58 18 7 17 1 2 69 22 7 20 7 2 83 26 7 23 7 2 96 31 3 28 5 3 11 36 5 36 5 3 28 42 6 42 6 3 5...

Страница 28: ...ng Indoor Section Size Heating Capacity Power Capacity Power CC5A CD5AC 048 0 98 1 08 CK5A CK5BA 048 1 00 0 98 CC5A CD5AW 048 1 00 1 02 CK5A CK5BT 048 1 00 0 98 CD5AA 048 1 00 1 02 CK5A CK5BW 048 1 00 0 98 CE3AA 048 1 02 1 04 CK5PA 048 1 00 0 98 CK3BA 048 1 02 1 03 CK5PT 048 1 01 0 99 CK5A CK5BA 048 1 02 1 03 CK5PW 048 1 00 0 98 CK5A CK5BW 048 1 02 1 03 COILS 58CV A X 155 22 VARIABLE SPEED FURNACE...

Страница 29: ... 30 5 3 94 40 9 37 2 4 10 48 6 48 6 4 31 56 7 56 7 4 49 63 7 63 7 4 69 Indoor Section Size Heating Indoor Section Size Heating Capacity Power Capacity Power CC5A CD5AA 060 1 01 1 12 CK5A CK5BT 060 1 00 1 00 CC5A CD5AW 060 1 01 1 06 CK5A CK5BX 060 1 00 1 00 CE3AA 060 1 02 1 08 CK5PA 060 1 00 1 00 CK3BA 060 1 02 1 04 CK5PT 060 1 00 1 00 CK5A CK5BA 060 1 01 1 03 CK5PX 060 1 00 0 99 CK5A CK5BX 060 1 0...

Страница 30: ...24 7 4 10 33 0 30 3 4 23 39 2 35 7 4 35 45 8 40 6 4 46 53 5 48 7 4 61 62 6 62 6 4 80 73 4 73 4 5 06 84 1 84 1 5 27 2250 27 3 25 1 4 17 33 5 30 8 4 29 39 6 36 1 4 39 46 3 41 1 4 49 54 2 49 3 4 62 63 3 63 3 4 80 74 4 74 4 5 02 84 0 84 0 5 20 70 1750 25 3 23 3 4 20 31 8 29 2 4 38 38 3 34 9 4 55 44 7 39 7 4 69 52 2 47 5 4 86 60 9 60 9 5 08 71 3 71 3 5 37 83 2 83 2 5 68 2000 25 9 23 8 4 26 32 4 29 8 4 ...

Страница 31: ...ms 8 and 9 following 8 For interconnecting refrigerant tube lengths greater than 50 ft and or elevation differences between indoor and outdoor units greater than 20 ft consult Application Guide line and Service Manual Air Conditioners and Heat Pumps Using Puron Refrigerant 9 If ANY refrigerant tubing is buried provide a minimum 6 in vertical rise to the valve connections at the unit Refrigerant tu...

Страница 32: ... be constructed of galvanized steel bonderized and coated with a powder coat paint Fans Condenser fan will be direct drive propeller type discharging air upward Air Cooled Split System Heat Pump 38YZA 1 1 2 to 5 Tons Nominal Condenser fan motors will be totally enclosed 1 phase type with class B insulation and permanently lubricated bearings Shafts will be corrosion resistant Fan blades will be st...

Отзывы: