The thermostat supports the following types of constant volume units:
•
Standard heat/cool unit types with up to 3 stages of mechanical cooling, up to 2 stages of gas or electric
heating, and up to 4 stages for non-Carrier heat pumps
•
Heat pump units utilizing a reversing valve output for heating and cooling control
•
Carrier heat pump unit with an OEM defrost control board
NOTES
•
Humidification or dehumidification control strategies are available for appropriately equipped units
•
You can use the optional 6th relay for only
one
of the following functions:
○
Reversing valve
○
Third-stage cooling
○
Humidification
○
Dehumidification
Occupancy
Configure the thermostat to operate in a programmable or non-programmable mode. Non-programmable operates
continuously in occupied mode. Programmable operates as a 7-day programmable thermostat for either 2 or 4
periods per day. You can set each period as occupied or unoccupied.
If you configure
Smart Recovery
for 30 to 90 minutes, the occupied start time increases up to the maximum time,
in order to bring the space to the occupied setpoints at actual occupied time.
Supply fan
Configure the supply fan for
ON
or
AUTO
, in either occupied or unoccupied mode.
•
ON
– Fan runs continuously regardless of demand
•
AUTO
– Fan cycles heat or cool demand if there is a demand for humidity or dehumidification